6140--UPS Replacement Batteries - Provision and Installation Services Topeka, KS
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Kansas |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Set Aside: | Total Small Business Set-Aside (FAR 19.5) |
| Posted Date: | Feb 6, 2025 |
| Due Date: | Feb 10, 2025 |
| Solicitation No: | 36C25925Q0144 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
- Updated Published Date: Feb 06, 2025 12:19 pm MST
- Original Published Date: Feb 05, 2025 01:17 pm MST
- Updated Date Offers Due: Feb 10, 2025 12:00 pm MST
- Original Date Offers Due: Feb 10, 2025 12:00 pm MST
- Inactive Policy: Manual
- Updated Inactive Date: Mar 12, 2025
- Original Inactive Date: Mar 12, 2025
-
Initiative:
- None
- Original Set Aside: Total Small Business Set-Aside (FAR 19.5)
- Product Service Code: 6140 - BATTERIES, RECHARGEABLE
-
NAICS Code:
- 335999 - All Other Miscellaneous Electrical Equipment and Component Manufacturing
-
Place of Performance:
VHA Member Services Call Center Building 9 Topeka , KS 66604USA
Q&A
Are there any access issues?
We have a dock and double doors to bring the batteries in.
Any doorways and floor covering needed?
No floor protection needed.
Are there any stairs or ladders to climb up or down to perform work and or transport batteries?
No
Is there a loading dock available and what is approximate distance from facility entrance to battery change out area?
There is a loading dock. There is nothing stopping you from going from truck to the hall outside the rooms they are in.
Is there an elevator that requires a breakdown of each battery pallet before reaching the change out area?
No
Are there any narrow doorways or hallways (or heavy carpeting) or raised/access floor to transit that would require breakdown of each battery pallet before reaching the change out area?
No
Is there a battery monitoring system to dis-engage and re-engage and test before job completion?
Yes, but it is internal.
Is there a forklift, pallet jack or carts available to use?
No, can only use pallet jack.
1 room is on the ground floor.
2 rooms are on the first floor.
1 room is on the 2nd floor.
The following images have been included to provide more specifications on the UPS machines the replacement batteries will be used for.
1. Room C-136 (1st floor), (40) 12HX400-FR Current UPS: Vertiv Liebert Npower 2. Room B-112 (1st floor), (40) 12HX300-FR Current UPS: Vertiv Liebert Npower 3. Room B-215 (2nd floor), (40) 12HX300-FR Current UPS: Vertiv Liebert Npower
4. Room B-014 (Ground floor), (24) 12HX300-FR Current UPS: Vertiv Liebert EXM
- 6162 S WILLOW DR SUITE 300
- Greenwood Village , CO 80111
- USA
- Stephanie Cahill
- Stephanie.Cahill@va.gov
- Phone Number 303-712-5841
- Feb 06, 2025 12:19 pm MSTCombined Synopsis/Solicitation (Updated)
- Feb 05, 2025 03:14 pm MST Combined Synopsis/Solicitation (Updated)
- Feb 05, 2025 01:17 pm MST Combined Synopsis/Solicitation (Original)