Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Aug 5, 2025 |
| Due Date: | Aug 12, 2025 |
| Solicitation No: | 36C25525R0097 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Solicitation (Updated)
- Updated Published Date: Aug 05, 2025 09:26 am CDT
- Original Published Date: May 29, 2025 02:54 pm CDT
- Updated Date Offers Due: Aug 12, 2025 10:00 am CDT
- Original Date Offers Due: Jul 14, 2025 10:00 am CDT
- Inactive Policy: Manual
- Updated Inactive Date: Sep 11, 2025
- Original Inactive Date: Aug 13, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: Z1DA - MAINTENANCE OF HOSPITALS AND INFIRMARIES
-
NAICS Code:
- 238220 - Plumbing, Heating, and Air-Conditioning Contractors
-
Place of Performance:
We don't use the JB morgue too often. Most patients that pass at JB go directly to the funeral home. The morgue is only used with the veteran does not have funeral home plans in place. The backup plan is the patient will be transported to JC morgue until funeral home arrangements are made.
RFI #70. Sizing the temp units based on a preconstruction TAB report will not enable us to provide the proper pricing for our scope of work. This information needs to be available for us to include the correct pricing at the time of our bid not after we are awarded the project. Otherwise, it becomes and guess which usually drives the price up.
AHU-01-1 Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-01-2 Trane CSHX0035F3 (OR EQUIVALENT)Â (with electric heat), 7000 CFM Nominal, 5in Max ESP, Â 460V 3 Phase, MCA 179.8A, MOP 200A. Note: The contractor shall coordinate required electrical connection with the VA.
AHU-24-1 Trane CSH0050F4 (OR EQUIVALENT)Â (with electric heat), 10000 CFM nominal, 5in Max ESP, 460V 3 Phase, MCA 232.2A, MOP 250A. Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA..
AHU-51-1 Trane RSHX0080 (OR EQUIVALENT)Â (with electric heat), 12,800 CFM nominal, 4.8in Max ESP, 460V 3 Phase, MCA 329A, MOP 400A Note: 460V unavailable at building 24. The contractor shall coordinate required electrical connection with the VA. If alternate is used, unit must have adequate capacity for DOAS application.
The needs of the station and the temporary units are based on availability. The information provided is to ensure the contractor understands the situation and the need to ensure a maintenance team/ plan is made available by the subcontractor to avoid any issues with the temporary cooling during construction.
Power can be provided to the temporary units as follows:
Building 1: Feed the temporary AHU from 208V panel EMDP . Provide temporary transformer and connections as necessary.
Building 24: Feed the temporary AHU from 208V External Wireway . Provide temporary transformer and connections as necessary.
Building 51: Feed the temporary AHU from 208V switchboard MSB-51A . Provide temporary transformer and connections as necessary.
RFI #72, 73 & 108. We need the design team to provide the proper information on the steam trap sizing and placement. Including the traps at the units and any drip traps that might be required. This is a complicated issue that would need to be designed .by the design team .not the installing contractor. Drip traps are generally based on the pounds per hour capacity of the main. This information is not available to us.
Steam trap to be placed at the unit steam coil / humidifier.
Anticipated piping lengths do not require steam drip traps. Contractor to verify and report the piping lengths from steam mains.
STEAM TRAP SCHEDULE BASIS OF DESIGN
Â
MANUFACTURER
TRAP NO.
TRAP SIZE
MAX PRESSURE (PSI)
STEAM CONDENSATE LOAD
CONSTRUCTION
AHU-1-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
217
STAINLESS STEEL
AHU-1-02 HEATING COIL
SPIRAX SARCO
FT450-4.5
1"
15
276
STAINLESS STEEL
AHU-24-01 HEATING COIL
SPIRAX SARCO
FT450-4.5
1-1/2"
15
466
STAINLESS STEEL
AHU-51-01 HUMIDIFER
SPIRAX SARCO
FT450-4.5
3/4"
15
23
STAINLESS STEEL
NOTE: STEAM TRAP CONNECTION SHALL BE RAISED FACE FLANGE. Additional Information regarding RFIs 97 and 100:
3C06 As builts and site photos:
Condensate pumps in basement mechanical room GC18:
Location of the Steam supply and condensate return riser main connection to horizontal main.
No as-built of the steam condensate pump is available in Building 1, Room GC18. The steam riser main is 2-1/2 and the condensate return riser main is 2 based on as-built drawings available as noted above.
- VA MEDICAL CENTER 4101 SOUTH 4TH STREET
- LEAVENWORTH , KS 66048
- USA
- Sean P Jackson
- Sean.Jackson@va.gov
- Aug 05, 2025 09:26 am CDTSolicitation (Updated)
- Aug 04, 2025 10:01 am CDT Solicitation (Updated)
- Jul 24, 2025 10:10 am CDT Solicitation (Updated)
- Jul 17, 2025 03:49 pm CDT Solicitation (Updated)
- Jul 10, 2025 12:01 pm CDT Solicitation (Updated)
- May 29, 2025 02:54 pm CDT Solicitation (Original)
Related Document
| May 20, 2025 | [Presolicitation (Original)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| May 29, 2025 | [Solicitation (Original)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| Jul 10, 2025 | [Solicitation (Updated)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| Jul 17, 2025 | [Solicitation (Updated)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| Jul 24, 2025 | [Solicitation (Updated)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| Aug 4, 2025 | [Solicitation (Updated)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
| Sep 2, 2025 | [Award Notice (Original)] Z1DA--657-23-101JB FCA Replace Various Air Handling Units/Chillers Buildings 1, 24 and 51 |
See Also
Follow Z1DA--Replace Cast Iron Fittings 676-23-009 Active Contract Opportunity Notice ID 36C25226B0037 Related
VETERANS AFFAIRS, DEPARTMENT OF
Due by 10/14/2026
Follow ZION-EAST ENTRANCE STATION REHAB Active Contract Opportunity Notice ID 140P6026Q0063 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/15/2026
Follow NNSY DD4 DUCT INSULATION REPLACEMENT Active Contract Opportunity Notice ID N4008526R0254 Related
DEPT OF DEFENSE
Due by 9/21/2026
Follow MT-BOWDOIN NWR-HQ OFFICE FLOORS Active Contract Opportunity Notice ID 140FGA26Q0074 Related Notice
INTERIOR, DEPARTMENT OF THE
Due by 9/23/2026