Spirit Elementary - Upgrade HVAC Bldg. 7 Addendum No. 1

Agency: Volusia County Schools
State: Florida
Type of Government: State & Local
NAICS Category:
  • 238220 - Plumbing, Heating, and Air-Conditioning Contractors
Posted Date: Mar 12, 2026
Due Date: Mar 24, 2026
Solicitation No: Project No. 2648250
Original Source: Please Login to View Page
Contact information: Please Login to View Page
Bid Documents: Please Login to View Page
Spirit Elementary - Upgrade HVAC Bldg. 7 - Project No. 2648250
Mandatory Prebid Meeting: March 3, 2026 at 3:00 PM
Bid: March 24, 2026 at 2:00 PM
Project Bid Documents: Plans
Project Manual
Prebid Sign-in Sheets
Addendum No. 1 issued 3/12/2026
Estimate: $310,648
Consultant: TLC Engineering Solutions, Inc.
Jim Mullen

(321) 877-4260
Owner: VCS Project Manager
Mike Semon

(386) 947-8786
Bid Status: Active

Attachment Preview

VOLUSIA
COUNTY SCHOOLS
"LEADING WITH GRACE AND RESPECT"
THE SCHOOL BOARD OF VOLUSIA
COUNTY FLORIDA
200 North Clara Avenue
DeLand, Florida 32720
SPIRIT ELEMENTARY
UPGRADE HVAC BLDG. 7
VCS Project NO. 2648250
SCHOOL BOARD
MEMBERS
RUBEN COLÓN
KRISTA GOODRICH
DONNA BROSEMER
JAMIE HAYNES
JESSICA THOMPSON
CARMEN J. BALGOBIN
BOARD CHAIR
VICE BOARD CHAIR
MEMBER
MEMBER
MEMBER
SUPERINTENDENT
SEAL
1500 MEADOWLARK DR
DELTONA, FL 32725
DESCRIPTION OF WORK
REPLACEMENT OF THE 60 TON CHILLER SERVING BUILDING 7.
ADD ALTERNATE REPLACEMENT OF THE PUMPS SERVING THE 60 TON CHILLER.
Architect's Statement of Compliance
To the best of my knowledge, these drawings and the project manual are complete and comply with
the Florida Building Code.
BUILDING DATA
A. SURVEY PARCEL ID
B. LEGAL DESCRIPTION
C. OCCUPANCY TYPE
D. CONSTRUCTION TYPE
E. RISK CATEGORY
F. AUTOMATIC SPRINKLER
G. BUILDING AREA
H. BUILDING HEIGHT
I. OCCUPANT LOAD
XXX
XXX
XXX
TYPE XXX
XXX
XXX
XXX
XXX
XXX
LOCATION MAP
ENGINEERS & CONSULTANTS
MEP
TLC ENGINEERING SOLUTIONS
7370 CABOT CT, SUITE 103
MELBOURNE, FL 32940
321.636.0274
JIM MULLEN
JIM-MULLEN@TLC-ENG.COM
WWW.TLC-ENGINEERS.COM
Sheet Number
G001
COVER SHEET
SHEET MANAGER
Sheet Name
E001
ELECTRICAL SYMBOLS, LEGEND, AND ABBREVIATIONS
E002
ELECTRICAL GENERAL NOTES AND INDEX
E101
ELECTRICAL PLAN
E501
ELECTRICAL DETAILS
E601
ELECTRICAL PANEL AND EQUIPMENT SCHEDULES
ED101
ELECTRICAL DEMO PLAN
M001
M101
MD101
M601
MECHANICAL SYMBOLS. LEGEND, NOTES, AND INDEX
MECHANICAL PLAN
MECHANICAL DEMOLITION PLAN
MECHANICAL CONTROLS
NOT TO SCALE
Construction Documents 12/01/2025
ENGINEER OF RECORD
JIM MULLEN
DESIGNED BY
LUKE ADAMS
DRAWN BY
LUKE ADAMS
ISSUE DATE
12/01/2025
AE PROJECT NUMBER
525260
SHEET TITLE
COVER SHEET
DRAWING NO.
G001
ELECTRICAL SYMBOL LEGEND
BASIC MATERIALS
SYMBOL
DESCRIPTION
DEVICE ABBREVIATION TAGS:
6C
POKE-THRU WITH 6" CORE DRILL
8C
POKE-THRU WITH 8" CORE DRILL
4G
FOUR-GANG FLOOR BOX
6G
SIX-GANG FLOOR BOX
8G
EIGHT-GANG FLOOR BOX
AV
DOUBLE DUPLEX RECEPTACLE WITH DEDICATED CIRCUIT FOR AV RACK OR CART
C
RECEPTACLE CONTROLLED PER ASHRAE 90.1 (2010); PROVIDE POWER PACK FOR
RECEPTACLE CIRCUIT, TO BE CONTROLLED THROUGH LOCAL ROOM OCCUPANCY
SENSOR(S); PROVIDE DEVICE WITH BLUE DOT OR UNIVERSAL POWER SYMBOL
ETR
EXISTING TO REMAIN
H
HOSPITAL GRADE
IG
ISOLATED GROUND (ORANGE DEVICE)
RL
RELOCATED
TR
TAMPER RESISTANT
TV
RECEPTACLE MOUNTED ADJACENT TO TV OUTLET, COORDINATE HEIGHT W/ ARCHITECT
U
DUPLEX RECEPTACLE WITH (2) USB PORTS
WP
WEATHERPROOF
OS
WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
OS
DL
DL
VS
VS
PC
J
CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR
DAYLIGHT SENSOR CEILING MOUNTED
DAYLIGHT SENSOR WALL MOUNTED
VACANCY SENSOR CEILING MOUNTED
VACANCY SENSOR WALL MOUNTED
PHOTOCELL, MOUNTED ON ROOF FACING NORTH
NOTE: DIAGONAL MARKS INDICATED ON ANY DEVICE REPRESENTS DEVICE
CONNECTED TO EMERGENCY CIRCUIT (RED DEVICE FOR RECEPTACLE);
TYPICAL FOR ANY DEVICE IN LEGEND
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
TWO DUPLEX RECEPTACLES (QUAD) WITH COMMON COVER MOUNTED ABOVE COUNTER
DUPLEX RECEPTACLE; EACH RECEPTACLE ON SEPARATE CIRCUIT (PROVIDE
BREAKER WITH 2-POLE COMMON TRIP HANDLE)
SPLIT-WIRED CONTROLLED DUPLEX RECEPTACLE
GFCI RECEPTACLE; "WP" INDICATES CAST METAL "IN-USE" WEATHERPROOF COVER,
WEATHER-RESISTANT LISTED
TWO GFCI DUPLEX RECEPTACLES (QUAD) WITH COMMON COVERPLATE
GFCI RECEPTACLE MOUNTED ABOVE COUNTER
GND
GROUND BUS BAR, COPPER
SPD
SURGE PROTECTIVE DEVICE
MOTOR CONNECTION
MD
MOTORIZED DAMPER CONNECTION
VFD
VARIABLE FREQUENCY DRIVE
DDC
DIRECT DIGITAL CONTROL PANEL
BAS
BUILDING AUTOMATION SYSTEM CONTROL PANEL
LCP
LIGHTING CONTROL PANEL
SYMBOL
DESCRIPTION
MH
MANHOLE
PB
PULLBOX
HH
HANDHOLE
T
TRANSFORMER
ATS
30AR
NF
3R
30AR
20AF
3R
MCP
AMPERE
RATING
30/3
0
3R
AUTOMATIC TRANSFER SWITCH
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
NON-FUSED DISCONNECT SWITCH, RATING AS NOTED
NF = NON-FUSED
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
FUSED DISCONNECT
AF = AMPERE RATING OF FUSE
AR = AMPERE RATING OF SWITCH
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
# OF POLES
NEMA RATING; NEMA 1 UNLESS OTHERWISE NOTED
COMBINATION MAGNETIC MOTOR STARTER, SIZE AS NOTED, 3-POLE UNLESS OTHERWISE
NOTED
4X SS = NEMA 4X STAINLESS STEEL ENCLOSURE
NEMA STARTER SIZE
SWITCHBOARD/ SWITCHGEAR/ DISTRIBUTION PANEL
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, OVER 240 VOLTS, FLUSH MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, SURFACE MOUNTED
BRANCH CIRCUIT PANELBOARD, UNDER 240 VOLTS, FLUSH MOUNTED
CONDUIT CONCEALED ABOVE CEILING OR IN WAL
CONDUIT EXPOSED
CONDUIT CONCEALED IN SLAB, UNDERGROUND OR UNDER FLOOR
CONDUIT HOMERUN TO ELECTRICAL PANEL
UP CONDUIT TURNING UP
DN CONDUIT TURNING DOWN
CONDUIT STUBBED OUT OR UP
CONDUIT CONTINUED
FLEXIBLE CONDUIT
CONDUIT SEAL-OFF FITTING
GROUND OR GROUND ROD AS NOTED
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
EXISTING TO REMAIN (LIGHT, SOLID LINE)
NEW (HEAVY, SOLID LINE)
ABBREVIATIONS
A/C
AIR CONDITIONING
AC
ALTERNATING CURRENT
ABV CLG ABOVE CEILING
ADA
AMERICANS WITH DISABILITIES ACT
AF
AMPERE FRAME
AFF
ABOVE FINISHED FLOOR
AFG
ABOVE FINISHED GRADE
AHU
AIR HANDLING UNIT
AIC
AMPERE INTERRUPTING CAPACITY
AL
ALUMINUM
AMP
AMPERE
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
ASA
AMERICAN STANDARDS ASSOCIATION
AT
AMPERE TRIP
ATS
AUTOMATIC TRANSFER SWITCH
AUX
AUXILIARY
AWG
AMERICAN WIRE GUAGE
BC
BARE COPPER
BIL
BASIC IMPULSE LEVEL
BAS
BUILDING AUTOMATION SYSTEM
BMS
BUILDING MANAGEMENT SYSTEM
BRKR OR BKR BREAKER
C
CONDUIT OR RACEWAY
CAB
CABINET
CKT
CIRCUIT
CB
CIRCUIT BREAKER
CBM
CERTIFIED BALLAST MANUFACTURERS
CATV
CABLE TELEVISION
CCTV
CLOSED CIRCUIT TELEVISION
CLEC
CLOCK EQUIPMENT CABINET
CLG
CEILING
CO
CONDUIT OR RACEWAY ONLY
COAX
COAXIAL CABLE
COND
CONDUCTOR
CONN
CONNECTION
CPU
CENTRAL PROCESSING UNIT
CRT
CATHODE RAY TERMINAL (VIDEO DISPLAY TERMINAL)
CT
CURRENT TRANSFORMER
CU
COPPER
CW
COLD WATER
DC
DIRECT CURRENT
DDC
DIRECT DIGITAL CONTROL
DEG
DEGREE
DF
DEMAND FACTOR
DISC
DISCONNECT
DISC SW DISCONNECT SWITCH
DO
DRAW OUT
DN
DOWN
DPST
DOUBLE POLE SINGLE THROW
EDH
ELECTRIC DUCT HEATER
EMT
ELECTRIC METALLIC TUBING
EO
ELECTRICALLY OPERATED
EOL
END OF LINE
EOR
ENGINEER OF RECORD
ETR
EXISTING TO REMAIN
EWC
ELECTRIC WATER COOLER
FA
FIRE ALARM
FAAP
FIRE ALARM ANNUNCIATOR PANEL
FATC
FIRE ALARM TERMINAL CABINET
FBC
FLORIDA BUILDING CODE
FCU
FAN COIL UNIT
FLA
FULL LOAD AMPERES
FM
FACTORY MUTUAL
FPU
FAN POWERED UNIT
FT
FEET
GF
GROUND FAULT
GFA
GROUND FAULT ALARM
GFCI
GROUND FAULT CIRCUIT INTERRUPTER
GFR
GROUND FAULT RELAY
GND, G
GROUND
HP
HORSEPOWER
HOA
HAND-OFF-AUTOMATIC
HORIZ
HORIZONTAL
IBC
INTERNATIONAL BUILDING CODE
IC
INTERCOM
ICU
INTENSIVE CARE UNIT
IECC
INTERNATIONAL ENERGY CONSERVATION CODE
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
ABBREVIATIONS (CONT.)
IEEE
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS
IES
ILLUMINATING ENGINEERING SOCIETY
IMC
INTERMEDIATE METAL CONDUIT
IN
INCHES
IPCEA
INSULATED POWER CABLE ENGINEERS ASSOCIATION
IT
INSTANTANEOUS TRIP
JB OR J-BOX JUNCTION BOX
KCMIL
ONE THOUSAND CIRCULAR MILS
KV
KILOVOLT
KVA
KILOVOLT AMPERES
KW
KILOWATT
KWH
KILOWATT HOURS
LBS
POUNDS
LED
LIGHT EMITTING DIODE
LP
LIGHTNING PROTECTION
LT
LIGHT
LTG
LIGHTING
LSIG
LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND
LSIA
LONG TIME, SHORT TIME, INSTANTANEOUS, ALARM
LSI
LONG TIME, SHORT TIME, INSTANTANEOUS
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPS
MCB
MAIN CIRCUIT BREAKER
MCC
MOTOR CONTROL CENTER
MDP
MAIN SERVICE DISTRIBUTION PANEL
MIC
MICROPHONE
MIN
MINIMUM
MLO
MAIN LUGS ONLY
MOCP
MAXIMUM OVERCURRENT PROTECTION
MSB
MAIN SERVICE SWITCHBOARD
MTD
MOUNTED
MTG
MOUNTING
MTR
MOTOR
MTS
MANUAL TRANSFER SWITCH
MUX
MULTIPLEX (TRANSPONDER) PANEL
MVA
MEGA VOLT AMPS
N
NEUTRAL
NC
NORMALLY CLOSED
NEC
NATIONAL ELECTRICAL CODE
NEMA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NFPA
NATIONAL FIRE PROTECTION ASSOCIATION
NIC
NOT IN CONTRACT
NF
NON-FUSED
NL
NON-LINEAR
NO
NORMALLY OPEN OR NUMBER
OL
OVERLOAD
OSHA
OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION
P
POLE
PB
PULLBOX
PF
POWER FACTOR
PIV
POST INDICATOR VALVE
PNL
PANEL
PR
PAIR
PRI
PRIMARY
PT
POTENTIAL TRANSFORMER
PVC
POLYVINYLCHLORIDE
PWR
POWER
REC, RECEPT RECEPTACLE
REF
REFRIGERATOR
RGS, GRC RIGID GALVANIZED STEEL CONDUIT
RLA
RUNNING LOAD AMPERES
RMS
ROOT-MEAN-SQUARE
RPM
REVOLUTIONS PER MINUTE
RTU
ROOF TOP UNIT
SCA
SHORT CIRCUIT AMPERES
SD
SMOKE DETECTOR
SEC
SECONDARY
S/N
SOLID NEUTRAL
SPD
SURGE PROTECTIVE DEVICE
SPKR
SPEAKER
SPST
SINGLE POLE SINGLE THROW
SS
STAINLESS STEEL
SST
SOLID STATE TRIP
STD
SHORT TIME TRIP
SW
SWITCH
SWBD
SWITCHBOARD
SWGR
SWITCHGEAR
TEL
TELEPHONE
TTB
TELEPHONE TERMINAL BOARD
TTC
TELEPHONE TERMINAL CABINET
TVEC
TELEVISION EQUIPMENT CABINET
TYP
TYPICAL
UG
UNDERGROUND
UON
UNLESS OTHERWISE NOTED
UL
UNDERWRITERS LABORATORIES
UTIL
UTILITY
V
VOLT
VA
VOLTAMPERE
VAR
VOLT AMPERE REACTIVE
VAV
VARIABLE AIR VOLUME
VFD
VARIABLE FREQUENCY DRIVE
W
WIRE
WP
WEATHER PROOF
XFMR
TRANSFORMER
XFR
TRANSFER
SEAL
ENGINEER OF RECORD
MONCEF M. HADIJI
DESIGNED BY
JOEY HOLT
DRAWN BY
JOEY HOLT
ISSUE DATE
12/01/2025
AE PROJECT NUMBER
525260
SHEET TITLE
ELECTRICAL SYMBOLS,
LEGEND, AND
ABBREVIATIONS
DRAWING NO.
E001
ELECTRICAL DEMOLITION NOTES
ELECTRICAL GENERAL NOTES
1. DEVICES, LIGHT FIXTURES AND EQUIPMENT SHOWN IN BOLD LINE TYPE ARE EXISTING TO BE DEMOLISHED; DEVICES, LIGHT
FIXTURES AND EQUIPMENT SHOWN IN LIGHT (SCREENED) SOLID LINE TYPE ARE EXISTING TO REMAIN, UNLESS NOTED
OTHERWISE.
2. EXISTING EQUIPMENT, LIGHT FIXTURES AND DEVICES SHOWN ARE BASED ON FIELD SURVEYS AND DRAWINGS PROVIDED BY
THE OWNER, AND ARE NOT NECESSARILY INCLUSIVE OF ALL EXISTING ELECTRICAL EQUIPMENT, LIGHT FIXTURES AND
DEVICES WITHIN PROJECT AREAS. IT IS THE INTENT THAT THE DEMOLITION PLANS PROVIDE A GENERAL KNOWLEDGE OF THE
EXISTING CONDITIONS WITHIN THE PROJECT AREA. ANY DISCREPANCIES OR CONDITIONS NOT SHOWN ON THE PLAN SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER. THE CONTRACTOR IS RESPONSIBLE FOR REQUIRED
ELECTRICAL DEMOLITION WHETHER INDICATED ON THE PLANS OR NOT.
3. EXISTING CIRCUITING SHOWN IS BASED ON RECORD DRAWINGS AND THE SURVEYED PANEL DIRECTORIES, WHERE THEY
WERE AVAILABLE. THE ACTUAL CONDITIONS MAY VARY. ALL EXISTING CONDITIONS MUST BE VERIFIED BY THE CONTRACTOR
PRIOR TO BID. THE CONDITIONS SHOWN ARE INTENDED TO SHOW THE GENERAL LOCATIONS OF EXISTING DEVICES, LIGHT
FIXTURES AND EQUIPMENT, WHERE SHOWN ON THE PLAN DRAWINGS, AND IN NO WAY RELIEVES THE CONTRACTOR FROM
PROVIDING ANY AND COORDINATION NECESSARY TO COMPLETE THE NEW WORK. FIELD CONDITIONS SHALL GOVERN.
4. WHERE EXISTING DEVICES ARE INDICATED TO REMAIN OR BE RELOCATED, ARE WITHIN THE SCOPE OF THIS PROJECT AND
EXISTING CIRCUITING INFORMATION IS UNAVAILABLE, CONTRACTOR SHALL PROVIDE CIRCUIT TRACING TO IDENTIFY PANEL
AND CIRCUIT SERVING THE DEVICE. THEY SHALL PROVIDE THAT INFORMATION TO THE ARCHITECT/ENGINEER PRIOR TO
ROUTING CONDUITS AND WIRING FOR THESE DEVICES AND EQUIPMENT.
5. WHERE EXISTING DEVICES ARE TO REMAIN, CONTRACTOR SHALL EXTEND EXISTING CIRCUITING WHERE NECESSARY TO
MAINTAIN CONTINUITY OF CIRCUIT.
6. COORDINATE WITH THE OWNER FOR DISPOSAL OF ELECTRICAL ITEMS TO BE DEMOLISHED. OWNER SHALL HAVE THE
OPTION TO RETAIN REUSABLE ITEMS SUCH AS COVERPLATES, RECEPTACLES, LIGHT FIXTURES, PANELBOARDS,
TRANSFORMERS, ETC. NOT BEING USED IN THE FINISHED WORK. COORDINATE WITH THE OWNER PRIOR TO START OF
DEMOLITION. PROPERLY AND LEGALLY DISPOSE OF EQUIPMENT AND MATERIALS BEING REMOVED.
7. COORDINATE EXACT AREAS, WALLS, CEILINGS, ETC. TO BE DEMOLISHED WITH ARCHITECTURAL, STRUCTURAL, PLUMBING AND
MECHANICAL DEMOLITION PLANS.
8. WHERE EXISTING DEVICES, LIGHT FIXTURES AND EQUIPMENT ARE INDICATED TO BE DEMOLISHED, REMOVE ASSOCIATED
BOXES, CONDUIT AND WIRING BACK TO SOURCE PANEL OR TO NEAREST JUNCTION BOX TO MAINTAIN CIRCUIT CONTINUITY
OF DEVICES AND EQUIPMENT TO REMAIN. WHERE PANELS ARE TO REMAIN, TURN BREAKER TO "OFF" POSITION AND LABEL
THE CIRCUIT AS "SPARE" ON THE PANEL DIRECTORY.
9. AREAS OUTSIDE THE SCOPE OF CONSTRUCTION ARE TO REMAIN ENERGIZED. COORDINATE PHASING WITH CONSTRUCTION
MANAGER AND OWNER PRIOR TO DEMOLITION OF ANY ITEM WHICH MAY RESULT IN THE INTERRUPTION OF POWER.
10. REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EXTENT OF AREA REQUIRING DEMOLITION AND ADDITIONAL
INFORMATION ON ELECTRICAL DEMOLITION WITHIN THAT AREA. DISCONNECT ELECTRICAL SERVICE TO EQUIPMENT BEING
REMOVED. DEMOLITION SHALL BE PHASED AS REQUIRED BY DIVISION 1, OR AS DIRECTED BY THE OWNER.
11. REMOVE CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED OR RENOVATED AREA. CAP BOTH
ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING OPENINGS IN EXISTING CONSTRUCTION AFTER REMOVAL OF
EQUIPMENT, LIGHT FIXTURES, AND DEVICES UNLESS OTHERWISE NOTED ON ARCHITECTURAL PLANS. REPAIRS ARE TO BE
DONE TO LOGICAL EDGES OF SURFACES AFFECTED AND SHALL MATCH THE IMMEDIATE ADJACENT AREAS IN CONSTRUCTION,
MATERIAL, FIRE RATING, FINISH AND COLOR.
13. FIELD VERIFY EXISTING CONDITIONS AND DIMENSIONS PRIOR TO COMMENCEMENT OF WORK AND OBTAIN CLARIFICATIONS
FROM ARCHITECT / ENGINEER IF NECESSARY.
14. COORDINATE POWER INTERRUPTION WITH CONSTRUCTION MANAGER, OWNER, LANDLORD, AND UTILITY COMPANY (WHERE
APPLICABLE) AND DO NOT INTERRUPT POWER WITHOUT WRITTEN PERMISSION. PROVIDE A MINIMUM OF ONE WEEK'S
WRITTEN NOTIFICATION PRIOR TO WHEN POWER IS DESIRED TO BE INTERRUPTED. CONTRACTOR SHALL INVESTIGATE AND
IDENTIFY LOADS TO BE AFFECTED BY THE REQUESTED INTERRUPTION. CONTRACTOR SHALL SUBMIT WRITTEN SEQUENCE OF
STEPS FOR EACH SHUTDOWN ALONG WITH THE ESTIMATED INTERRUPTION DURATIONS. MAKE ARRANGEMENTS TO MAINTAIN
POWER TO EXISTING NECESSARY LIGHTING, DEVICES AND EQUIPMENT AS NEEDED AND REQUESTED BY THE OWNER PRIOR
TO COMMENCEMENT OF WORK.
15. EXERCISE EXTREME CAUTION WHEN REMOVING / RELOCATING WIRING AND EQUIPMENT. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO ENSURE THAT OTHER WIRING DEVICES, EQUIPMENT AND LIGHT FIXTURES THAT MAY BE CONNECTED TO
THE SAME CIRCUIT REMAIN OPERATIONAL AND ACTIVE.
16. INFORMATION INDICATED IN THE DEMOLITION PORTION OF THE CONTRACT DRAWINGS IS DIAGRAMMATIC IN NATURE. FIELD
VERIFY ELECTRICAL CIRCUIT HOMERUNS TO ITEMS SCHEDULED OR NOTED TO BE DEMOLISHED AND PERFORM THE WORK AS
INTENDED AND DEPICTED ON THE DRAWINGS OR DIRECTED IN THE FIELD.
17. UPDATE EXISTING ELECTRICAL EQUIPMENT NAMEPLATES AND DIRECTORIES AS NECESSARY TO REFLECT FINAL AS-BUILT
CONDITIONS AT THE END OF CONSTRUCTION.
18. STORE ITEMS INDICATED TO BE RETURNED TO THE OWNER IN A DRY, CLEAN AND PROTECTED AREA. NOTIFY OWNER WHEN
ITEMS ARE READY TO BE REMOVED.
19. COORDINATE ANY ALTERATION AND CHANGES TO THE EXISTING ELECTRICAL SERVICE WITH THE LOCAL UTILITY COMPANY
AND THE OWNER PRIOR TO COMMENCEMENT OF WORK.
20. PROVIDE ANY NECESSARY REPROGRAMMING OF EXISTING BUILDING FIRE ALARM SYSTEMS TO DISABLE FIRE ALARM DEVICES
THAT ARE BEING DISCONNECTED AND REMOVED, AND FOR ANY NEW DEVICES THAT ARE ADDED, AS PART OF BID PRICE.
21. CONDUITS SERVING OTHER SPACES THAT RUN THROUGH THE PROJECT AREA SHALL REMAIN ACTIVE DURING CONSTRUCTION
SO AS NOT TO CAUSE DISRUPTION TO THESE OTHER SPACES. ENSURE THAT CONDUITS, NEW OR EXISTING WITHIN THE
PROJECT AREA ARE PROPERLY SUPPORTED IN ACCORDANCE WITH THE NEC.
22. REMOVE ABANDONED OR UNUSED RACEWAYS INCLUDING CONDUCTORS, JUNCTION BOXES, SUPPORTS, AND FASTENERS
THAT ARE WITHIN THE PROJECT AREA PRIOR TO THE END OF CONSTRUCTION.
GENERAL REQUIREMENTS
1. THE DRAWINGS AND APPLICABLE SPECIFICATIONS SHALL BE CONSIDERED SUPPLEMENTARY, ONE TO THE OTHER AND ARE
CONSIDERED THE "CONTRACT DOCUMENTS". WORKMANSHIP, METHODS AND/OR MATERIALS DESCRIBED OR IMPLIED BY ONE
AND NOT DESCRIBED OR IMPLIED BY THE OTHER SHALL BE PROVIDED, FURNISHED OR PERFORMED AS IF IT HAD APPEARED IN
BOTH SECTIONS. THE TERM "CONTRACT DOCUMENTS" DESCRIBED HEREIN IS NOT LIMITED SOLELY TO THE ELECTRICAL
PORTION OF THE DRAWINGS AND SPECIFICATIONS, BUT ENCOMPASSES THE DRAWINGS AND SPECIFICATIONS OF ALL
DIVISIONS AS A WHOLE.
2. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO SHOW EVERY DETAIL OF CONSTRUCTION, METHODS,
MATERIALS AND EQUIPMENT, OR EXACT LOCATIONS, ROUTING, ETC. THEY INDICATE THE RESULT TO BE ACHIEVED BY THE
ASSEMBLAGE OF SEVERAL SYSTEMS FOR A COMPLETE AND OPERATIONAL ELECTRICAL SYSTEM. DO NOT SCALE THE
CONTRACT DOCUMENTS. COORDINATE EXACT EQUIPMENT LOCATIONS WITH THE ARCHITECTURAL, CIVIL, STRUCTURAL,
MECHANICAL, PLUMBING, AND FIRE PROTECTION CONTRACT DOCUMENTS, AS WELL AS FIELD CONDITIONS, APPROVED SHOP
DRAWINGS AND WORK OF OTHER DIVISIONS/TRADES.
3. THE TERM "PROVIDE" USED IN THE CONTRACT DOCUMENTS INDICATES TO FURNISH AND INSTALL MATERIALS REQUIRED FOR
CORRECT INSTALLATION OF A COMPLETE SYSTEM, UNLESS SPECIFICALLY NOTED OTHERWISE.
4. UNLESS NOTED AS EXISTING, ELECTRICAL SYSTEMS AND DEVICES INDICATED ON THE CONTRACT DOCUMENTS SHALL BE NEW,
SHALL BE U.L. LISTED, AND SHALL BEAR A U.L. LABEL. WHERE NO U.L. LABEL OR LISTING IS AVAILABLE, THE MATERIAL SHALL BE
LISTED WITH AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY AS DEFINED BY OSHA.
5. PROVIDE EXPERIENCED, QUALIFIED AND RESPONSIBLE SUPERVISION FOR WORK REQUIRED BY THE CONTRACT DOCUMENTS.
ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER, TO THE SATISFACTION OF THE
ARCHITECT/ENGINEER AND OWNER.
6. CARRY INSURANCE REQUIRED TO PROTECT AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THIS
PROJECT.
7. GUARANTEE MATERIALS AND WORKMANSHIP ARE FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE YEAR FROM
THE DATE OF FINAL ACCEPTANCE BY THE ARCHITECT/ENGINEER AND OWNER, UNLESS NOTED OTHERWISE IN DIVISION 1. AT
NO ADDITIONAL COSTS, PROVIDE THE CORRECTION OF ANY DEFECTS INCLUDING REPAIR OR REPLACEMENT.
8. INCLUDE COSTS ASSOCIATED WITH PERMITS, LICENSES, FEES, INSPECTIONS, TESTING AND TEMPORARY POWER IN THE BID
PRICE, UNLESS NOTED OTHERWISE.
9. IF HAZARDOUS MATERIALS ARE ENCOUNTERED, COMPLY WITH APPLICABLE RULES, REGULATIONS AND GUIDELINES
CONCERNING REMOVAL, HANDLING, DISPOSAL AND PROTECTION AGAINST ENVIRONMENTAL EXPOSURE OR POLLUTION.
PROVIDE DOCUMENTATION OF SAID COMPLIANCE.
10. PROVIDE ELECTRONIC SUBMITTALS (PRODUCT DATA & SHOP DRAWINGS) FOR EACH MAJOR COMPONENT OF THE ELECTRICAL
SYSTEM FOR REVIEW BY THE ARCHITECT/ENGINEER AND OWNER. MAJOR COMPONENTS INCLUDE, BUT ARE NOT LIMITED TO,
RACEWAYS, BOXES, WIRE AND CABLE, EQUIPMENT, DEVICES, LIGHT FIXTURES, SWITCHGEAR, PANELBOARDS, CIRCUIT
BREAKERS, SAFETY SWITCHES, FIRE ALARM SYSTEM, ETC. SUBMITTALS ARE TO BE REVIEWED AND APPROVED BY THE
CONTRACTOR FOR CONFORMANCE WITH THE PROJECT REQUIREMENTS PRIOR TO SUBMITTING TO THE ARCHITECT/ENGINEER.
ALLOW A MINIMUM OF TEN (10) BUSINESS DAYS FOR REVIEW BY ARCHITECT/ENGINEER, UNLESS NOTED OTHERWISE IN
DIVISION 1.
11. THE ELECTRICAL PORTION OF THE CONTRACT DOCUMENTS ARE COORDINATED WITH THE DESIGN BASIS EQUIPMENT
SPECIFIED BY DIVISION 26 AND OTHER DIVISIONS. WHERE THE CONTRACTOR ELECTS TO SUBSTITUTE A PRODUCT IN LIEU OF
PROVIDING THE DESIGN BASIS, AND SAID SUBSTITUTION IS ACCEPTED BY THE ARCHITECT/ENGINEER AND OWNER, THE
CONTRACTOR SHALL MAKE CORRECTIONS TO THE ELECTRICAL SYSTEM NECESSARY IN ORDER TO ENSURE A COMPLETE AND
OPERATIONAL INSTALLATION OF THE EQUIPMENT AT NO ADDITIONAL COSTS. WHERE THE CONTRACTOR'S DESIGN
SUBSTITUTION RESULTS IN THE NEED FOR THE ENGINEER TO REVISE THE CONTRACT DOCUMENTS, THE ENGINEER RESERVES
THE RIGHT TO REQUEST COMPENSATION FROM THE CONTRACTOR FOR SAID SERVICES.
12. MAINTAIN A CURRENT AND ACCURATE SET OF PROJECT RECORD DOCUMENTS (AS-BUILTS) AT THE SITE THROUGHOUT THE
DURATION OF THE PROJECT. RECORD DRAWINGS SHALL BE UPDATED EACH DAY TO REFLECT THE ACTUAL LOCATIONS, SIZES,
ROUTING, ETC. OF EACH PORTION OF THE ELECTRICAL SYSTEM AFFECTED BY THIS WORK. A FINAL SET OF RECORD
DOCUMENTS SHALL BE ISSUED TO THE ARCHITECT/ ENGINEER FOR REVIEW AND THEN SUBMITTED TO THE OWNER WITHIN 30
DAYS AFTER THE DATE OF FINAL ACCEPTANCE. PROVIDE RECORD DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING
SINGLE LINE DIAGRAM, POWER RISER DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND
ELECTRICAL FLOOR PLANS, DETAILS, PANEL SCHEDULES, ETC.
13. PROVIDE AN OPERATING AND MAINTENANCE MANUAL TO OWNER PRIOR TO THE FINAL ACCEPTANCE. THE MANUAL SHALL
INCLUDE, AS A MINIMUM, (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF
EQUIPMENT REQUIRING MAINTENANCE, (2) PROVIDE TWO OPERATIONS AND MAINTENANCE MANUALS FOR EACH PIECE OF
EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS AND METHOD OF OPERATION FOR
EQUIPMENT SHALL BE CLEARLY IDENTIFIED, AND THE NAME, PHONE NUMBER AND ADDRESS OF AT LEAST ONE QUALIFIED
SERVICE AGENCY.
14. INCLUDE IN BID COSTS FOR EXCAVATION, SAW CUTTING, DIRECTIONAL BORING, CORE DRILLING, BACKFILLING, SURFACE
RESTORATION, REPAIR OF FINISHES, ETC. THAT IS REQUIRED IN ORDER TO MEET THE PROJECT REQUIREMENTS.
15. INCLUDE IN BID COSTS ASSOCIATED WITH TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR USE BY TRADES DURING
CONSTRUCTION. REMOVE TEMPORARY POWER AT THE COMPLETION OF THE PROJECT. OBTAIN AND PAY FOR REQUIRED
PERMITS FOR TEMPORARY POWER. ENGINEER OF RECORD SHALL BE PROVIDED WITH ADDITIONAL COMPENSATION FROM THE
CONTRACTOR WHERE SIGNED & SEALED DRAWINGS ARE REQUESTED BY THE CONTRACTOR TO THE ENGINEER OF RECORD IF
REQUIRED BY THE AHJ FOR THE TEMPORARY POWER.
16. PRIOR TO TRENCHING IN ANY AREA LOCATE, IDENTIFY, PROTECT AND DOCUMENT UTILITY LINES LOCATED WITHIN THE
PROJECT BOUNDARY. FOR LOCATING SITE UTILITIES, CONTACT LOCAL MUNICIPALITIES AND UTILITIES AT LEAST 48 HOURS
PRIOR TO DIGGING.
17. INCLUDE IN BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF WASTE MATERIALS GENERATED BY THIS PROJECT IN
ACCORDANCE WITH LOCAL, STATE AND FEDERAL RULES, REGULATIONS AND GUIDELINES APPLICABLE. COMPLY FULLY WITH
APPLICABLE STATUTES REGARDING MERCURY-CONTAINING DEVICES, AND WITH LOCAL, STATE AND FEDERAL APPLICABLE
GUIDELINES AT THE TIME OF DISPOSAL. PROVIDE OWNER WITH WRITTEN CERTIFICATION OF ACCEPTED DISPOSAL.
GROUNDING
1. FIRE PROTECTION PIPING SHALL NOT BE USED FOR GROUNDING.
2. FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE AN EQUIPMENT GROUND CONDUCTOR. METAL RACEWAYS SHALL NOT BE
USED AS THE SOLE EQUIPMENT GROUND.
3. WHERE A PHASE CONDUCTOR IS INCREASED IN SIZE DUE TO VOLTAGE DROP, THE EQUIPMENT GROUND CONDUCTOR SHALL BE
INCREASED IN SIZE PROPORTIONATELY.
COORDINATION
1. VERIFY AND COORDINATE LOCATIONS OF ANY MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS (I.E.,
COPIERS, FAX MACHINES, PRINTERS, KITCHEN APPLIANCES, LAUNDRY APPLIANCES, PROJECTION SCREENS, SHOP TOOLS,
MACHINE, ELEVATORS, ETC.) WITH APPROVED SHOP DRAWINGS, OWNER-PROVIDED CUT SHEETS, MANUFACTURER'S
INSTRUCTIONS, AND EQUIPMENT NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE NECESSARY ELECTRICAL
REQUIRED.
2. VERIFY AND COORDINATE LOCATIONS AND EXACT ELECTRICAL REQUIREMENTS FOR MECHANICAL, PLUMBING AND FIRE
PROTECTION EQUIPMENT PRIOR TO SUBMITTAL OF SHOP DRAWINGS OF ELECTRICAL EQUIPMENT. PROVIDE NECESSARY
RACEWAYS, CONDUCTORS, BOXES, EQUIPMENT, ACCESSORIES, ASSOCIATED DISCONNECT SWITCHES, CIRCUIT BREAKERS,
CONTROL TRANSFORMERS, FIRE ALARM SHUTDOWN, ETC. REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
COORDINATE WITH APPROPRIATE TRADE'S APPROVED SHOP DRAWINGS, MANUFACTURER'S INSTRUCTIONS, AND EQUIPMENT
NAMEPLATE INFORMATION, PRIOR TO ROUGH IN, AND PROVIDE NECESSARY ELECTRICAL REQUIRED, UNLESS NOTED
OTHERWISE.
3. THIS PROJECT REQUIRES COORDINATION DRAWINGS BY THE CONTRACTOR. PARTICIPATE IN THE COORDINATION DRAWING
PREPARATION PROCESS AND PROVIDE NECESSARY INFORMATION REQUIRED TO COORDINATE TRADE INFORMATION.
4. WORK ON THE ELECTRICAL SYSTEM REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE COORDINATED WITH THE WORK OF
OTHER DIVISIONS/TRADES PRIOR TO COMMENCEMENT OF WORK. AVOID INTERFERENCES WITH THE PROGRESS OF OTHER
DIVISIONS/TRADES.
5. WHERE WALLS ARE OF TILT-UP OR PRE-CAST CONSTRUCTION, PROVIDE COORDINATION FOR EXACT DIMENSIONS AND
OPENINGS REQUIRED FOR ELECTRICAL COMPONENTS INSTALLED WITHIN SUCH WALLS DURING THE SHOP DRAWING REVIEW
PROCESS OF THE WALLS, PRIOR TO CONSTRUCTION OF THE WALLS.
6. LOCATIONS OF VFD'S, DISCONNECTS, MOTOR STARTERS, ETC. FOR HVAC EQUIPMENT ARE DIAGRAMMATIC ON THE PLAN
DRAWINGS. EXACT LOCATIONS ARE TO BE COORDINATED WITH CONTRACTOR'S COORDINATION DRAWINGS PRIOR TO ROUGH-
IN TO ENSURE PROPER NEC CLEARANCES AND APPROPRIATE MOUNTING SURFACES.
7. REFER TO ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL, LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY,
STRUCTURAL, AND VENDOR EQUIPMENT DRAWINGS FOR RELATED INFORMATION AND ADDITIONAL INSTALLATION
REQUIREMENTS TO BE PERFORMED AS PART OF THE WORK.
8. WHERE A DISCREPANCY OR CONFLICT IS FOUND BETWEEN ONE DRAWING AND ANOTHER, OR BETWEEN A DRAWING AND
APPLICABLE SPECIFICATIONS, NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY IN WRITTEN FORM. IN GENERAL, THE MOST
STRINGENT REQUIREMENT SHALL GOVERN UNLESS THE DISCREPANCY CONFLICTS WITH APPLICABLE CODES OR OWNER'S
DESIGN STANDARDS, WHEREIN THE CODE OR OWNER'S DESIGN STANDARDS SHALL GOVERN.
9. CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND/OR SITE AFFECTED BY THIS WORK PRIOR TO SUBMITTING BID
PRICE, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT MAY AFFECT EXECUTION OF THE
WORK. SUBMISSION OF A BID PRICE SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE. LATER
CLAIMS FOR LABOR, EQUIPMENT AND/OR MATERIALS REQUIRED DUE TO DIFFICULTIES ENCOUNTERED THAT COULD HAVE
BEEN REASONABLY OBSERVED WILL NOT BE RECOGNIZED.
10. COORDINATE PROJECT SCHEDULING AND PHASING REQUIREMENTS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO
SUBMITTING BID PRICE. THIS PROJECT MAY REQUIRE PHASING SEQUENCES AND POTENTIAL PREMIUM TIME WORK AND ALL
COSTS FOR SUCH SHALL BE INCLUDED IN THE BID PRICE. PROVIDE ADEQUATE WORK FORCE AND EQUIPMENT, AND INCLUDE
PREMIUM TIME AS MAY BE REQUIRED IN ORDER TO ADHERE TO THE PROJECT SCHEDULE. ADDITIONALLY, ENSURE THAT LONG
LEAD ITEMS DO NOT IMPACT THE PROJECT'S SCHEDULE OR PHASING.
11. ANY TEMPORARY INTERRUPTION OF POWER REQUIRED FOR THE SYSTEM TIE-IN OR SWITCHOVER FOR ANY PORTION OF THE
ELECTRICAL SYSTEM SHALL BE PRE-APPROVED IN WRITING BY THE OWNER AND SCHEDULED IN ADVANCE.
12. COORDINATE EXACT REQUIREMENTS WITH THE LOCAL UTILITY COMPANIES AND PROVIDERS (ELECTRIC, TELEPHONE, CABLE
TV, ETC.) AND INCLUDE COSTS FOR PROVIDING TEMPORARY AND PERMANENT SERVICES REQUIRED FOR THIS PROJECT IN
THE BID PRICE. BID PRICE SHALL INCLUDE, BUT NOT BE LIMITED TO, EXCAVATION, RACEWAYS, BACKFILL, EQUIPMENT,
EQUIPMENT PADS, BACKBOARDS, METERS, GROUNDING, UTILITY ENGINEERING AND IMPACT FEES.
13. CONDUCT WORK OPERATIONS AND DEBRIS REMOVAL IN A MANNER THAT ENSURES MINIMUM INTERFERENCE WITH NORMAL
BUSINESS OPERATIONS, TRAFFIC, PARKING, ETC. ONGOING IN ADJACENT OCCUPIED SPACES OR FACILITIES. PROVIDE ALL
THAT IS REQUIRED TO EFFECTIVELY PROTECT SURROUNDING OCCUPANTS, EQUIPMENT, FINISHES, FURNITURE, ETC. FROM
DAMAGE OR EXCESSIVE NOISE THROUGHOUT THE DURATION OF THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR ANY
LOSSES OR ANY DAMAGE RESULTING FROM THE FAILURE TO ADHERE TO THIS REQUIREMENT. RESTORE DAMAGED ELEMENTS
TO ORIGINAL CONDITION TO THE SATISFACTION OF THE ARCHITECT/ENGINEER AND OWNER, AT NO ADDITIONAL COSTS.
REPORT OF ANY SUCH OCCURRENCE TO THE ARCHITECT/ENGINEER AND OWNER IMMEDIATELY AND AWAIT WRITTEN
DIRECTION PRIOR TO PROCEEDING WITH REPAIRS.
14. COORDINATE THE LOCATION OF LIGHT FIXTURES, DEVICES AND BOXES WITH WINDOWS, MIRRORS, MILLWORK, CABINETS,
GLASS CURTAIN WALLS, AND GLASS WALLS PRIOR TO INSTALLATION OF CONDUITS OR BOXES. REVIEW CONTRACT DRAWINGS
TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. OBTAIN CLARIFICATION FROM THE ARCHITECT/ENGINEER PRIOR TO BID.
CONTRACTOR SHALL NOT BE ENTITLED TO ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET BOXES
OR RACEWAYS FOR COORDINATION WITH OTHER TRADE'S WORK.
CONDUCTORS
1. CONDUCTOR SIZE SHALL BE ASSUMED TO BE #12 AWG MINIMUM OR OTHERWISE SIZED TO MEET NEC OR VOLTAGE DROP
REQUIREMENTS.
2. BRANCH CIRCUITS SHALL BE INCREASED IN SIZE AS REQUIRED TO COMPENSATE FOR VOLTAGE DROP FROM LENGTH OF
CIRCUIT DUE TO FIELD ROUTING. FINAL INSTALLATION SHALL NOT EXCEED A MAXIMUM OF 3% VOLTAGE DROP FOR BRANCH
CIRCUITS. REFER TO VOLTAGE DROP TABLE BELOW FOR CONDUCTOR SIZES FOR BRANCH CIRCUITS AS FOLLOWS:
A. 120V, 20A CIRCUITS SHALL BE:
i. #12 FROM 0-70 FT
ii. #10 FROM 71-115FT
iii. #8 FROM 116-180FT
B. 277V, 20A CIRCUITS SHALL BE:
i. #12 FROM 0-140FT
ii. #10 FROM 141-220FT
iii. #8 FROM 221-350FT
ANYTHING LONGER THAN THE ABOVE SHALL BE SUBMITTED TO THE ENGINEER WITH CALCULATIONS FOR APPROVAL.
3. CONDUCTORS IN CABINETS MUST BE CAREFULLY FORMED AND HARNESSED SO THAT EACH CONDUCTOR DROPS OFF
DIRECTLY OPPOSITE TO TERMINAL.
4. CONDUCTORS ARE BASED ON AMPACITIES FOR 60 OR 75 DEGREE CELSIUS TEMPERATURE RATING UP TO 100A OR UP TO #1
AWG AND 60 OR 75 DEGREE CELSIUS TEMPERATURE RATING ABOVE 100A OR ABOVE #1 AWG PER NEC 110.14(C)(1)(a)/(b) AND
TABLE 310.15(B)(16).
RACEWAYS
1. FLEXIBLE METAL CONDUIT AND LIQUID-TIGHT FLEXIBLE METAL CONDUIT (FMC & LFMC) SHALL NOT BE USED IN LENGTHS
THAT EXCEED 6'-0" UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS THE ARCHITECT/ENGINEER GRANTS WRITTEN
PERMISSION.
2. FEEDER AND BRANCH CIRCUIT CONDUCTORS, INCLUDING LOW VOLTAGE SYSTEMS, SHALL BE INSTALLED IN A COMPLETE
RACEWAY SYSTEM (CONDUIT) UNLESS SPECIFICALLY NOTED OTHERWISE.
3. THE USE OF ELECTRICAL NON-METALLIC TUBING (ENT) AND LIQUID-TIGHT FLEXIBLE NON-METALLIC CONDUIT (LFNC) ARE
PROHIBITED UNLESS SPECIFICALLY NOTED OTHERWISE, OR UNLESS THE ARCHITECT/ENGINEER OR OWNER GRANTS
WRITTEN PERMISSION.
4. CONNECTIONS TO TRANSFORMERS, AHU'S, AND PUMPS SHALL BE FLEXIBLE METAL CONDUIT (FMC) FOR INDOOR, DRY
LOCATIONS AND LIQUID-TIGHT FLEXIBLE METAL CONDUIT (LFMC) FOR EXTERIOR OR INDOOR WET LOCATIONS.
5. PVC CONDUIT SHALL NOT BE USED INSIDE BUILDING UNLESS OTHERWISE NOTED. UNDERGROUND OR IN-SLAB
INSTALLATIONS ARE ACCEPTABLE. WHERE AN UNDERGROUND RACEWAY ENTERS A BUILDING OR STRUCTURE, IT SHALL BE
SEALED AS PER NEC ARTICLES 230.8 AND 300.5(G). CONDUITS STUB-UPS WITHIN BUILDING SHALL BE MADE WITH
GALVANIZED RIGID CONDUIT. NO NON-METALLIC RACEWAY ALLOWED WITHIN BUILDING (ASSEMBLY OCCUPANCY, NEC
ARTICLE 518)
6. CONDUIT TERMINATIONS AT TERMINAL BOARDS SHALL HAVE GROUNDING BUSHINGS AT CONDUIT ENDS.
7. CONDUITS SHALL BE CONCEALED UNLESS IMPOSSIBLE DUE TO EXISTING CONDITIONS (I.E., EXPOSED CEILINGS, BUILDING
EXTERIOR WALL RUNS). CONCEAL CONDUITS ABOVE CEILINGS OR IN WALLS AND MILLWORK. WHERE EXISTING CONDITIONS
DICTATE THAT CONDUITS CANNOT BE CONCEALED, NOTIFY ARCHITECT/ENGINEER PRIOR TO INSTALLING CONDUIT FOR
RESOLUTION TO ROUTING.
8. SEAL PENETRATIONS AND OPENINGS MADE DURING EXECUTION OF WORK IN FIRE-RATED AND SMOKE-RATED WALLS.
WALLS SHALL BE SEALED WITH UL-APPROVED PRODUCT WITH THE SAME OR GREATER RATING OF WALL PENETRATED.
9. PROVIDE PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND ROOFS WHERE REQUIRED. COORDINATE LOCATIONS
AND SIZES WITH ARCHITECTURAL AND STRUCTURAL DRAWINGS, FIELD CONDITIONS AND WORK OF OTHER
DIVISIONS/TRADES. PENETRATIONS THROUGH FLOORS, WALLS, CEILINGS AND ROOFS SHALL BE WATERTIGHT.
10. RACEWAYS THAT TURN UP THROUGH THE SLAB OR INTO ELECTRICAL EQUIPMENT FROM UNDERGROUND SHALL BE RIGID
GALVANIZED STEEL (RGS) WITH BITUMASTIC COATING FOR AT LEAST THE FINAL 18" LENGTH. THE USE OF NON-METALLIC
CONDUIT ABOVE GRADE IS PROHIBITED.
11. PANEL SCHEDULES AND FLOOR PLANS MAY INDICATE DEDICATED HOMERUNS FOR EACH BRANCH CIRCUIT. BRANCH
CIRCUITS MAY BE GROUPED IN A COMMON HOMERUNS WHERE THE HOMERUN DOES NOT EXCEED 3 PHASE CONDUCTORS,
3 NEUTRAL CONDUCTORS, AND 1 EQUIPMENT GROUND. THE HOMERUN RACEWAY SIZE AND CONDUCTOR SIZE SHALL BE
INCREASED AS NECESSARY TO COMPLY WITH THE NEC FOR 40% MAXIMUM FILL AND DERATING REQUIREMENTS.
12. PROVIDE SEAL OFF FITTINGS, APPROVED FOR SUCH USE, WHERE RACEWAYS PENETRATE BETWEEN A DRY, CONDITIONED
ENVIRONMENT AND THE EXTERIOR OR OTHER WET ENVIRONMENTS AND ADDITIONAL AREAS WHERE CONDUITS PASS
FROM WARM TO COLD LOCATIONS SUCH AS WALK-IN COOLERS OR FREEZERS, BOILER ROOMS, ETC.
13. PROVIDE POLYOLEFIN JET-LINE #232 (NYLON PULL STRING) IN EACH EMPTY CONDUIT WITH ENGRAVED METAL TAG
INDICATING CONDUIT DESIGNATION.
14. HOMERUNS SHALL BE IN 3/4" RACEWAY MINIMUM. 1/2" RACEWAY IS ACCEPTABLE FOR A SINGLE CIRCUIT FROM THE
HOMERUN TO REMAINING DEVICES.
15. WHERE AN UNDERGROUND RACEWAY ENTERS A BUILDING OR STRUCTURE, IT SHALL BE SEALED AS PER NEC ARTICLES
230.8 AND 300.5(G).
16. CONDUIT SHALL USE SET SCREW TYPE FITTINGS OR COMPRESSION FITTINGS.
17. WHERE RACEWAYS ARE INSTALLED IN SLABS, THE MINIMUM SPACING, MAXIMUM RACEWAY SIZE, AND ANY OTHER
STRUCTURAL LIMITATIONS SHALL BE COORDINATED WITH THE STRUCTURAL DRAWINGS AND THE STRUCTURAL ENGINEER
PRIOR TO INSTALLATION.
IDENTIFICATION
1. PROVIDE TYPED PANEL DIRECTORIES FOR ALL NEW PANELBOARDS, AND EXISTING PANELBOARDS AFFECTED BY THIS PROJECT.
DIRECTORIES SHALL REFLECT PROJECT AS-BUILT CONDITIONS FOR BRANCH CIRCUITS. DIRECTORIES SHALL INCLUDE WHERE
EACH PANEL IS FED FROM. ADDITIONALLY, EACH BRANCH CIRCUIT LOAD DESCRIPTION SHALL INCLUDE THE ROOM NUMBER(S)
FOR EACH LOAD (I.E., RECEPTACLES-RMS 501,503). ROOM NUMBERS SHALL BE BASED ON ACTUAL ROOM SIGNAGE INSTALLED IN
FIELD. COORDINATE EXACT ROOM NUMBERS WITH ARCHITECT/ENGINEER AND OWNER PRIOR TO COMPLETION OF PANEL
DIRECTORIES.
2. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS ON EACH SWITCHBOARD, SWITCHGEAR, DISTRIBUTION PANEL,
PANELBOARD, MOTOR CONTROL CENTER, SAFETY SWITCH, ENCLOSED CIRCUIT BREAKER, CABINET, STEP-DOWN
TRANSFORMER, TRANSFER SWITCH, ETC., AND ANY OTHER MAJOR COMPONENT OF THE ELECTRICAL SYSTEM.
3. PROVIDE ENGRAVED PLASTIC LAMINATE NAME TAGS FOR EACH DISTRIBUTION BREAKER OR BRANCH CIRCUIT BREAKER IN
SWITCHGEAR, SWITCHBOARDS, MOTOR CONTROL CENTERS AND OTHER DISTRIBUTION EQUIPMENT. NAME TAG SHALL INCLUDE
LOAD DESCRIPTION AND ROOM NUMBER FOR EACH LOAD.
4. ARC FLASH DANGER/WARNING LABELS SHALL BE APPLIED TO SWITCHBOARDS, PANELBOARDS, EQUIPMENT CONTROLLERS AND
OTHER DISTRIBUTION EQUIPMENT PER NEC.
5. PROVIDE NEATLY, HANDWRITTEN IDENTIFICATION ON THE EXTERIOR COVER OF JUNCTION BOXES, PULLBOXES AND WIREWAYS,
IDENTIFYING THE PANEL(S)/ CIRCUIT NUMBER(S) CONTAINED WITHIN.
6. PROVIDE A PERMANENT LABEL ON PANELBOARDS, SWITCHBOARDS, SWITCHGEAR, MOTOR CONTROL CENTERS AND
DISTRIBUTION PANELS STATING "DO NOT WORK ON EQUIPMENT WHILE ENERGIZED. LOCK- OUT TAG-OUT REQUIRED".
7. PROVIDE REQUIRED IDENTIFICATION PER ANSI STANDARDS, NEC REQUIREMENTS, AND OWNER'S PUBLISHED DESIGN
STANDARDS WHERE APPLICABLE.
8. PROVIDE ENGRAVED PHENOLIC LABEL ON NEW SERVICE EQUIPMENT TO INDICATE THE MAXIMUM AVAILABLE FAULT CURRENT
AND THE DATE THE FAULT CURRENT CALCULATION WAS PERFORMED. PROVIDE LABEL ON EXISTING SERVICE EQUIPMENT WHEN
MODIFICATIONS OCCUR THAT AFFECT THE MAXIMUM AVAILABLE FAULT CURRENT AT THE SERVICE.
APPLICABLE CODES
APPLICABLE CODES:
WORK UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE AND IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF THE
FOLLOWING CODES AND STANDARDS INCLUDING THE REGULATIONS OF GOVERNING LOCAL, STATE, COUNTY AND OTHER
APPLICABLE CODES. REFER TO SPECIFICATIONS FOR ADDITIONAL CODE REQUIREMENTS:
BUILDING CODES:
• FLORIDA BUILDING CODE, 8TH EDITION (2023)
• FLORIDA ENERGY CONSERVATION CODE, 8TH EDITION (2023)
• FLORIDA FIRE PREVENTION CODE, 8TH EDITION (2023)
ADDITIONAL CODES, STANDARDS, AND REQUIREMENTS
1. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
2. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).
3. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).
4. REQUIREMENTS OF LOCAL POWER COMPANY.
5. THE AMERICANS WITH DISABILITIES ACT (ADA).
6. OWNER'S PUBLISHED DESIGN STANDARDS.
ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE LISTED BY A NATIONALLY RECOGNIZED TESTING LAB, AS
DEFINED BY OSHA. WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR CERTAIN TYPES OF EQUIPMENT, TEST DATA
SHALL BE SUBMITTED TO VALIDATE THAT EQUIPMENT MEETS OF EXCEEDS AVAILABLE STANDARDS.
NATIONAL FIRE PROTECTION (NFPA) STANDARDS:
• NFPA 70, 2020 EDITION, NATIONAL ELECTRICAL CODE®.
• NFPA 101, 2021 EDITION, LIFE SAFETY CODE®.
• NFPA 110, 2019 EDITION, STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS.
4. PROVIDE A GROUND BUS BAR IN EACH ELECTRICAL ROOM AND TELECOMMUNICATIONS / IDF/ MDF ROOM FOR NEW
CONSTRUCTION AND NEW ROOMS IN EXISTING CONSTRUCTION, AND IN EXISTING CONSTRUCTION WHERE THERE IS NONE
INSTALLED WITHIN AN EXISTING ROOM.
ELECTRICAL EQUIPMENT
1. EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN WHICH THEY ARE TO BE
INSTALLED. COMPONENTS OF THE ELECTRICAL SYSTEM LOCATED OUTDOORS OR INDOORS WHERE EXPOSED TO SIGNIFICANT
MOISTURE SHALL BE WEATHERPROOF, NEMA 3R, AS A MINIMUM, WHETHER INDICATED ON THE CONTRACT DRAWINGS OR NOT.
2. TERMINATION PROVISIONS FOR ELECTRICAL EQUIPMENT (PANELBOARDS, SWITCHBOARD, TRANSFORMERS, DISCONNECT
SWITCHES, MOTOR CONTROLLERS, AUTOMATIC TRANSFER SWITCHES, ENCLOSED CIRCUIT BREAKERS, BUSWAYS, ETC.) SHALL
BE LISTED AND IDENTIFIED FOR USE WITH MINIMUM 75 DEGREES FAHRENHEIT CONDUCTORS IN ACCORDANCE WITH NEC.
3. WORKING CLEARANCES FOR ELECTRICAL EQUIPMENT SHALL BE IN COMPLIANCE WITH NEC.
4. THE ELECTRICAL DEDICATED EQUIPMENT SPACE EXTENDING FROM FLOOR TO 6' ABOVE ELECTRICAL EQUIPMENT OR TO THE
STRUCTURAL CEILING, WHICHEVER DISTANCE IS LOWER, WITH A WIDTH AND DEPTH OF THE PANELBOARD OR SWITCHBOARD
MUST BE CLEAR OF PIPING, DUCTS, ARCHITECTURAL APPURTENANCES AND OTHER EQUIPMENT FOREIGN TO THE ELECTRICAL
INSTALLATION IN ACCORDANCE WITH NEC. IF SPACE IS AVAILABLE, FOREIGN SYSTEMS MAY BE PRESENT ABOVE THE
DEDICATED EQUIPMENT SPACE PROVIDED PROTECTION IS INSTALLED TO PREVENT DAMAGE TO ELECTRICAL EQUIPMENT
BELOW FROM CONDENSATION, LEAKS, OR BREAKS IN THESE SYSTEMS.
5. PROVIDE A REINFORCED CONCRETE PAD, SIZED 4" LARGER IN ALL DIRECTIONS THAN THE FOOTPRINT OF THE EQUIPMENT AND
FOR FREESTANDING, FLOOR-MOUNTED ELECTRICAL EQUIPMENT. PROVIDE VIBRATION ISOLATORS AND/OR ANCHORS PER
MANUFACTURER'S INSTRUCTIONS.
6. PROVIDE HACR RATED CIRCUIT BREAKER FOR HVAC EQUIPMENT.
5. CONDUCTORS SHALL BE COPPER UNLESS OTHERWISE NOTED, THHN/THWN-2 90 DEGREES CELSIUS; SOLID FOR #10 AWG AND
SMALLER; STRANDED FOR #8 AWG AND LARGER.
6. CONDUCTORS USED IN WET LOCATIONS, INCLUDING BUT NOT LIMITED TO UNDERGROUND CONDUITS/DUCTBANKS AND
EXTERIOR CONDUITS SHALL COMPLY WITH NEC 310.10 AND BE LISTED FOR USE IN WET LOCATIONS.
7. POWER CIRCUITS HAVE BEEN DESIGNED TO MEET 2% OR LESS VOLTAGE DROP FOR FEEDERS, AND 3% OR LESS VOLTAGE
DROP FOR BRANCH CIRCUITS.
8. BRANCH CIRCUIT NEUTRALS SHALL BE DEDICATED UNLESS OTHERWISE NOTED. CIRCUITS SHARING A COMMON NEUTRAL
MUST HAVE COMMON TRIP CIRCUIT BREAKERS TO ALLOW ALL TO BE TURNED OFF SIMULTANEOUSLY, AS PER NEC 210.4(B).
ELECTRICAL DEVICES OUTLET BOXES, JUNCTION BOXES
1. COMPONENTS OF THE ELECTRICAL SYSTEM (INCLUDE RACEWAYS, ELECTRICAL EQUIPMENT, OUTLET BOXES, JUNCTION BOXES,
ETC.) LOCATED IN A HAZARDOUS (CLASSIFIED) LOCATION SHALL BE APPROVED FOR USE IN SAID LOCATION, AS DEFINED BY THE
NEC, WHETHER INDICATED ON THE CONTRACT DOCUMENTS OR NOT.
2. DEVICES SHALL BE MOUNTED VERTICALLY, UNLESS NOTED OTHERWISE.
3. WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES, THEY SHALL BE INSTALLED WITHOUT
AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
A. ELECTRICAL BOXES SHALL BE METALLIC.
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY FILLED WITH JOINT COMPOUND (OR
OTHER APPROVED MATERIAL).
E. PROVIDE A WALL AROUND OUTLETS LARGER THAN 16 SQUARE INCHES. THE INTEGRITY OF THE WALL RATING SHALL BE
MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE INCHES PER 100 SQUARE FEET.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE RESISTIVE ASSEMBLIES SHALL BE SEPARATED BY A MINIMUM
HORIZONTAL DISTANCE OF 24 INCHES.
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED 1/8 INCH BETWEEN THE EDGES OF THE
OUTLET BOX AND THE EDGES OF THE OPENING.
SHEET
E001
E002
E101
E501
E601
ED101
ELECTRICAL DRAWING INDEX
DESCRIPTION
ELECTRICAL SYMBOLS, LEGEND, AND ABBREVIATIONS
ELECTRICAL GENERAL NOTES AND INDEX
ELECTRICAL PLAN
ELECTRICAL DETAILS
ELECTRICAL PANEL AND EQUIPMENT SCHEDULES
ELECTRICAL DEMO PLAN
WHERE THERE IS A DISCREPANCY BETWEEN ABOVE GENERAL NOTES AND SPECIFICATIONS, WHERE APPLICABLE, SPECIFICATIONS SHALL BE FOLLOWED
SEAL
ENGINEER OF RECORD
MONCEF M. HADIJI
DESIGNED BY
JOEY HOLT
DRAWN BY
JOEY HOLT
ISSUE DATE
12/01/2025
AE PROJECT NUMBER
525260
SHEET TITLE
ELECTRICAL GENERAL
NOTES AND INDEX
DRAWING NO.
E002
TOILET
700D
CH-1
MECH EQUIP AREA
713
TOILET
700C
M7-2
1
1
ELECTRICAL PLAN
1/4" = 1'-0"
EX OAC7
CUST
700A
PUMP & MECH. ROOM
712
PCH7-1
PCH7-2
P71-14,16,18
12
P71-38,40,42
12
T7
M7
M700
ELEC
711
P71
LV71
P701
C.E.R.
710C
STOR
710D
GENERAL NOTES
A. LAYOUT IS BASED UPON NON-INVASIVE FIELD INVESTIGATION AND LIMITED EXISTING AS-
BUILTS. CONTRACTOR SHALL NOTIFY THE ENGINEER OF RECORD OF ANY DISCREPANCIES
BETWEEN THIS LAYOUT AND FIELD CONDITIONS.
# KEYNOTES
1. SEE MECHANICAL EQUIPMENT SCHEDULE ON SHEET E601 FOR ALL CONDUCTOR, CONDUIT,
AND DISCONNECT SIZES.
2. REPLACEMENT OF PUMPS AND ASSOCIATED ELECTRICAL EQUIPMENT IS BID ALTERNATE 1.
SEAL
ENGINEER OF RECORD
MONCEF M. HADIJI
DESIGNED BY
JOEY HOLT
DRAWN BY
JOEY HOLT
ISSUE DATE
12/01/2025
AE PROJECT NUMBER
525260
SHEET TITLE
ELECTRICAL PLAN
DRAWING NO.
E101
METAL SUPPORT
STRUCTURE NEC
250-52(A)(2)
MAIN GROUNDING BUS
(GROUND BAR)
GROUNDING
ELECTRODE
CONDUCTOR
NEC 250-66
FINISHED GRADE
GROUND ROD NEC
250-52(A)(5)
INCOMING
SERVICE
SERVICE EQUIPMENT
MAIN
BUSSING
ABCN
SUPPLY SIDE BONDING JUMPER.
NEC 250-102
NEUTRAL BUS
MAIN BONDING JUMPER. NEC 250-102
1
EQUIPMENT GROUND BUS
GROUNDING ELECTRODE
CONDUCTOR. NEC 250-66
FINISHED FLOOR
NOTES:
1 BONDING JUMPER. NEC 250.102
PROVIDE COMPLETE GROUNDING ELECTRODE SYSTEM AND GROUNDING ELECTRODE CONDUCTOR IN ACCORDANCE WITH NEC
ARTICLE 250 AND NEC ARTICLE 250.50.
GROUNDING SYSTEM DETAIL
No Scale
2
FINISHED CEILING
WALL MOUNTED LIGHT FIXTURES
AS NOTED ON PLANS
PANELBOARD
C ABOVE COUNTER
TELE./DATA OUTLET
78" MAX.
TO TOP OF
HIGHEST
OPERABLE
DEVICE
6" AFC
36"
AFF
CENTERED
OVER DOOR
(CEILING OR WALL)
CL
6" MIN
CS CB SH T SE S D NCS NURSE CALL DEVICE
ABOVE COUNTER
RECEPTACLE
CL
3" (TYP)
48" TO
TOP OF
DEVICE
42" AFF W/36"H COUNTER,
39" AFF W/30"H COUNTER,
48" AFF WITHOUT COUNTER
OR AS NOTED ON PLANS
FINISHED FLOOR
NOTES:
1. MOUNTING HEIGHTS INDICATED ON ARCHITECTURAL ELEVATIONS, OTHER DISCIPLINES, AND ELECTRICAL PLANS TAKE PRECEDENCE OVER MOUNTING HEIGHTS INDICATED IN THIS
DETAIL. IF THERE IS A DISCREPANCY IN THE MOUNTING HEIGHTS BETWEEN ARCHITECTURAL ELEVATIONS, OTHER DISCIPLINES, AND THE ELECTRICAL PLANS, THE DIMENSIONS ON THE
ARCHITECTURAL ELEVATIONS AND OTHER DISCIPLINES SHALL DICTATE MOUNTING HEIGHT. IF NO MOUNTING HEIGHTS ARE INDICATED, INSTALL DEVICES PER THIS DETAIL.
2. NOT ALL DEVICES SHOWN APPLY TO PROJECT.
WALL-MOUNTED - CENTERED BETWEEN FLOORS & CEILING FOR CEILINGS 10' & LESS, 6"
ABOVE DOOR FRAME TO BOTTOM OF EXIT LIGHT FOR CEILINGS GREATER THAN 10'
(COORDINATE WITH ARCHITECTURAL ELEVATIONS)
WALL-MOUNTED FIRE ALARM STROBE,
SPEAKER/STROBE, HORN/STROBE, OR
SPEAKER
BOTTOM OF STROBE
LENS
MULTI-SERVICE BOX OR SINGLE BOX
DEVICES FOR TELEVISION OR MONITOR TV
FIRE ALARM PULL F
STATION
CL
80"
48" TO
TOP OF
DEVICE
WALL PHONE
W
LIGHT SWITCH S
VOICE/DATA
OUTLET
CL
18"
3" (TYP)
DUPLEX OR QUAD RECEPTACLE,
SPECIAL RECEPTACLE
WALL FURNITURE FEED (POWER OR
DATA)
MOUNTING HEIGHT SHALL BE
VERIFIED WITH ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN
CL
18"
MULTI-SERVICE BOX FOR AV EQUIP.
CABINET
TV
AV
MOUNTING HEIGHTS
No Scale
1
SEAL
AHU-X
480V, 3Ø
EMERGENCY BRANCH
FED FROM PANEL "XXXX-##"
AHU-X
480V, 3Ø
EMERGENCY BRANCH
FED FROM PANEL "XXXX-##"
TYPICAL EQUIPMENT
EQUIPMENT NAMEPLATE
No Scale
LETTERING COLOR PER SPECIFICATIONS U.O.N.
ON THIS DETAIL
1/16" THICK WHITE PLASTIC WITH FACE COLOR PER
SPECIFICATIONS U.O.N. ON THIS DETAIL
FASTEN WITH BRASS SCREWS WHEN LOCATED IN
NON-CONDITIONED OR EXTERIOR SPACES
IDENTIFY BRANCH OF THE ELECTRICAL SYSTEM
(E.G. NORMAL, CRITICAL, LIFE SAFETY, EQUIPMENT, EMERGENCY,
LEGALLY-REQUIRED STANDBY, OPTIONAL STANDBY)
ADHESIVE BACKING WHEN INSTALLED
IN CONDITIONED INTERIOR SPACES (SILICONE
SEALANT AROUND OUTSIDE EDGE TO PREVENT
MOISTURE DAMAGE TO ADHESIVE BACKING)
EQUIPMENT NAME (1/2" HIGH LETTERING)
1/4" HIGH LETTERING FOR
REMAINING TEXT
EQUIPMENT VOLTAGE
BRANCH OF ELECTRICAL SYSTEM
EQUIPMENT SOURCE (PANEL & CIRCUIT)
BRANCH
LIFE SAFETY
EQUIPMENT
CRITICAL
NORMAL
UPS
PLATE AND LETTERING COLOR
YELLOW WITH BLACK LETTERING
GREEN WITH WHITE LETTERING
ORANGE WITH WHITE LETTERING
BLACK WITH WHITE LETTERING.
BLUE WITH WHITE LETTERING
3
ENGINEER OF RECORD
MONCEF M. HADIJI
DESIGNED BY
JOEY HOLT
DRAWN BY
JOEY HOLT
ISSUE DATE
12/01/2025
AE PROJECT NUMBER
525260
SHEET TITLE
ELECTRICAL DETAILS
DRAWING NO.
E501
This page summarizes the opportunity, including an overview and a preview of the attached documents.
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.

Sign-up for a Free Trial, Government Bid Alerts

With Free Trial, you can:

You will have a full access to bids, website, and receive daily bid report via email and web.

Try One Week FREE Now

See Also

ITB No. 26-05 Lakes by the Bay Parking Lot and Walkway Retrofit Project

Cutler Bay town

Bid Due: 6/25/2026

Description: Belle Glade Water Main Improvements-SE Zone 6 Water System Department: Water Utilities

Palm Beach County

Bid Due: 1/23/2030

Description: Government Center 11th and 12th floor - Minor Renovation Department: Facilities Dev

Palm Beach County

Bid Due: 7/06/2030

Description: Government Center 11th and 12th floor - Minor Renovation Department: Facilities Dev

Palm Beach County

Bid Due: 8/14/2030