Z2DZ--Refeed Electrical from Generator Room to ATS# 3
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Aug 12, 2025 |
| Due Date: | Aug 18, 2025 |
| Solicitation No: | 36C25925Q0638 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Solicitation (Updated)
- Updated Published Date: Aug 12, 2025 12:24 pm CDT
- Original Published Date: Jul 17, 2025 04:17 pm CDT
- Updated Date Offers Due: Aug 18, 2025 10:00 am CDT
- Original Date Offers Due: Aug 18, 2025 10:00 am CDT
- Inactive Policy: Manual
- Updated Inactive Date: Sep 17, 2025
- Original Inactive Date: Aug 23, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: Z2DZ - REPAIR OR ALTERATION OF OTHER HOSPITAL BUILDINGS
-
NAICS Code:
- 238210 - Electrical Contractors and Other Wiring Installation Contractors
-
Place of Performance:
Refeed Electrical from Generator Room to ATS #3
Vendor Questions and VA answers in red
CONTRACTOR Q&As #1 Question No. 1: How many days' notice do we need to provide to access the two ER rooms and pipe out of both?
Answer No. 1: Please provide an overall schedule to include the days that you will need access to the rooms as a submittal prior to start of work
Question No. 2: How long can each ER be shut down? And can both be shut down simultaneously, or will they need to be phased down?
Answer No. 2: Please provide an overall schedule to include the days that you will need access to the rooms as a submittal prior to start of work
Question No. 3: Is there a way to coordinate access to the 2 ER Rooms in the same day, shut down the ATS 3, which powers all or most of the hospitals MRI machines, and Panel EGR to tie it all in, in the same week and shut down ATS#3 and the panel feeding it, all in the same week?
Answer No. 3: Part 1: both ER rooms would be able to be closed at the same time, in doing so a barrier would have to be placed at the entrances, as only one tile can be out at a time otherwise.
Part 2: ATS-3 is critical and down time is limited to four hours in total, it can not be down for a week.
Question No. 4: What are the hours we can work, without noise affecting patients with drilling through concrete walls?
Answer No. 4: There is no best time to work. Patient occupancy fluctuates. COR work hours are 7:00am to 1530pm.
Question No. 5: What are the busiest days for MRIS?
Answer No. 5: It varies, as it supports our emergency patients as well as regularly scheduled patients, two weeks notice and coordination will ensure goal is met for outage.
Question No. 6: How long can we shut MRIS down?
Answer No. 6: No more than 4 hours. Provide schedule of work
Question No. 7: Do we need to shut down the Panel EGP, which supplies ATS #3 and features a 225 amp breaker, in order to work on it, or can we work on it while it's live?
Answer No. 7: Panel EGP is only energized when the generator is running, there will be no problem in shutting the main breaker off, located left of the panel in generator control gear, as long as electrical staff is made aware at the time, no notice would be required for this portion of the project. Question No. 8. Please confirm award contractor will have access to the emergency room during construction.
Answer No. 8: Yes, the contractor will have access to the emergency room, however, the COR will have to badge the contractors in
Question No. 9: Since construction will be performed in an active emergency room, will an ICRA plan be provided to all bidders?
Answer No. 9: Yes an ICRA will be provided to all bidders
Question No. 10: Can the VA specify conduit and wire size/type that needs to be installed?
Answer No. 10: 4) 4/0s 1) #4 ground, in a 2 1/2' or 3 conduit, contractor s choice.
Question No 11: Can an alternate route be considered? Outside above the canopy walkway possibly? This would keep us from having to go through ER areas.
Answer No. 11: Conduit needs to be ran with existing conduits, everything currently ran on the outside is for temporary equipment only, permanent utilities need to be physically secured and away from damage.
Question No. 12: Does the new feeder need to be in place and ready to terminate before we can demo the old feeder? Or can we demo old feeder as we install new feeder?
Answer No. 12: Yes, new feeder needs to be in place prior to demo of existing feeder, providing continuity of backup generator feed serving critical loads and patients.
Question No. 13: Please confirm if we can do all of the install during normal working hours.
Answer No. 13: Normal business hours would be best as this is an emergency room, which never shuts down.
- 6162 S WILLOW DR SUITE 300
- Greenwood Village , CO 80111
- USA
- Frances Basham (CO)
- Frances.Basham@va.gov
- Aug 12, 2025 12:24 pm CDTSolicitation (Updated)
- Jul 26, 2025 01:38 pm CDT Solicitation (Updated)
- Jul 17, 2025 04:17 pm CDT Solicitation (Original)
Related Document
| Jul 17, 2025 | [Presolicitation (Original)] Z2DZ--Refeed Electrical from Generator Room to ATS# 3 |
| Jul 17, 2025 | [Solicitation (Original)] Z2DZ--Refeed Electrical from Generator Room to ATS# 3 |
| Jul 26, 2025 | [Solicitation (Updated)] Z2DZ--Refeed Electrical from Generator Room to ATS# 3 |
See Also
Follow Z1DA--Replace Cast Iron Fittings 676-23-009 Active Contract Opportunity Notice ID 36C25226B0037 Related
VETERANS AFFAIRS, DEPARTMENT OF
Due by 10/14/2026
Follow ZION-EAST ENTRANCE STATION REHAB Active Contract Opportunity Notice ID 140P6026Q0063 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/15/2026
Follow NNSY DD4 DUCT INSULATION REPLACEMENT Active Contract Opportunity Notice ID N4008526R0254 Related
DEPT OF DEFENSE
Due by 9/21/2026
Follow MT-BOWDOIN NWR-HQ OFFICE FLOORS Active Contract Opportunity Notice ID 140FGA26Q0074 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/23/2026