4120--Portable HVACs and Mobile Generator
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Colorado |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Set Aside: | Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14) |
| Posted Date: | Jul 23, 2025 |
| Due Date: | Jul 24, 2025 |
| Solicitation No: | 36C25925Q0617 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
- Updated Published Date: Jul 23, 2025 03:36 pm MDT
- Original Published Date: Jul 14, 2025 11:01 am MDT
- Updated Date Offers Due: Jul 24, 2025 02:00 pm MDT
- Original Date Offers Due: Jul 24, 2025 02:00 pm MDT
- Inactive Policy: Manual
- Updated Inactive Date: Aug 23, 2025
- Original Inactive Date: Aug 23, 2025
-
Initiative:
- None
- Original Set Aside: Service-Disabled Veteran-Owned Small Business (SDVOSB) Set-Aside (FAR 19.14)
- Product Service Code: 4120 - AIR CONDITIONING EQUIPMENT
-
NAICS Code:
- 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
-
Place of Performance:
Department of Veterans Affairs Eastern Colorado Health Care System Aurora , 80045USA
Regarding the HVAC units. The specs indicate the ducting must be 12 and 14 in diameter but it doesn t note the type or length. What length is needed? Will it need a certain type of duct material: flex duct, portable AC duct, inflatable, etc.? Does the powder coat finish on the cabinet need to come from the manufacturer that way or can it be added?
As far as the material, vinyl or portable a/c duct is needed. As far as length, 50 for each unit would be needed. Powder coat finish needs to come from manufacturer.
- 6162 S WILLOW DR SUITE 300
- Greenwood Village , CO 80111
- USA
- Noaa Lanotte
- Noaa.Lanotte@va.gov
- Phone Number 303-712-5794
- Jul 23, 2025 03:36 pm MDTCombined Synopsis/Solicitation (Updated)
- Jul 14, 2025 11:01 am MDT Combined Synopsis/Solicitation (Original)
Related Document
| Jul 14, 2025 | [Combined Synopsis/Solicitation (Original)] 4120--Portable HVACs and Mobile Generator |
See Also
Follow USAFA Liquid Nitrogen Plant /Generator Active Contract Opportunity Notice ID FA700026Q0111 Related
DEPT OF DEFENSE
Due by 9/15/2026
Removal and Installation of Cambridge M118 Air Unit at Clarifier Building at Persigo
City of Grand Junction
Due by 10/01/2026
General Information Document ID DQ1-GJJA-2027000096-2 Status Amended Description DQ 27-004 Cooling Tower Replacement
State Government of Colorado
Due by 9/15/2026
General Information Document ID DQ1-GJJA-2027000096-1 Status Open Description DQ 27-004 Cooling Tower Replacement
State Government of Colorado
Due by 9/15/2026