Storm Lake RC - Repair Mechanical Systems
| Agency: | State Government of Iowa |
|---|---|
| State: | Iowa |
| Type of Government: | State & Local |
| NAICS Category: |
|
| Posted Date: | Aug 15, 2026 |
| Due Date: | Sep 10, 2026 |
| Solicitation No: | 19084224 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
Bid Information
Bid Number
19084224
Solicitation
Storm Lake RC - Repair Mechanical Systems
Solicitation Type
Request for Bids
County
Description
Description
Iowa DPD seeks professional services to repair mechanical systems at the Storm Lake Readiness Center. See attachments for details. Bids must be submitted via IMPACS
Site visit scheduled for Thursday 8/27 @ 10:00 AM. 1601 Park St, Storm Lake, IA 50588. Bring photo identification.
Bid opening scheduled for Thursday 9/10 @ 1:00 PM. https://teams.microsoft.com/meet/250919690831165?p=hcZAh7hlMA8vrf9Pno
Meeting ID: 250 919 690 831 165
Passcode: Hf2MX7T9
Issuing Officer: Philip Payton. 515-975-6211. philip.payton@dpd.iowa.gov
Agency Information
Number
582
Name
Public Defense, Dept Of
Address 1
7105 NW 70th Ave
Address 2
Bldg 3465/W-41
City/State/Zip
Johnston, IA 50131
Contact Information
Contact Name
Philip Payton
Contact Title
Procurement Officer
Contact Email
Contact Phone Number
(515) 252-4928
Contact Phone Extension
Contact Other Number
Contact Fax Number
Valid Dates
From
8/15/2026 12:48:00 PM
Until
9/10/2026 1:00:00 PM
Documents/Attachments
Attachment Preview
Storm Lake RC / Maintenance Shop (FMS)
Scope
Storm Lake RC:
Demolition
- Remove and dispose offsite 6 existing York RTU’s, t-stats and associated wiring
- Remove and dispose offsite 6 radiant tube heaters and associated wiring to BAS
- Remove and dispose offsite 1 Ruud water heater and expansion tank
Furnish and install
- 6 new Lennox Enlight RTUs to include the following
- 208/3 phase power
- Bacnet ready
- 2 stage heat
- Combination gas valve
- NG heat
- 2 stage cooling
- Barometric relief dampers
- Hinged access doors
- Condensate switch
- Hail guards
- Non-fused disconnects
- Fire smoke heads if units exceed 2000 cfm in the return and units that exceed
15,000 cfm in both supply and return
- Curb adapters w/ hurricane straps
- Any gas line alterations to include replacing ball valve and unions
- Smart thermostat to include 7-day scheduling
- Any electrical associated with the project include breakers, line voltage wiring and
low voltage wiring
- Reconnect any fire alarm controls that may shut off equipment in the event of fire.
- Any roofing membrane repairs or changes that may be needed from the installation
must be compatible with the roofing system
- Include crane use
Furnish and install
- 6 new Shwank radiant tube heaters to include the following
- Combination gas valve
- NG heat
- 2-stage heat
- 26 GA aluminized steel reflector
- Direct-drive ECM motor
- 6 programmable t-sats for individual control
- Fresh air intake kits
- Horizontal wall vent kits
- Provide any electrical line voltage and low voltage needed for completing the project
including wiring, conduit, and breakers
- Include scissor lift for project
Furnish and install
- 1 new 100-gallon RUUD direct replacement water heater to include:
- 115V power
- NG fired
- All associated copper piping and copper fitting materials needed to install the
replacement water heater
- Include any electrical needed
- Expansion tank
- Condensate neutralizer kit
- Fiber glass insulation and all associated materials needed to re-insulate damaged
or nonrepairable insulation on water lines
FMS maintenance shop alternates priced separately
Demolition:
- Remove and dispose offsite 1 York RTU, thermostat, and associated wiring
- Remove existing Co-Ray-Vac system and dispose of offsite
- Remove wash bay radiant tube system and dispose of offsite
- Furnish and install the following
- 1 new Lennox Enlight RTU to include the following
- 208/3 phase power
- Bacnet ready
- 2 stage heat
- Combination gas valve
- NG heat
- 2 stage cooling
- Barometric relief dampers
- Hinged access doors
- Condensate switch
- Hail guards
- Non-fused disconnects
- Fire smoke heads if units exceed 2000 cfm in the return and units that exceed
15,000 cfm in both supply and return
- Curb adapters w/ hurricane straps
- Any gas line alterations to include replacing ball valve and unions
- Smart thermostat to include 7-day scheduling
- Any electrical associated with the project to include breakers, line voltage wiring
and low voltage wiring
- Reconnect any fire alarm controls that may shut off equipment in the event of fire.
- To include replacement roof blocks to support the gas lines and electrical lines
- Any roofing membrane repairs or changes that may be needed from the installation
must be compatible with the roofing system
- Include crane use
Maintenance shop:
- Furnish and install the following
- (2) 2 stage Schwank radiant tube heaters
- Heaters to run North – South one on the West side and 1 on the East side of the shop
- New holes drilled for intake and exhaust pipes
- Provide all material needed for venting materials needed to bring in combustion air
from the South side of the building and exhaust materials needed to exhaust from
the North side of building
- Provide all materials for gas lines to each radiant tube heater
- 2 each 7-day programmable tstats
- Provide any electrical line voltage and low voltage needed for completing the project
including wiring, conduit, and breakers
- Patch hole with similar materials from the demoing of the Co-Ray-Vac vacuum
pump
- Include scissor lift
Wash Bay:
- Furnish and install the following
- (1) 2 stage Schwank moisture resistant radiant tube heater
- Moisture proof t-stat
- Tie onto existing combustion air intake
- Run new exhaust thru the existing penetration on the North exterior wall
This page summarizes the opportunity, including an overview and a preview of the attached documents.
Get Government Bids Like This by Email
Receive daily bid alerts that match your keywords, business categories, and target regions.
See Also
Bid Number Bid Title Bid Type Organization Bid Issue Date Bid Close Date
City of Davenport
Due by 11/12/2026
Bid Information Type Invitation to Bid Status Issued Number 27-29 (Union Station Canopy
City of Davenport
Due by 11/19/2026
Bid Information Type Invitation to Bid Status Issued Number 27-27 (Davenport Compost Facility
City of Davenport
Due by 11/09/2026
Iowa DOT Repair Shop Annex Overhead Door Tracks Iowa DOT Repair Shop Annex
Iowa Department of Administrative Services
Due by 11/10/2026
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.