Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Feb 10, 2026 |
| Due Date: | Feb 25, 2026 |
| Solicitation No: | 36C25526R0035 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Solicitation (Original)
- Original Published Date: Feb 10, 2026 09:23 am CST
- Original Date Offers Due: Feb 25, 2026 12:00 pm CST
- Inactive Policy: Manual
- Original Inactive Date: Jun 04, 2026
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: Z2NB - REPAIR OR ALTERATION OF HEATING AND COOLING PLANTS
-
NAICS Code:
- 238220 - Plumbing, Heating, and Air-Conditioning Contractors
-
Place of Performance:
STATEMENT OF WORK (SOW)
for
CONSTRUCTION PROJECT:
1. This contract is for CONSTRUCTION services for the work required to replace and upgrade steam safety valves within the steam boiler system in Building 75 at the Jefferson Barracks VA.
2. Description: Existing steam safety valves found within the steam boiler system in Building 75 are in need of replacement and upgrading so to improve facility safety and efficiency. To do so, this Scope of Work (SOW) will address a total of eight steam safety valves, which is comprised of two steam safety valves per each of the three separate boilers, one safety valve following the PRV station upstream of the deaerator, and one deaerator safety valve. All new work and equipment shall comply with VHA Directive 1810. The following outlines the SOW for the different valve types, with respect to their adjacent structure/function:
a. Steam Safety Valves on Boiler (SVB) SOW: Removal of two existing SVB per each of the three separate boilers, totally in six SVB to be removed. Installation of two new SVB per each of the three separate boilers, totaling in six SVB to be installed. All new SVB being installed will require flange reducers 2½ x 4 flange reducers, properly upsized drip 90 bowl/cups, upgraded A193 flange steam bolts, and other related materials to complete their proper installation. For all new SVB being installed, steam escape piping contiguous with drip 90 bowl/cup and/or vertically extending upwards through the roof of Building 75 may require modification. For each of the three separate boilers, the two new SVB being installed are to be similar but have unique specifications, as outlined below:
SVB type 1:
Relieve Boiler Steam at 130 psi (Set Point)
Relieve 80% of total steam capacity of 35,000 lbs/hr, or 28,000 lbs/hr
SVB shall be constructed of Cast Steel
SVB type 2:
Relieve Boiler Steam at 135 psi / Set Point
Relieve 100% total steam capacity of 35,000 lbs/hr, or 35,000 lbs/hr
SVB shall be constructed of Cast Steel
b. Safety Valve Following PRV (SVFPRV) SOW: The existing SVFPRV, located upstream of the Deaerator, is to be removed. In its place, a new Kunkle is to be installed. Its installation will require newly upgraded A193 flange steam bolts and other related materials to complete proper installation. The new Kunkle being installed must meet the following specifications: Relieve steam at 15 psi (Set Point)
Relieve steam capacity of 17,972 lbs/hr
Shall be constructed of Cast Steel c. Deaerator Safety Valve (DASV) SOW: The existing DASV is to be removed. In its place, a new DASV is to be installed, which must meet the following specifications: Relieve steam at 15 psi (Set Point)
Relieve steam capacity of 2,990 lbs/hr. The acceptable relief steam capacity is 500 lbs/hr to 1,000 lbs/hr.
Shall be constructed of Cast Steel
The contractor shall furnish all labor, supervision, materials, products, tools, equipment, temporary structures (including scaffolding), and any other resources necessary to complete the work as described in this SOW, whether specifically listed or implied by the scope. The contractor shall provide a high level of quality and workmanship. The contractor is responsible for the removal and disposal of any project-related equipment and materials. The contractor shall also assist relevant Building 75 personnel, or independently perform the following duties as required:
Safely shut down, including lock out tag out, of boilers and steam lines
Scaffolding set up and removal
Test the steam system for leaks upon completion of all valve installation
Safely restart steam system, including lock out tag out, and verify proper operations
3. Note: Contractor to abide by all work & requirements set in the final release for construction project specifications.
4. Project shall conform to all Records Management and Privacy Language.
5. The period of performance for this project will be 180 calendar days after NTP issue date.
- VA MEDICAL CENTER 4101 SOUTH 4TH STREET
- LEAVENWORTH , KS 66048
- USA
- Kevin M Farrell
- kevin.farrell@va.gov
- Feb 10, 2026 09:23 am CSTSolicitation (Original)
- Jan 27, 2026 03:15 pm CST Presolicitation (Updated)
Related Document
| Dec 8, 2025 | [Presolicitation (Original)] Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL |
| Jan 27, 2026 | [Presolicitation (Updated)] Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL |
| Feb 26, 2026 | [Solicitation (Updated)] Z2NB--657-26-110JB - Upgrade Boiler Safety Valves , STL |
See Also
Follow Z1DA--Replace Cast Iron Fittings 676-23-009 Active Contract Opportunity Notice ID 36C25226B0037 Related
VETERANS AFFAIRS, DEPARTMENT OF
Due by 10/14/2026
Follow ZION-EAST ENTRANCE STATION REHAB Active Contract Opportunity Notice ID 140P6026Q0063 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/15/2026
Follow NNSY DD4 DUCT INSULATION REPLACEMENT Active Contract Opportunity Notice ID N4008526R0254 Related
DEPT OF DEFENSE
Due by 9/21/2026
Follow MT-BOWDOIN NWR-HQ OFFICE FLOORS Active Contract Opportunity Notice ID 140FGA26Q0074 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/23/2026