Transportation Daytona Beach - Replace Emergency Generator

Agency: Volusia County Schools
State: Florida
Type of Government: State & Local
NAICS Category:
  • 238210 - Electrical Contractors and Other Wiring Installation Contractors
  • 811310 - Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
Posted Date: Jul 21, 2026
Due Date: Aug 27, 2026
Solicitation No: Project No. 2648204
Original Source: Please Login to View Page
Contact information: Please Login to View Page
Bid Documents: Please Login to View Page
Transportation Daytona Beach - Replace Emergency Generator - Project No. 2648204
Mandatory Prebid Meeting: August 14, 2026 at  9:00 AM
Bid: August 27, 2026 at  1:00 PM
Project Bid Documents: Plans
Project Manual
Estimate: $233,649.87
Consultant: SGM Engineering, Inc.
Mark Escott

(407) 767-5188
Owner: VCS Project Manager
Jim Bott

(386) 947-8786
Bid Status: Active

Attachment Preview

VOLUSIA
COUNTY SCHOOLS
"LEADING WITH GRACE AND RESPECT"
THE SCHOOL BOARD OF VOLUSIA
COUNTY FLORIDA
200 North Clara Avenue
Deland, Florida 32720
TRANSPORTATION
DAYTONA BEACH
REPLACE EMERGENCY
GENERATOR
VCS Project NO. 2648204
1648 Hancock Blvd.
Daytona Beach, FL 32114
SCHOOL BOARD
MEMBERS
RUBEN COLON
KRISTA GOODRICH
JAMIE HAYNES
JESSIE THOMPSON
DONNA BROSEMER
BOARD CHAIR
BOARD VICE CHAIR
MEMBER
MEMBER
MEMBER
CARMEN J. BALGOBIN
SUPERINTENDENT
DESCRIPTION OF WORK
A. Scope of Services
1. Replace existing 60KW, 75KVA 208V, 3PH, 4W generator serving the complex. This includes
replacement of the ATS's, generator annunciator, water jacket heater, battery charger and
conductors.
2. Replace 3 existing ATS's. One at each of the following locations; fuel island building, maintenance
and operations.
3. Replace feeder wire from generator to generator distribution panel GDP.
4. Provide overcurrent device coordination study and arc flash labeling for all new equipment,
disconnects, transfer switches and panels.
5. This scope is not all inclusive and is complimented by the set of drawings and specifications.
Engineer's Statement of Compliance
To the best of my knowledge, these drawings and the project manual are complete and comply with
the 2023 Florida Building Code 8th edition.
BUILDING DATA
A. SURVEY PARCEL ID
B. LEGAL DESCRIPTION
C. OCCUPANCY TYPE
D. CONSTRUCTION TYPE
E. RISK CATEGORY
F. AUTOMATIC SPRINKLER
G. BUILDING AREA
H. BUILDING HEIGHT
I. OCCUPANT LOAD
XXX
XXX
EDUCATIONAL
XXX
XXX
XXX
XXX
XXX
XXX
LOCATION MAP
ENGINEERS & CONSULTANTS
ELECTRICAL
SGM ENGINEERING
935 LAKE BALDWIN LANE
ORLANDO, FL 32814
407-767-5188
MARK ESCOTT
MARK@SGMENGINEERING.COM
WWW.SGMENGINEERING.COM
G001
COVER SHEET
ELECTRICAL
ALL WORK COMPLETED UNDER THE SCOPE OF THIS PROJECT SHALL, AS A MINIMUM, COMPLY WITH THE
LAWS, RULES, STANDARDS AND DECISIONS WITH THE LATEST AMENDMENTS OF THE GOVERNMENTAL
UNITS HAVING STATUTORY JURISDICTION OVER THIS PROJECT:
a. FLORIDA BUILDING CODES 8TH EDITION (2023)
b. NATIONAL ELECTRIC CODE, NFPA 70 (2020)
c. NATIONAL FIRE-ALARM CODE, NFPA 72 (2019)
d. FLORIDA FIRE PREVENTION CODE 8TH EDITION (2023)
e. STATE REQUIREMENTS FOR EDUCATIONAL FACILITIES (SREF) - 2014 ED.
f. FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA)
E001
ED101
ED301
ED302
ED303
E101
E301
E302
E303
E501
E701
E801
ELECTRICAL SYMBOLS
DEMO ELECTRICAL SITE PLAN
DEMO ELECTRICAL FLOOR PLAN MAINTENANCE BLD
DEMO ELECTRICAL FLOOR PLAN BUS WASH & FUEL ISLAND
DEMO ELECTRICAL FLOOR PLAN OPS BUILDING
ELECTRICAL SITE PLAN
ELECTRICAL FLOOR PLAN MAINTENANCE BLDG
ELECTRICAL FLOOR PLAN BUS WASH & FUEL ISLAND
ELECTRICAL FLOOR PLAN OPS BUILDING
ONE LINE DIAGRAM
ELECTRICAL PANEL SCHEDULES
ELECTRICAL DETAILS
CA-00006208
935 Lake Baldwin Lane
Orlando, Fl. 32814
Tel: 407-767-5188
Fax: 407-767-5772
www.sgmengineering.com
Copyright © 2025 SGM Engineering, Inc.
SGM #: 2025-393
NOT TO SCALE
CONSTRUCTION DOCUMENTS 02-06-2026
ENGINEER
MARK A. ESCOTT
DESIGNED BY
DRAWN BY
ENGR OF RECORD
ISSUE DATE
02/06/2026
AE PROJECT NUMBER
2025-393
SHEET TITLE
COVER SHEET
DRAWING NO.
G001
POWER DISTRIBUTION
120/208V PANELBOARD, RECESSED
120/208V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, SURFACE MOUNT
277/480V PANELBOARD, RECESSED
1R1-1
FEEDER OR BRANCH CIRCUIT CONCEALED IN WALL,
CEILING OR FLOOR
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 1-POLE CIRCUIT, SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
1M1-1:3
HOMERUN CONSISTING OF ONE SINGLE-PHASE, 2-P0LE CIRCUIT:
SEE SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE
SIZES. PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
SWITCHES
S
SWITCH
SM
MOTOR RATED SWITCH
SEXP
SL
SWITCH, EXPLOSION PROOF
SWITCH, LOW VOLTAGE MOMENTARY, HUBBELL I-557I OR EQUAL
SWP
SWITCH, WEATHERPROOF
MISCELLANEOUS SYMBOL LEGEND
DETAIL NUMBER
TITLE 1
E200 SCALE:
DETAIL TITLE REFERENCE
E200
SHEET NUMBER WHERE DETAIL IS REFERENCED
ADDITIONAL SHEET REFERENCES
1R1-1,3
HOMERUN CONSISTING OF TWO SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATION ARE INDICATED.
1R1-1,3,5
HOMERUN CONSISTING OF THREE SINGLE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
1M1-1:3:5
HOMERUN CONSISTING OF ONE THREE-PHASE CIRCUITS: SEE
SPECIFICATIONS AND/OR FEEDER SCHEDULES FOR WIRE SIZES.
PANELBOARD AND CIRCUIT DESIGNATIONS ARE INDICATED.
POWER DEVICES
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
SPECIAL PURPOSE RECEPTACLE
SINGLE 250V NON-LOCKING TYPE RECEPTACLE
G
DUPLEX RECEPTACLE, GROUND FAULT
G
DUPLEX RECEPTACLE, GROUND FAULT, ABOVE COUNTER
G
QUAD RECEPTACLE, GROUND FAULT
WP
DUPLEX RECEPTACLE, GROUND FAULT WITH CAST ALUMINUM
PADLOCKABLE (1/4" HASP) WEATHERPROOF "IN USE" COVER.
TAYMAC MX3200 OR EQUAL
WP
EWC
G
C
G
C
G
TV
QUAD RECEPTACLE, GROUND FAULT WITH CAST ALUMINUM
PADLOCKABLE (41" HASP) WEATHERPROOF "IN USE"
COVER. TAYMAC MX 6200 OR EQUAL.
DUPLEX RECEPTACLE LOCATED WITHIN ELECTRIC WATER
COOLER PER MANUFACTURER'S INSTRUCTIONS. CIRCUIT
BREAKER IS TO BE GFCI.
DUPLEX RECEPTACLE, GROUND FAULT FOR COMPUTER
WORKSTATION
QUAD RECEPTACLE, GROUND FAULT FOR COMPUTER
WORKSTATION
DUPLEX RECEPTACLE, GROUND FAULT FOR TV LOCATED AT 84"
AFF UNLESS NOTED OTHERWISE.
C
CLOCK
PD
POWER/DATA POLE
PP
POWER POLE
DISCONNECT SWITCH
MOTOR STARTER
STARTER/DISCONNECT SWITCH
VFD
VARIABLE FREQUENCY DRIVE
J
JUNCTION BOX
J
FLOOR MOUNTED JUNCTION BOX
PB
PULL BOX
C
EQUIPMENT CONNECTION
PUSH BUTTON
T
TRANSFORMER
ST
SHUNT TRIP. MTD. AT 6'-5" AFF/AFG TO TOP OF ENCLOSURE
SM
JUNCTION BOX WITH MOTOR RATED SWITCH
MOTOR
XX
XX.XX
DETAIL NUMBER
SHEET NUMBER TO WHERE DETAIL IS REFERENCED
ABBREVIATIONS
A
AMPERES
MCB
AE
AUDIO ENHANCEMENT
MCC
AFC
ABOVE FINISHED CEILING
MCP
AFF
ABOVE FINISHED FLOOR
MFR
AFG
ABOVE FINISHED GRADE
MH
AIC
AL
AWG
BFC
BFG
C
CAB
CKT
CLG
CL
CT's
CU
DISC
DWG
EA
ECB
EF
EMT
EQUIP
EUH
EWC
EWH
EXH
EXIST
EXP
AMPERES INTERUPTING
MIN
CAPACITY
MISC
ALUMINUM
MLO
AMERICAN WIRE GAUGE
MMS
BELOW FINISHED CEILING
MTR
BELOW FINISHED GRADE
MTD
CONDUIT
MTG
CABINET
NAC
CIRCUIT
NEC
CEILING
NL
CENTERLINE
PNL
CURRENT TRANSFORMERS PSI
COPPER
PVC
DISCONNECT(ING)
REC
DRAWING(S)
RGS
EACH
SPD
ENCLOSED CIRCUIT BREAKER TEL
EXHAUST FAN
TYP
ELECTRICAL METALLIC TUBING UON
EQUIPMENT
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
EXHAUST
EXISTING
V
VA
VFD
W
WP
XFMR
EXPLOSION PROOF
FA
FIRE ALARM
FLA
FULL LOAD AMPERES
FLUOR FLUORESCENT
GFCI
GROUND FAULT CIRCUIT
INTERRUPTER
GFP
GROUND FAULT PROTECTION
GND
GROUND
HGT
HEIGHT
HID
HIGH INTENSITY DISCHARGE
HPS
HIGH PRESSURE SODIUM
HOA
HAND-OFF-AUTOMATIC
HP
HORSEPOWER
HVAC HEATING/VENTILATING/
AIR CONDITIONING
HV
HIGH VOLTAGE
INC
INCANDESCENT
JB
JUNCTION BOX
kV
KILO-VOLTS
kVA
KILO-VOLTS-AMPERES
kVAR KILO-VOLTS-AMPERES REACTIVE
kW
KILO-WATTS
kWH
KILO-WATT-HOURS
LTG
LIGHTING
m
METER
mm
MILLIMETER
MAX
MAXIMUM
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MOTOR CIRCUIT PROTECTOR
MANUFACTURER
METAL HALIDE
MINIMUM
MISCELLANEOUS
MAIN LUG ONLY
MANUAL MOTOR STARTER SWITCH
MOTOR
MOUNTED
MOUNTING
NOTIFICATION APPLIANCE CIRCUIT
NATIONAL ELECTRICAL CODE
NIGHT LIGHT, UNSWITCHED
PANEL
PULL STATION INSIDE
POLYVINYL CHLORIDE
RECEPTACLE
RIGID GALVANIZED STEEL
SURGE PROTECTION DEVICE
TELEPHONE
TYPICAL
UNLESS OTHERWISE NOTED
VOLTS
VOLT-AMPERES
VARIABLE FREQUENCY DRIVE
WATTS
WEATHER PROOF
TRANSFORMER
G
GENERATOR
LB
LOCKBOX
GROUND BUS BAR
GROUND ROD WITH TEST INSPECTION WELL. SEE
SPECIFICATIONS.
SPD
SURGE PROTECTION DEVICE, SEE SPECIFICATIONS.
CA-00006208
935 Lake Baldwin Lane
Orlando, Fl. 32814
Tel: 407-767-5188
Fax: 407-767-5772
www.sgmengineering.com
Copyright © 2025 SGM Engineering, Inc.
SGM #: 2025-393
ENGINEER
MARK A. ESCOTT
DESIGNED BY
DRAWN BY
ENGR OF RECORD
ISSUE DATE
02/06/2026
AE PROJECT NUMBER
2025-393
SHEET TITLE
ELECTRICAL SYMBOLS
DRAWING NO.
E001
N
DEMO ELECTRICAL SITE PLAN
SCALE: 1/32"=1'-0"
0
16'
32'
64'
80KW 1
GENERATOR
2
CA-00006208
935 Lake Baldwin Lane
Orlando, Fl. 32814
Tel: 407-767-5188
Fax: 407-767-5772
www.sgmengineering.com
Copyright © 2025 SGM Engineering, Inc.
SGM #: 2025-393
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO EQUIPMENT SCHEDULES ON DRAWINGS 601 FOR DISCONNECT,
CONDUIT AND WIRE SIZES.
d. EXACT LOCATIONS OF UNDERGROUND UTILITIES ARE TO BE VERIFIED PRIOR
TO BEGINNING WORK.
e. UNLESS OTHERWISE NOTED, WHERE EXISTING CONDUITS AND CONDUCTORS
ARE NOTED TO BE REMOVED, THEY ARE TO BE REMOVED IN THEIR ENTIRETY
BACK TO THE POINT OF ORIGIN.
f. ALL DEMOLISHED EQUIPMENT AND FIXTURES NOTED TO BE SALVAGED, SHALL
BE DELIVERED TO THE OWNER. TRANSPORT ITEMS TO OWNERS DESIGNATED
STORAGE AREA WITHIN 25 MILES OF THE SITE. SHOULD THE OWNER DECIDE
NOT TO RECEIVE THESE ITEMS, THE CONTRACTOR WILL REMOVE FROM THE
SITE AND DISPOSE IN A LEGAL MANNER TO AN EPA APPROVED LANDFILL.
COMPLY WITH ALL NATIONAL, STATE AND LOCAL REQUIREMENTS WITH REGARD
TO HAZARDOUS MATERIALS REMOVAL, HANDLING AND DISPOSAL.
g. REMOVE ALL CONDUIT AND WIRE, FROM REMOVED ITEMS, BACK TO THE
SOURCE UNLESS IT IS TO BE RE-USED FOR NEW WORK.
h. VISIT THE EXISTING FACILITY AND CAREFULLY EXAMINE THOSE PORTIONS OF
THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING
PROPOSALS, SO AS TO BECOME FAMILIAR WITH THE EXISTING CONDITIONS
AND DIFFICULTIES THAT WILL AFFECT THE EXECUTION OF THE WORK.
SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH
EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR DIFFICULTIES
ENCOUNTERED WILL NOT BE RECOGNIZED.
i. COORDINATE WITH THE OWNER AND OWNERS REPRESENTATIVE ANY POWER
OUTAGES THAT MAY AFFECT THE OWNER IN ANY MANNER. 72 HOUR PRIOR
NOTICE SHOULD BE GIVEN TO THE OWNER FOR ALL COORDINATED OUTAGES.
j. NOTIFY THE CONSTRUCTION MANAGER SEVEN (7) DAYS PRIOR TO THE START
OF ANY DEMOLITION WORK. NOTIFICATION SHALL INCLUDE A GENERAL LIST OF
SERVICES AFFECTED AND A SCHEDULE OF WORK TO BE PERFORMED.
PLAN KEY NOTES: #
1. EXISTING GENERATOR. REFER TO SHEET ED302 FOR ADDITIONAL
INFORMATION.
2. REMOVE EXISTING CONCRETE PAD. EXTEND/MODIFY EXISTING
CONDUIT TO FOR NEW GENERATOR INSTALLATION.
ENGINEER
MARK A. ESCOTT
DESIGNED BY
DRAWN BY
ENGR OF RECORD
ISSUE DATE
02/06/2026
AE PROJECT NUMBER
2025-393
SHEET TITLE
DEMO ELECTRICAL SITE
PLAN
DRAWING NO.
ED101
2
ED301
CA-00006208
935 Lake Baldwin Lane
Orlando, Fl. 32814
Tel: 407-767-5188
Fax: 407-767-5772
www.sgmengineering.com
Copyright © 2025 SGM Engineering, Inc.
SGM #: 2025-393
N
DEMO ELECTRICAL FLOOR PLAN MAINTENANCE BLD
SCALE: 3/32"=1'-0"
0 4' 8'
16'
1
ENLARGED ELECTRICAL RM-M115
SCALE: 1/2"=1'-0"
0
1'
2'
4'
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO EQUIPMENT SCHEDULES ON DRAWINGS E501 FOR DISCONNECT,
CONDUIT AND WIRE SIZES.
d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL
BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP.
e. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH CIRCUITS SHARING
A COMMON NEUTRAL, THEN EACH UNGROUNDED CONDUCTOR MUST BE
DISCONNECTED SIMULTANEOUSLY BY A COMMON TRIP CIRCUIT BREAKER.
CONTRACTOR MAY, AT THEIR OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE
CIRCUIT BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN ORDER
TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE NOT SHOWN IN THE
PANEL SCHEDULES AND MUST BE PROVIDED BY THIS SCOPE OF WORK. NO MORE
THAN 3 CIRCUITS MAY BE COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR
APPROVAL BY THE ENGINEER.
f. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR ALL PANELS
BEING REPLACED.
g. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO DISCONNECTION AND AFTER
RECONNECTION OF POWER.
h. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION SPECIFICATION.
i. EQUIPMENT SHOWN SCREENED IS EXISTING TO REMAIN. EQUIPMENT SHOWN DARK
IS EXISTING TO BE REMOVED.
PLAN KEY NOTES:
1. REMOVE EXISTING ATS. EXISTING CONDUIT AND WIRE TO REMAIN TO NORMAL
AND EMERGENCY. REMOVE WIRE TO LOAD AS SHOWN ON ONE LINE DRAWING.
CONDUIT TO LOAD MAY BE REUSED.
ENGINEER
MARK A. ESCOTT
DESIGNED BY
DRAWN BY
ENGR OF RECORD
ISSUE DATE
02/06/2026
AE PROJECT NUMBER
2025-393
SHEET TITLE
DEMO ELECTRICAL
FLOOR PLAN
MAINTENANCE BLD
DRAWING NO.
ED301
2
3
N
DEMO ELECTRICAL FLOOR PLAN MAINTENANCE BLD
SCALE: 1/8"=1'-0"
0
4'
8'
16'
CA-00006208
935 Lake Baldwin Lane
Orlando, Fl. 32814
Tel: 407-767-5188
Fax: 407-767-5772
www.sgmengineering.com
Copyright © 2025 SGM Engineering, Inc.
SGM #: 2025-393
1
4
5
GENERAL NOTES:
a. REFER TO SYMBOL LEGEND ON SHEET E001.
b. REFER TO BOOK SPECIFICATIONS.
c. REFER TO EQUIPMENT SCHEDULES ON DRAWINGS E501 FOR DISCONNECT,
CONDUIT AND WIRE SIZES.
d. ALL FEEDERS ARE TO HAVE LESS THAN 2% TOTAL VOLTAGE DROP AND ALL
BRANCH CIRCUITS SHALL HAVE LESS THAN 3% VOLTAGE DROP.
e. IF CIRCUITS ARE COMBINED AND RUN AS MULTI-WIRE BRANCH CIRCUITS SHARING
A COMMON NEUTRAL, THEN EACH UNGROUNDED CONDUCTOR MUST BE
DISCONNECTED SIMULTANEOUSLY BY A COMMON TRIP CIRCUIT BREAKER.
CONTRACTOR MAY, AT THEIR OPTION, PROVIDE EITHER COMMON TRIP MULTI-POLE
CIRCUIT BREAKERS OR UTILIZE MANUFACTURERS LISTED HANDLE TIES IN ORDER
TO PROVIDE THE SIMULTANEOUS TRIP. THESE DEVICES ARE NOT SHOWN IN THE
PANEL SCHEDULES AND MUST BE PROVIDED BY THIS SCOPE OF WORK. NO MORE
THAN 3 CIRCUITS MAY BE COMBINED IN A SINGLE RACEWAY WITHOUT PRIOR
APPROVAL BY THE ENGINEER.
f. CONTRACTOR SHALL PROVIDE ARC FLASH WARNING LABELS FOR ALL PANELS
BEING REPLACED.
g. CONTRACTOR TO CHECK PHASE ROTATION PRIOR TO DISCONNECTION AND AFTER
RECONNECTION OF POWER.
h. ENSURE ALL WIRES ARE TAGGED PER IDENTIFICATION SPECIFICATION.
i. EQUIPMENT SHOWN SCREENED IS EXISTING TO REMAIN. EQUIPMENT SHOWN DARK
IS EXISTING TO BE REMOVED.
PLAN KEY NOTES: #
1. REMOVE EXISTING GENERATOR. EXISTING CONDUIT TO REMAIN. REMOVE ALL
WIRING AND CONNECTIONS TO ASSOCIATED EQUIPMENT SCHEDULED TO BE
REMOVED. SECURE AND PROTECT EXISTING WIRE SCHEDULED TO BE
REUSED.
2. REMOVE EXISTING ATS. EXISTING CONDUIT TO REMAIN.
3. REMOVE GENERATOR ANNUNCIATOR PANEL. EXISTING CONDUIT TO REMAIN.
REMOVE ALL WIRING AND CONNECTIONS TO ASSOCIATED EQUIPMENT.
PREPARE FOR NEW GENERATOR ANNUNCIATOR PANEL TO BE INSTALLED IN
EXISTING LOCATION.
4. BLOCK HEATER. SECURE AND PROTECT EXISTING WIRE SCHEDULED TO BE
REUSED.
5. BATTERY CHARGER. SECURE AND PROTECT EXISTING WIRE SCHEDULED TO
BE REUSED.
ENGINEER
MARK A. ESCOTT
DESIGNED BY
DRAWN BY
ENGR OF RECORD
ISSUE DATE
02/06/2026
AE PROJECT NUMBER
2025-393
SHEET TITLE
DEMO ELECTRICAL
FLOOR PLAN BUS WASH &
FUEL ISLAND
DRAWING NO.
ED302
This page summarizes the opportunity, including an overview and a preview of the attached documents.
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.

Sign-up for a Free Trial, Government Bid Alerts

With Free Trial, you can:

You will have a full access to bids, website, and receive daily bid report via email and web.

Try One Week FREE Now

See Also

Main Agency City of Ocala Status Active Fiscal Year 2026 Primary Contact Caley

City of Ocala

Bid Due: 7/28/2026

Bid Information Type Invitation To Bid Status Issued Number ITB26-046 (Prepurchase of Generators)

City of Pompano Beach

Bid Due: 8/17/2026

Description: RFQ 26-0157-BW 3 PHASE PAD MOUNT TRANSFORMER, PURCHASE AND D Department: Procurement

Palm Beach County

Bid Due: 7/24/2026