4610--WATER PURIFICATION SYSTEM HAMPTON VAMC/DIALYSIS
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| Posted Date: | Feb 9, 2026 |
| Due Date: | Feb 17, 2026 |
| Solicitation No: | 36C24626Q0335 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Sources Sought (Original)
- Original Published Date: Feb 09, 2026 10:00 am EST
- Original Response Date: Feb 17, 2026 10:00 am EST
- Inactive Policy: Manual
- Original Inactive Date: Mar 19, 2026
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: 4610 - WATER PURIFICATION EQUIPMENT
-
NAICS Code:
- 333310 - Commercial and Service Industry Machinery Manufacturing
-
Place of Performance:
,
- Salient Characteristics
- Water Purification System that can produce not less than 200 liters of water per hour, fitted with deionization capabilities
- MODEL MEDICA-R 200
- Make-up rate 15C 200 l/hr
- Delivery flow rate maximum115V, 60Hz 21 l/min @ 45psi (3bar) Inorganics (resistivity @25°C) >10 M -cm (1)
- Organics (TOC) - typical - Particles 0.2 m filter Silica - Notes: 1 with Ion-exchange cylinder installed (Nuclear or Hypex grade resin), 2 subject to correct operating and maintenance procedures
- Feedwater Requirement:
- Source: Tap water as detailed below Conductivity: - Contaminant:
- Measure: Range: Pretreatment:
- Calcium: Ca ppm as CaCO3 - >250 Softener or use very low RO recovery3
- Free chlorine: Cl2ppm - 0.1 0.5 20 inch carbon block
- >0.5 Cylinder of carbon sized correctly to obtain - Chloramine: Cl2 ppm - 0.1 0.5 20 inch high efficiency carbon (5)
- >0.5 Cylinder of carbon sized correctly to obtain - Silica: SiO2 ppm - >30 20 inch cartridge depth filter or use very low RO recovery (4)
- Fouling index: FI - 10 to 20 20 inch cartridge depth filter
- >20 Back washable media filter with a minimum flow rate of 20 l/min
- Iron/manganese: Fe/Mn ppm - >0.05 20 inch cartridge depth filter (5)
- >0.1 Back-washable Fe filter (6)
- Organics: TOC ppm C - 2 to 3 20 inch carbon block (4)
- >3 Carbon sized Cylinder correctly for TOC demand (4) Temperature: 4 - 40°C (Recommended 15 - 25°C)
-- Flowrate: (requirement at 15°C) 20 l/min
- Drain requirements: (gravity fall with air gap) 45 l/min
- Feedwater pressure: 60psi (4bar) maximum, 30psi (2bar) minimum
- Notes: 3) Check LSI, increase frequency of acid cleaning, 4) Increase frequency of alkaline cleaning,
- 5) Please use ELGA Part Numbers LA683 (Filter Housing) and LC172 (Carbon Filter), 6) Increase frequency of acid cleaning Wall mount canister filter will need (Wall backing required)
- Must include Installation, Commissioning, Training
- Electrical Requirements Mains Input: 115V, 60Hz
- System control voltage (not including pumps and UV) 24V dc Power consumption (peak demand): 2000VA
- Electrical protection rating 20 amps Noise level during recirculation - ***Note: System requires approximately 4' x 6' of floor space for tanks, filtration Unit, and filters.
- -The floor drain must be a minimum of 3" and meet all applicable building codes and system requirements
- -Actual Unit measurement 32" Wide x35"Deep x72"High
- 100 EMANCIPATION DR
- HAMPTON , VA 23667
- USA
- John P Harmsen
- john.harmsen@va.gov
- Phone Number 757-722-7961
- Feb 09, 2026 10:00 am ESTSources Sought (Original)
Related Document
| Mar 18, 2026 | [Sources Sought (Updated)] 4610--WATER PURIFICATION SYSTEM HAMPTON VAMC/DIALYSIS |
See Also
Follow 46--FILTER ASSEMBLY,WATER Active Contract Opportunity Notice ID SPE8E826T5618 Related Notice Department/Ind. Agency
DEPT OF DEFENSE
Due by 9/28/2026
Follow 46--DEMINERALIZER,WATER,IO Active Contract Opportunity Notice ID SPE4A526T458U Related Notice Department/Ind. Agency DEPT
DEPT OF DEFENSE
Due by 9/28/2026
Follow 46--CELL AND VALVE ASSEMBL Active Contract Opportunity Notice ID SPE8E826T5707 Related Notice
DEPT OF DEFENSE
Due by 10/02/2026
Follow 46--FILTER ELEMENT,WATER P Active Contract Opportunity Notice ID SPE8E826T5697 Related Notice Department/Ind.
DEPT OF DEFENSE
Due by 10/01/2026