Protective Relays and RTAC Equipment

Agency: State Government of North Carolina
State: North Carolina
Type of Government: State & Local
NAICS Category:
  • 423840 - Industrial Supplies Merchant Wholesalers
Posted Date: Apr 7, 2026
Due Date: Apr 14, 2026
Solicitation No: 320-2026-609
Original Source: Please Login to View Page
Contact information: Please Login to View Page
Bid Documents: Please Login to View Page
Solicitation Number: 320-2026-609
Project Title: Protective Relays and RTAC Equipment
Description: The City of Rocky Mount is requesting informal quotations for the purchase of microprocessor based protective relays and a real-time automation controller (RTAC) for a substation upgrade. The total purchase is expected to be under $30,000.00.
Opening Date: 4/14/2026 5:00 PM
Posted Date: 4/7/2026
Status: Open
Department: CITY OF ROCKY MOUNT
Solicitation Number
*
320-2026-609
Department
CITY OF ROCKY MOUNT
Status Reason
Open
Opening Date
2026-04-14T17:00:00.0000000
Posted Date
*
2026-04-07T13:14:20.0000000Z
Primary Commodity Code
Automation control connectivity devices
Mandatory Conference/Site Visit
Special Instructions
Solicitation Type
*
Select RFP IFB RFI
Owner
Tracy Winfield
Description
The City of Rocky Mount is requesting informal quotations for the purchase of microprocessor based protective relays and a real-time automation controller (RTAC) for a substation upgrade. The total purchase is expected to be under $30,000.00.

Attachment Preview

City of Rocky Mount-Energy Resource
Request for Quotation (RFQ) Informal Purchase (Under $30,000.00)
Protective Relays and RTAC Equipment
RFQ Number: 2026-609
Issue Date: April 6, 2026
Quote Due Date: April 14, 2026
1. Purpose
The City of Rocky Mount is requesting informal quotations for the purchase of microprocessor-
based protective relays and a real-time automation controller (RTAC) for a substation upgrade.
This is an informal RFQ and not a formal bid solicitation. The total purchase is expected to be
under $30,000.
2. Scope of Work / Specifications
Vendors shall provide pricing and lead times for the following equipment:
Transformer Protection Relay
Protection Functions
The Transformer relay shall provide:
o Two-winding current differential protection
o Phase and ground overcurrent protection
o Backup protection functions
o Event reporting and fault oscillography
Current Inputs
o Six (6) AC current inputs
o 5 AMP CT secondary rating for both transformer windings
User Interface
o English Language
o Two-line, sixteen-character (2x 16) LCD display
o Minimum eight (8) front-panel push buttons
Power Supply
o 24-48 VDC control power supply
Digital Inputs and Outputs
o Four (4) programmable digital inputs
o Four (4) programmable electromechanical outputs (Form A contacts)
o Digital input rating: 48 VDC/VAC
Communication
o One (1) 10/100 Base-T Ethernet port (RJ-45)
o One (1) rear EIA-232 serial port
o DNP3 protocol support
o SEL communication protocol support
o Mirrored Bits® communication support
2. Feeder Protection Relay
Protection Functions
The feeder relay shall provide:
o Phase overcurrent protection
o Ground overcurrent protection
o Voltage-based protection functions
o Event reporting and disturbance recording
Current and Voltage Inputs
o Phase current inputs rated for 5 Amp CT secondary
o Neutral current input rated for 5 Amp
o Three-phase AC voltage inputs rated up to 300 VAC
User Interface
o English Language
o Two-line, sixteen-character (2x 16) LCD display
o Front-panel push buttons for local control and configuration
Power Supply
o 24-48 VDC control power supply
Digital Inputs and Outputs
o Four (4) programmable digital inputs
o Four (4) programmable electromechanical outputs (Form A contacts)
o Digital input rating: 48 VDC/VAC
Communications
o One (1) 10/100 Base-T Ethernet port (RJ-45)
o One (1) rear EIA-232 serial port
o DNP3 protocol support
o SEL communication protocol support
o Mirrored Bits® communications support
3. REAL-TIME AUTOMATION CONTROLLER (RTAC)
General: The automation controller shall serve as the substation data concentrator and logic
processor.
Processor and Memory
o Industrial-grade processor suitable for substation temperature range
o Minimum 8 GB RAM
o Industrial-grade solid-state drive (minimum 480 GB)
o Processor Intel Atom x5-E3940 Quad Core
Operating System
o Manufacturer's real-time automation operating system
Mounting
o 3U rack-mounted chassis suitable for installation in substation control panel
Power Supply
o 48-125 VDC or 110-120 VAC control power compatible
Communications
o Minimum four (4) rear Ethernet ports (10/100/1000 Mbps RJ-45)
o Serial communications- minimum 32 serial ports via expansion module
o DNP3 protocol support
o SEL communication protocol support
o Mirrored Bits® communication support
Functional Capabilities: The RTAC shall
o Provide programmable logic control function
o Serve as a SCADA data concentrator
o Interface with protective relays via Ethernet and serial communications
o Support peer-to-peer messaging with SEL relays
Communications Integration Requirement- All devices furnished shall be fully
compatible and capable of:
o Operating on the Owner's existing SEL-based communication architecture
o Exchanging high-speed peer-to-peer signals using Mirrored Bits®
o Integrating into the Owner's DNP3 SCADA system
3. General Requirements
All relays and automation equipment furnished under this specification shall:
Be new, utility-grade, microprocessor-based devices.
Be from a single manufacturer to ensure full communication compatibility and
interoperability.
Support SEL communication protocol.
Support Mirrored Bits® communication for high-speed peer-to-peer relay messaging.
Be suitable for installation in an electrical substation environment.
Operate on station services control voltage as specified.
Included Ethernet communications capability.
Support DNP3 protocol for SCADA integration.
Included event reporting and oscillography.
Be configurable using manufacturer-provided software tools.
Meet applicable IEEE C37 standards for protective relays.
Included a minimum ten (10) year manufacturer warranty.
4. Quote Submission Requirements
Quotes must include:
- Company information
- Pricing
- Lead times
- Warranty
- Shipping terms
Submit via email to: Fantashia.Dickens@rockymountnc.gov
5. Questions
All questions must be submitted via email to Fantashia.Dickens@rockymountnc.gov prior to the
due date.
6. Award
Award will be made to the lowest responsive, responsible vendor, or in the best
interest of the City. The City reserves the right to reject any or all quotes.
This page summarizes the opportunity, including an overview and a preview of the attached documents.
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.

Sign-up for a Free Trial, Government Bid Alerts

With Free Trial, you can:

You will have a full access to bids, website, and receive daily bid report via email and web.

Try One Week FREE Now

See Also

Follow Base Telephone Parts Active Contract Opportunity Notice ID M6700126Q0008 Related Notice M6700126Q0008

DEPT OF DEFENSE

Bid Due: 6/12/2026

Solicitation Number: Doc2136726873 Project Title: 30-26264-DSDHH - Assistive Telecommunication Devices Description: The purpose

State Government of North Carolina

Bid Due: 6/30/2026

Follow Base Telephone Parts Active Contract Opportunity Notice ID M6700126Q0008 Related Notice M6700126Q0008

DEPT OF DEFENSE

Bid Due: 6/12/2026

RFP Number 2710 ReBid - Electrical Services - Housing Department Submissions Due: 6-12-2026

City of Concord

Bid Due: 6/12/2026