PAO Chiller System
| Agency: | DEPT OF DEFENSE |
|---|---|
| State: | Utah |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Jan 29, 2026 |
| Due Date: | Feb 9, 2026 |
| Solicitation No: | 14816 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Sources Sought (Updated)
- Updated Published Date: Jan 29, 2026 03:12 pm MST
- Original Published Date: Sep 18, 2025 10:46 am MDT
- Updated Response Date: Feb 09, 2026 09:00 am MST
- Original Response Date: Sep 25, 2025 12:00 pm MDT
- Inactive Policy: 15 days after response date
- Updated Inactive Date: Feb 24, 2026
- Original Inactive Date: Oct 10, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: 1660 - AIRCRAFT AIR CONDITIONING, HEATING, AND PRESSURIZING EQUIPMENT
-
NAICS Code:
- 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
-
Place of Performance:
Hill Air Force Base , UT 84056USA
PAO Chiller System. Please see Sources Saught doc and Equipment List attached.
Follow up from initial RFI request (PAO Chiller System (Notice ID: 14816), provide capabilities for the following? The full SOW is also attached for reference.
- Provide and install all material to construct overflow basin for PAO chillers and pumps.
-
Mechanical Room to House PAO Chillers
- 5.3.1 The Contractor shall construct a dedicated, sound-attenuated room at the designated
location to house the PAO chillers. The room shall meet the following specifications:
-
- 5.3.2 Walls: Construct walls using 6-inch, 16-gauge metal studs with 5/8-inch drywall on both
sides. Install R-21 insulation within the framing. Extend walls from the true floor to the
underside of the metal deck above, effectively creating a full-height barrier.
-
- 5.3.3 Sound Attenuation: The complete room assembly (walls and doors) must achieve a Sound
Transmission Class (STC) rating of 45.
-
- 5.3.4 Doors: Install doors with a minimum STC rating of 45. Provide at least one door of sufficient
size to facilitate the passage of the PAO chillers during installation and maintenance.
-
- 5.3.5 Finishes: Paint the walls to match the existing laboratory aesthetic.
- 5.3.6 Floor and Ceiling Integration: The Contractor shall modify the existing raised access floor and
grid ceiling as necessary to accommodate the new wall placement and chiller skid, ensuring a
seamless and integrated appearance. This modification shall not be done until the
mechanical room is in place and the Chiller skids arrive.
-
Chiller Support and Containment
- 5.4.1 The chiller room shall house the support and isolation stand(s) for the PAO chillers.
- 5.4.2 Each stand shall include a containment pan to meet the contract requirements, unless the
chiller units have integrated containment features.
-
- 5.4.3 The new mechanical room layout must accommodate the Pall Filter unit.
- 5.4.4 The height of the support stands shall match the existing raised access floor height.
- 5.4.5 In-fill the area around the stands with raised access floor panels to maintain a consistent
floor surface.
-
Paint/Finish
- 5.6.1 Any damage to paint must be repaired using 1 coat primer and 2 coats paint and shall match
existing paint.
-
Plumbing
- 5.8.1 Contractor shall direct the overflow drain line to an overflow drain catch. This overflow drain
catch must be separate from the spill catch system.
-
- 5.8.2 If the allocated space is not sufficiently sized for the PAO chiller system, the Contractor shall
propose an alternate solution before contract is awarded.
- CP 801 777-8958 6038 ASPEN AVE BLDG 1289
- HILL AFB , UT 84056-5805
- USA
- jonathan Graham
- jonathan.graham.11@us.af.mil
- Phone Number 8015863365
- jonathan Graham
- jonathan.graham.11@us.af.mil
- Phone Number 8015863365
- Jan 29, 2026 03:12 pm MSTSources Sought (Updated)
- Jan 29, 2026 03:00 pm MST Sources Sought (Updated)
- Oct 10, 2025 10:04 pm MDT Sources Sought (Original)
Related Document
| Sep 18, 2025 | [Sources Sought (Original)] PAO Chiller System |
| Mar 5, 2026 | [Combined Synopsis/Solicitation (Updated)] 14816 PAO Chiller System Combined Synopsis/Solicitation |
| Mar 19, 2026 | [Combined Synopsis/Solicitation (Updated)] 14816 PAO Chiller System Combined Synopsis/Solicitation |
See Also
Project: Cloud Based Phone System for Davis County (Re-post) Ref. #: DC2026-06 Department:
State Government of Utah
Due by 9/28/2026
Follow STATOR TUBE, TORQUE, C-130 Active Contract Opportunity Notice ID SPRHA1-26-Q-0849 Related Notice
DEPT OF DEFENSE
Due by 10/02/2026
Project: SLCo FAC133242 ADC Heat Exchangers - Final Phase- CONST Ref. #: SLCo
State Government of Utah
Due by 9/17/2026