| 130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020 |
| CERT. OF AUTH. No. 5096 FAX (407) 740-0365
MPE JOB #2:025-135 |
| ADDING BASEBALL FIELD LIGHTING TO THE EXISTING BASEBALL FIELD AS SHOWN ON THESE DRAWINGS AND DESCRIBED IN
THE PROJECT MANUAL.
Engineer's Statement of Compliance
To the best of my knowledge, these drawings and the project manual are complete and comply with
the Florida Building Code. |
| BUILDING DATA |
| A. SURVEY PARCEL ID XXX
B. LEGAL DESCRIPTION XXX
C. OCCUPANCY TYPE Educational
D. CONSTRUCTION TYPE XXX
E. RISK CATEGORY XXX
F. AUTOMATIC SPRINKLER XXX
G. BUILDING AREA XXX
H. BUILDING HEIGHT XXX
I. OCCUPANT LOAD XXX |
| LOCATION MAP |
| SHEET INDEX |
|
|
| SHEET
NO. |
SHEET NAME |
SCALE |
| G001 |
COVER SHEET |
NONE |
| E001 |
GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS |
NONE |
| E100 |
SITE PLAN - ELECTRICAL |
1" = 50' |
| E101 |
PARTIAL SITE PLAN - ELECTRICAL - RENOVATION |
1" = 20'-0" |
| E102 |
PARTIAL SITE PLAN - ELECTRICAL - RENOVATION |
1" = 20'-0" |
| E501 |
DETAILS |
NONE |
| E502 |
DETAILS |
NONE |
| E503 |
DETAILS |
NONE |
| E504 |
DETAILS |
NONE |
| E601 |
POWER RISER DIAGRAM AND SCHEDULES |
NONE |
| E602 |
SCHEDULES |
NONE |
| DESIGNED BY
AWB |
DRAWN BY
MM |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
COVER SHEET |
|
SCHOOL BOARD
MAINLAND HIGH
MEMBERS
BASEBALL FIELD
LIGHTING
VCS Project NO. 2648275
DESCRIPTION OF WORK ENGINEERS & CONSULTANTS
ADDING BASEBALL FIELD LIGHTING TO THE EXISTING BASEBALL FIELD AS SHOWN ON THESE DRAWINGS AND DESCRIBED IN
THE PROJECT MANUAL.
Engineer's Statement of Compliance
To the best of my knowledge, these drawings and the project manual are complete and comply with
the Florida Building Code.
BUILDING DATA
A. SURVEY PARCEL ID XXX
B. LEGAL DESCRIPTION XXX
C. OCCUPANCY TYPE Educational
D. CONSTRUCTION TYPE XXX
E. RISK CATEGORY XXX
F. AUTOMATIC SPRINKLER XXX
G. BUILDING AREA XXX
H. BUILDING HEIGHT XXX
I. OCCUPANT LOAD XXX
LOCATION MAP
NOT TO SCALE
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
VOLUSIA 130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
COUNTY SCHOOLS MPE JOB #2:025-135
"LEADING WITH GRACE AND RESPECT" Ruben Colon Board Chair
Krista Goodrich Board Vice Chair
Donna Brosemer Member
Jamie Haynes Member
THE SCHOOL BOARD OF VOLUSIA Jessie Thompson Member
COUNTY FLORIDA
200 North Clara Avenue Carmen J. Balgobin Superintendent
DeLand, Florida 32720
MATERN PROFESSIONAL ENGINEERING
130 Candace Drive
Maitland, Fl 32715
407-740 -5020
Adrian Baus
abaus@matern.net 130 Candace Drive
http://matern.net Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
ARCH/ENGR OF RECORD
Engineer
Adrian Baus
DESIGNED BY DRAWN BY
AWB MM
ISSUE DATE AE PROJECT NUMBER
02/20/2026 2025-135
SHEET TITLE
COVER SHEET
CONSTRUCTION DOCUMENTS 02/20/2026
DRAWING NO.
G001
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
1255 W INTERNATIONAL SPEEDWAY
BLVD, DAYTONA BEACH, FL 32114
SHEET INDEX
SHEET
SHEET NAME SCALE
NO.
G001 COVER SHEET NONE
E001 GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS NONE
E100 SITE PLAN - ELECTRICAL 1" = 50'
E101 PARTIAL SITE PLAN - ELECTRICAL - RENOVATION 1" = 20'-0"
E102 PARTIAL SITE PLAN - ELECTRICAL - RENOVATION 1" = 20'-0"
E501 DETAILS NONE
E502 DETAILS NONE
E503 DETAILS NONE
E504 DETAILS NONE
E601 POWER RISER DIAGRAM AND SCHEDULES NONE
E602 SCHEDULES NONE
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE AE PROJECT NUMBER
02/20/2026 2025-135
SHEET TITLE |
|
| GENERAL NOTES,
SYMBOL LEGEND,
AND ABBREVIATIONS |
|
"
34"
"
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
GENERAL NOTES,
SYMBOL LEGEND,
AND ABBREVIATIONS
E001
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
SITE PLAN -
ELECTRICAL |
|
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
SITE PLAN - ELECTRICAL
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
SITE PLAN -
ELECTRICAL
E100
| DESIGNED BY DRAWN BY
AWB MM/AWB |
| ISSUE DATE AE PROJECT NUMBER
02/20/2026 2025-135
SHEET TITLE
PARTIAL SITE PLAN -
ELECTRICAL -
RENOVATION |
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
PARTIAL SITE PLAN - ELECTRICAL - RENOVATION
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
PARTIAL SITE PLAN -
ELECTRICAL -
RENOVATION
E101
AREA OF WORK PARTIAL KEYPLAN
| DESIGNED BY DRAWN BY
AWB MM/AWB |
| ISSUE DATE AE PROJECT NUMBER
02/20/2026 2025-135
SHEET TITLE
PARTIAL SITE PLAN -
ELECTRICAL-
RENOVATION
DRAWING NO. |
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
PARTIAL SITE PLAN - ELECTRICAL - RENOVATION
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
AREA OF WORK
PARTIAL SITE PLAN -
ELECTRICAL-
RENOVATION
E102
PARTIAL KEYPLAN
| POLE |
DECRIPTION |
#LUMINAIRES/POLE LUMINAIRE |
FIXTURE GROUP
MOUNTING
MODEL POLE HEIGHT HEIGHT |
CONTACTOR |
FLA CONTACTOR SIZ |
E CIRCUIT SIZE ZONE |
| A2 |
BASEBALL |
4 MUSCO TLC- |
LED-1500 80'
C-BT-575 80' 19' |
C1 |
12.74 30 |
20 B |
|
|
|
|
|
|
|
|
|
1 MUSCO TL |
|
|
|
|
| A3 |
BASEBALL |
4 MUSCO TLC- |
LED-1500 80'
C-BT-575 80' 16' |
C2 |
12.74 30 |
20 B |
|
|
1 MUSCO TL |
|
|
|
|
|
|
|
|
|
|
|
| B2 |
BASEBALL |
6 MUSCO TLC- |
LED-1500 80'
C-BT-575 80'
80'
80
16' |
C3 |
15.00 30 |
20 B |
|
|
1 MUSCO TL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| B3 |
BASEBALL |
6 MUSCO TLC- |
LED-1500 80'
C-BT-575 80'
80'
80
16' |
C4 |
15.00 30 |
20 B |
|
|
1 MUSCO TL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| C1 |
BASEBALL |
5 MUSCO TLC- |
LED-1500 70'
C-BT-575 70' 70'
16' |
C5 |
12.74 30 |
20 B |
|
|
2 MUSCO TL |
|
|
|
|
|
|
|
|
|
|
|
| C2 |
BASEBALL |
5 MUSCO TLC- |
LED-1500 70'
C-BT-575 70' 70'
16' |
C6 |
12.75 30 |
20 B |
|
|
2 MUSCO TL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TOTAL |
|
38 |
|
|
80.97 |
|
| LUMINAIRE DESCRIPTION |
|
|
|
|
| TYPE |
SOURCE WATT |
AGE MAX AMPS LUMENS |
L90 |
L80 L70 |
| TLC-LED-1500 |
LED 5700K - 75 CRI 1410 W |
ATTS 3.6 181,000 |
>120,000 |
>120,000 >120,000 |
| TLC-LED-1200 |
LED 5700K - 75 CRI 1170 W |
ATTS 3.0 150,000 |
>120,000 |
>120,000 >120,000 |
| TLC-LED-900 |
LED 5700K - 75 CRI 880 WA |
TTS 2.3 104,000 |
>120,000 |
>120,000 >120,000 |
| TLC-BT-575 LED |
LED 5700K - 75 CRI 575 WA |
TTS 1.5 52,000 |
>120,000 |
>120,000 >120,000 |
|
|
| 2 1
7
2
3
4
14
5
6"
6
1
7
4"
(*)
(*)
10
12
8
4
13 3
10 9
10 4"
10
14 6
5
8
5" *
9
11 11
12
13
14
FLUSH GRADE HANDHOLE DETAIL - 'PBD2' |
|
| CALCULATON GRID SUMMARY |
|
|
|
|
| GRID NAME |
CALCULATION METRIC AVERAGE MINIMUM MAXIMUM MAX/MIN ZONES OPERATIN |
|
|
|
| INFIELD |
HORIZONTAL ILLUMINANCE |
51.05 36.14 |
63.36 |
1.75 B |
| OUTFIELD |
HORIZONTAL ILLUMINANCE |
33.97 24.7 |
44.50 |
1.80 B |
|
|
|
|
|
|
|
|
|
|
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
DETAILS |
|
BASEBALL FIELD POLE /FIXTURE SCHEDULE
FIXTURE GROUP
MOUNTING
POLE DECRIPTION #LUMINAIRES/POLE LUMINAIRE MODEL POLE HEIGHT HEIGHT CONTACTOR FLA CONTACTOR SIZE CIRCUIT SIZE ZONE PANEL /CKT
A2 BASEBALL 4 MUSCO TLC-LED-1500 80'
1 MUSCO TLC-BT-575 80' 19' C1 12.74 30 20 B HBBF-1:3:5
A3 BASEBALL 4 MUSCO TLC-LED-1500 80'
1 MUSCO TLC-BT-575 80' 16' C2 12.74 30 20 B HBBF-7:9:11
B2 BASEBALL 6 MUSCO TLC-LED-1500 80'
1 MUSCO TLC-BT-575 80'
80' C3 15.00 30 20 B HBBF-13:15:17
80
16'
B3 BASEBALL 6 MUSCO TLC-LED-1500 80'
1 MUSCO TLC-BT-575 80'
80' C4 15.00 30 20 B HBBF-19:21:23
80
16'
C1 BASEBALL 5 MUSCO TLC-LED-1500 70'
2 MUSCO TLC-BT-575 70' 70' C5 12.74 30 20 B HBBF-25:27:29
16'
C2 BASEBALL 5 MUSCO TLC-LED-1500 70'
2 MUSCO TLC-BT-575 70' 70' C6 12.75 30 20 B HBBF-31:33:35
16'
TOTAL 38 80.97
LUMINAIRE DESCRIPTION
TYPE SOURCE WATTAGE MAX AMPS LUMENS L90 L80 L70 QUANTITY
TLC-LED-1500 LED 5700K - 75 CRI 1410 WATTS 3.6 181,000 >120,000 >120,000 >120,000 30
TLC-LED-1200 LED 5700K - 75 CRI 1170 WATTS 3.0 150,000 >120,000 >120,000 >120,000
TLC-LED-900 LED 5700K - 75 CRI 880 WATTS 2.3 104,000 >120,000 >120,000 >120,000
TLC-BT-575 LED LED 5700K - 75 CRI 575 WATTS 1.5 52,000 >120,000 >120,000 >120,000 8
CALCULATON GRID SUMMARY
# FIXTURES
GRID NAME CALCULATION METRIC AVERAGE MINIMUM MAXIMUM MAX/MIN ZONES OPERATING
OPERATING
INFIELD HORIZONTAL ILLUMINANCE 51.05 36.14 63.36 1.75 B 38
OUTFIELD HORIZONTAL ILLUMINANCE 33.97 24.7 44.50 1.80 B 38
2 1
7
2
3
4
14
5
6"
6
1
7
4"
(*)
(*)
10
12
8
4
13 3
10 9
10 4"
10
14 6
5
8
5" * ARCH/ENGR OF RECORD
9
11 11 DESIGNED BY DRAWN BY
12
ISSUE DATE AE PROJECT NUMBER
13
14
DRAWING NO.
FLUSH GRADE HANDHOLE DETAIL - 'PBD2'
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
DETAILS
E501
| GROUND WELL DETAIL (MAIN SERVICE) FOR
GRASSY UNPAVED NON-TRAFFIC AREAS |
|
|
|
|
CHILLER CH-1
HEAT TAPE
20 AMP 120V 1PH 2W
FED FROM
1L1-73 LOCATED IN
BUILDING 1 ROOM 01-142
TYPICAL NAMEPLATE |
|
GROUND WELL DETAIL - POLE LIGHTING |
|
| WARNIN
! |
| Arc Flash and Shock H
Appropriate PPE Requ |
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
DETAILS |
|
DISCONNECT RACK (DOUBLE) -
FREESTANDING/GRADE MOUNTED
GROUND WELL DETAIL (MAIN SERVICE) FOR
GRASSY UNPAVED NON-TRAFFIC AREAS
CHILLER CH-1
HEAT TAPE
20 AMP 120V 1PH 2W
FED FROM
1L1-73 LOCATED IN
BUILDING 1 ROOM 01-142
WARNING
!
Arc Flash and Shock Hazard
Appropriate PPE Required
NOTES
PROVIDE/INSTALL SIGN ON ALL EQUIPMENT PER ANSI, NEC, AND OSHA.
ANSI Z535.4-2011, PRODUCT SAFETY SIGNS AND LABELS, PROVIDES GUIDELINES FOR
THE DESIGN OF SAFETY SIGNS AND LABELS FOR APPLICATION TO PRODUCTS.
TYPICAL NAMEPLATE
"ARC FLASH AND
ARCH/ENGR OF RECORD
SHOCK HAZARD" SIGN GROUND WELL DETAIL - POLE LIGHTING
N.T.S AFSH DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
DETAILS
E502
| LIGHTING FIXTURE SCHEDULE |
|
|
|
|
|
|
|
| VCS - MAINLAND HIGH |
|
|
|
|
|
|
|
| TYPE
SLB |
DESCRIPTION
ONE (1) ARM MOUNTED LED SHOEBOX LUMINAIRE, TYPE V
DISTRIBUTION, DARK BRONZE COLOR, MOUNT 20'-0" AFG
TO DIRECT BURIED CONCRETE POLE WITH 155 MPH WIND
LOADING BASED ON EMBEDMENT IN SAND |
APPROVED
DESIGN SELECTION
SUBSTITUTION
LEOTEK LIGHTING #
CURRENT LIGHTING #
ASL1 160L-115 4K7 5QW UNV MAF SP DBT
POLE:
SEMINOLE POLES # 28FT
PRE-CAST SPECIALTIES
(NOTE 9 & 10)
(NOTE 9 & 10) |
APPROVED
VOLTS
SUBSTITUTION
LITHONIA/ACUITY# 277
# |
CCT
4000K |
WATTAGE
110 |
LUMENS
15,632 |
LAM
LE |
| SLC |
ONE (1) ARM MOUNTED LED SHOEBOX LUMINAIRE, TYPE III
DISTRIBUTION, DARK BRONZE COLOR, MOUNT 20'-0" AFG
TO DIRECT BURIED CONCRETE POLE WITH 155 MPH WIND
LOADING BASED ON EMBEDMENT IN SAND |
LEOTEK LIGHTING #
CURRENT LIGHTING #
ASL1 160L-115 4K7 3 UNV MAF SP DBT
POLE:
SEMINOLE POLES # 28FT
PRE-CAST SPECIALTIES
(NOTE 9 & 10)
(NOTE 9 & 10) |
LITHONIA/ACUITY# 277
# |
4000K |
110 |
15,413 |
LE |
| LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILIN
(2) ALL FIXTURES TO HAVE IN-LINE FUSE AND FUSE HOLDER.
(3) PROVIDE MANUFACTURER'S POINT BY POINT PHOTOMETRIC ANALYSIS FOR SITE LIGHTING WITH SUBMITTALS 10 DAYS PRIOR TO BID FOR APPROVAL BY DESIGN ENGINEER.. PROVDIE EMBEDMENT DETAILS FOR SAND
(4) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS. ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHE
CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM PER SPECIFICATIONS.
(5) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NO
REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI
REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.
(6) MOUNT LINEAR FIXTURES TOGETHER, END TO END, WHERE SHOWN IN CONTINUOUS ROWS.
(7) MANUFACTURER SHALL PROVIDE A WARRENTY AGAINST LOSS OF PERFORMANCE AND DEFECTS IN MATERIALS AND WORKMANSHIP FOR THE LUNINAIRS FOR A PERIOD OF 10 YEARS AFTER ACCEPTANCE OF THE LUMINAIRES. WARRANTY SHALL COVER ALL
COMPONENTS COMPRISING THE LUMINAIRE.
(8) AT TIME OF PURCHASE, ALL APPROVED MANUFACTURERS MUST BE USING CREE, PHILLIPS, SAMSUNG, BRIDGELUXE LED'S, NO OTHER LED MANUFACTURERS ARE PERMITTED.
(9) PROVIDE SEPARATE SLEEVE IN CONCRETE POLES FOR LIGHTNING PROTECTION DOWN CONDUCTOR.
(10) PROVIDE MANUFACTURER'S POINT BY POINT PHOTOMETRIC ANALYSIS FOR SITE LIGHTING WITH SUBMITTALS. |
|
|
|
|
|
|
|
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
DETAILS |
|
PHOTOCONTROL TIME CLOCK SCHEMATIC - MXB
BASE DETAIL - CONCRETE LIGHT POLE
LIGHTING FIXTURE SCHEDULE
VCS - MAINLAND HIGH
APPROVED APPROVED
TYPE DESCRIPTION DESIGN SELECTION VOLTS CCT WATTAGE LUMENS LAMP
SUBSTITUTION SUBSTITUTION
LEOTEK LIGHTING #
ONE (1) ARM MOUNTED LED SHOEBOX LUMINAIRE, TYPE V CURRENT LIGHTING #
DISTRIBUTION, DARK BRONZE COLOR, MOUNT 20'-0" AFG ASL1 160L-115 4K7 5QW UNV MAF SP DBT
SLB POLE: LITHONIA/ACUITY# 277 4000K 110 15,632 LED
TO DIRECT BURIED CONCRETE POLE WITH 155 MPH WIND SEMINOLE POLES # 28FT
PRE-CAST SPECIALTIES #
LOADING BASED ON EMBEDMENT IN SAND (NOTE 9 & 10)
(NOTE 9 & 10)
LEOTEK LIGHTING #
ONE (1) ARM MOUNTED LED SHOEBOX LUMINAIRE, TYPE III CURRENT LIGHTING #
DISTRIBUTION, DARK BRONZE COLOR, MOUNT 20'-0" AFG ASL1 160L-115 4K7 3 UNV MAF SP DBT
SLC POLE: LITHONIA/ACUITY# 277 4000K 110 15,413 LED
TO DIRECT BURIED CONCRETE POLE WITH 155 MPH WIND SEMINOLE POLES # 28FT
PRE-CAST SPECIALTIES #
LOADING BASED ON EMBEDMENT IN SAND (NOTE 9 & 10)
(NOTE 9 & 10)
LIGHTING FIXTURE SCHEDULE GENERAL NOTES:
(1) CONTRACTOR SHALL CAREFULLY COORDINATE THE LIGHTING FIXTURE TRIM TYPES WITH THE TYPE OF CEILING WHERE THE LIGHTING FIXTURES ARE TO BE INSTALLED. MODIFY FIXTURE CATALOG NUMBER AS REQUIRED TO COORDINATE FIXTURE WITH CEILING.
(2) ALL FIXTURES TO HAVE IN-LINE FUSE AND FUSE HOLDER.
(3) PROVIDE MANUFACTURER'S POINT BY POINT PHOTOMETRIC ANALYSIS FOR SITE LIGHTING WITH SUBMITTALS 10 DAYS PRIOR TO BID FOR APPROVAL BY DESIGN ENGINEER.. PROVDIE EMBEDMENT DETAILS FOR SAND
(4) CONTRACTOR, AT HIS OPTION, MAY USE A U.L. LISTED FLEXIBLE WIRING SYSTEM FOR LIGHTING FIXTURE BRANCH CIRCUITRY ABOVE ACCESSIBLE LAY-IN CEILINGS. ALL HOMERUNS, CONNECTIONS TO LIGHT SWITCHES, AND BRANCH CIRCUITRY FOR ALL OTHER
CEILING CONDITIONS SHALL BE IN A CONVENTIONAL RACEWAY SYSTEM PER SPECIFICATIONS.
(5) WHEN FIXTURE MODEL NUMBER DIFFERS FROM FIXTURE DESCRIPTION, CONTRACTOR IS TO SUBMIT RFI REQUESTING CLARIFICATION PRIOR TO BID, PRIOR TO SHOP DRAWING SUBMITTAL AND PRIOR TO ORDERING OF FIXTURE. WHERE CONTRACTOR DOES NOT
REQUEST CLARIFICATION PRIOR TO BID, CONTRACTOR SHALL PROVIDE THE MOST EXPENSIVE OPTION BETWEEN A FIXTURE THAT MATCHES THE DESCRIPTION AND A FIXTURE THAT MATCHES THE MODEL NUMBER. AFTER BID, CONTRACTOR SHALL SUBMIT RFI
REQUESTING CLARIFICATION SO PROPER FIXTURE GETS SUBMITTED, PROVIDED AND INSTALLED.
(6) MOUNT LINEAR FIXTURES TOGETHER, END TO END, WHERE SHOWN IN CONTINUOUS ROWS. ARCH/ENGR OF RECORD
(7) MANUFACTURER SHALL PROVIDE A WARRENTY AGAINST LOSS OF PERFORMANCE AND DEFECTS IN MATERIALS AND WORKMANSHIP FOR THE LUNINAIRS FOR A PERIOD OF 10 YEARS AFTER ACCEPTANCE OF THE LUMINAIRES. WARRANTY SHALL COVER ALL
COMPONENTS COMPRISING THE LUMINAIRE.
DESIGNED BY DRAWN BY
(8) AT TIME OF PURCHASE, ALL APPROVED MANUFACTURERS MUST BE USING CREE, PHILLIPS, SAMSUNG, BRIDGELUXE LED'S, NO OTHER LED MANUFACTURERS ARE PERMITTED.
(9) PROVIDE SEPARATE SLEEVE IN CONCRETE POLES FOR LIGHTNING PROTECTION DOWN CONDUCTOR. ISSUE DATE AE PROJECT NUMBER
(10) PROVIDE MANUFACTURER'S POINT BY POINT PHOTOMETRIC ANALYSIS FOR SITE LIGHTING WITH SUBMITTALS.
PHOTOCONTROL CONTACTOR MXA SCHEMATIC - MXA
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
DETAILS
E503
| POLE |
DECRIPTION |
#LUMINAIRES/POLE |
LUMINAIRE MODEL |
POLE HEIGHT |
FIXTURE GROUP
MOUNTING
HEIGHT |
CONTACTOR |
FLA |
CONTACTOR SIZE |
CIRCUIT SIZE |
ZONE |
PANEL /CKT |
| A1 |
SOFTBALL |
1 |
MUSCO TLC-LED-1200 |
70' |
70' |
C1 |
5.17 |
30 |
15 |
A |
HBBF-2:4:6 |
|
|
2 |
MUSCO TLC-LED-550 |
|
16' |
|
|
|
|
|
|
|
|
1 |
MUSCO TLC-BT-575 |
|
|
|
|
|
|
|
|
| A2 |
SOFTBALL |
1 |
MUSCO TLC-LED-1200 |
80' |
70' |
C2 |
5.17 |
30 |
15 |
A |
HBBF-8:10:12 |
|
|
2 |
MUSCO TLC-LED-550 |
|
16' |
|
|
|
|
|
|
|
|
1 |
MUSCO TLC-BT-575 |
|
|
|
|
|
|
|
|
| B1 |
SOFTBALL |
5 |
MUSCO TLC-LED-1500 |
80' |
80' |
C3 |
12.47 |
30 |
20 |
A |
HBBF-14:16:18 |
|
|
1 |
MUSCO TLC-LED-550 |
|
80' |
|
|
|
|
|
|
|
|
1 |
MUSCO TLC-BT-575 |
|
16' |
|
|
|
|
|
|
| B2 |
SOFTBALL |
5 |
MUSCO TLC-LED-1500 |
80' |
80' |
C4 |
12.47 |
30 |
20 |
A |
HBBF-20:22:24 |
|
|
|
MUSCO TLC-LED-550 |
|
80' |
|
|
|
|
|
|
|
|
1 |
MUSCO TLC-BT-575 |
|
16' |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TOTAL |
|
21 |
|
|
|
|
35.28 |
|
|
|
|
| LUMINAIRE DESCRIPTION |
|
|
|
|
|
|
|
|
| TYPE |
SOURCE |
WATTAGE |
MAX AMPS |
LUMENS |
L90 |
L80 |
L70 |
QUANTITY |
| TLC-LED-1500 |
LED 5700K - 75 CRI |
1410 WATTS |
3.6 |
181,000 |
>120,000 |
>120,000 |
>120,000 |
10 |
| TLC-LED-1200 |
LED 5700K - 75 CRI |
1170 WATTS |
3.0 |
150,000 |
>120,000 |
>120,000 |
>120,000 |
2 |
| TLC-LED-900 |
LED 5700K - 75 CRI |
880 WATTS |
2.3 |
104,000 |
>120,000 |
>120,000 |
>120,000 |
|
| TLC-LED-550 |
LED 5700K - 75 CRI |
540 WATTS |
1.4 |
67,000 |
>120,000 |
>120,000 |
>120,000 |
5 |
| TLC-BT-575 LED |
LED 5700K - 75 CRI |
575 WATTS |
1.5 |
52,000 |
>120,000 |
>120,000 |
>120,000 |
4 |
| CALCULATON GRID SUMMARY |
|
|
|
|
|
|
|
| GRID NAME |
CALCULATION METRIC |
AVERAGE |
MINIMUM |
MAXIMUM |
MAX/MIN |
ZONES OPERATING |
# FIXTURES
OPERATING |
| INFIELD |
HORIZONTAL ILLUMINANCE |
50.29 |
34.91 |
64.33 |
1.84 |
A |
21 |
| OUTFIELD |
HORIZONTAL ILLUMINANCE |
31.43 |
18.42 |
42.88 |
2.33 |
A |
21 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
DETAILS |
|
SOFTBALL FIELD POLE /FIXTURE SCHEDULE
FIXTURE GROUP
MOUNTING
POLE DECRIPTION #LUMINAIRES/POLE LUMINAIRE MODEL POLE HEIGHT HEIGHT CONTACTOR FLA CONTACTOR SIZE CIRCUIT SIZE ZONE PANEL /CKT
A1 SOFTBALL 1 MUSCO TLC-LED-1200 70'
2 MUSCO TLC-LED-550 70' 16' C1 5.17 30 15 A HBBF-2:4:6
1 MUSCO TLC-BT-575
A2 SOFTBALL 1 MUSCO TLC-LED-1200 70'
2 MUSCO TLC-LED-550 80' 16' C2 5.17 30 15 A HBBF-8:10:12
1 MUSCO TLC-BT-575
B1 SOFTBALL 5 MUSCO TLC-LED-1500 80'
1 MUSCO TLC-LED-550 80' 80' C3 12.47 30 20 A HBBF-14:16:18
1 MUSCO TLC-BT-575 16'
B2 SOFTBALL 5 MUSCO TLC-LED-1500 80'
MUSCO TLC-LED-550 80' 80' C4 12.47 30 20 A HBBF-20:22:24
1 MUSCO TLC-BT-575 16'
TOTAL 21 35.28
LUMINAIRE DESCRIPTION
TYPE SOURCE WATTAGE MAX AMPS LUMENS L90 L80 L70 QUANTITY
TLC-LED-1500 LED 5700K - 75 CRI 1410 WATTS 3.6 181,000 >120,000 >120,000 >120,000 10
TLC-LED-1200 LED 5700K - 75 CRI 1170 WATTS 3.0 150,000 >120,000 >120,000 >120,000 2
TLC-LED-900 LED 5700K - 75 CRI 880 WATTS 2.3 104,000 >120,000 >120,000 >120,000
TLC-LED-550 LED 5700K - 75 CRI 540 WATTS 1.4 67,000 >120,000 >120,000 >120,000 5
TLC-BT-575 LED LED 5700K - 75 CRI 575 WATTS 1.5 52,000 >120,000 >120,000 >120,000 4
CALCULATON GRID SUMMARY
# FIXTURES
GRID NAME CALCULATION METRIC AVERAGE MINIMUM MAXIMUM MAX/MIN ZONES OPERATING
OPERATING
INFIELD HORIZONTAL ILLUMINANCE 50.29 34.91 64.33 1.84 A 21
OUTFIELD HORIZONTAL ILLUMINANCE 31.43 18.42 42.88 2.33 A 21
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
DETAILS
E504
| FEEDER SCHEDULE: BASEBALL FIELD |
|
|
|
|
DATE: 2/17/2026 |
|
COPYRIGHT: ME, LLC 2009VERSION: A8d5R1 REV: 1-7-2021 |
|
|
|
|
|
|
| FEEDER FEEDING |
OCP
AMP
SIZE |
VOLTS |
FEEDER
AMPACITY |
FEEDER
VOLTAGE
DROP (%) |
WIRE/PHASE |
NEUTRAL
WIRE |
GROUND
WIRE |
EXTRA
NEUTRAL |
FEEDER
MATERIAL |
PARALLEL
RUNS |
CONDUIT
SIZE (IN) |
SHORT
CIRCUIT
AMPS AT
PANEL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| HBBF |
250 |
480 |
248 |
2% |
#350 KCMIL |
#350 KCMIL |
#2 |
|
COPPER |
1 |
4 |
10243 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| POLE A2 (BASEBALL CKT) |
30 |
480 |
40 |
1% |
#8 |
#8 |
#8 |
|
COPPER |
1 |
1 |
|
|
| POLE A3 |
30 |
480 |
40 |
2% |
#8 |
#8 |
#8 |
|
COPPER |
1 |
1 |
|
|
| POLE B2 (BASEBALL CKT) |
30 |
480 |
40 |
0% |
#8 |
#8 |
#8 |
|
COPPER |
1 |
1 |
|
|
| POLE B3 |
30 |
480 |
30 |
2% |
#6 |
#6 |
#6 |
|
COPPER |
1 |
1 |
|
|
| POLE C1 |
30 |
480 |
40 |
1% |
#8 |
#8 |
#8 |
|
COPPER |
1 |
1 |
|
|
| POLE C2 |
30 |
480 |
30 |
2% |
#6 |
#6 |
#6 |
|
COPPER |
1 |
1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LBBF |
175 |
208 |
175 |
0% |
#2/0 |
#2/0 |
#4 |
|
COPPER |
1 |
2.5 |
1946 |
|
| LBBF XFMR PRI |
70 |
480 |
85 |
0% |
#4 |
----- |
#8 |
|
COPPER |
1 |
1.5 |
8085 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DESIGNED BY
AWB |
DRAWN BY
MM/AWB |
| ISSUE DATE
02/20/2026 |
AE PROJECT NUMBER
2025-135 |
| SHEET TITLE
POWER RISER DIAGRAM
AND SCHEDULES |
|
FEEDER SCHEDULE: BASEBALL FIELD DATE: 2/17/2026 COPYRIGHT: ME, LLC 2009VERSION: A8d5R1 REV: 1-7-2021
SHORT
OCP FEEDER
FEEDER NEUTRAL GROUND EXTRA FEEDER PARALLEL CONDUIT CIRCUIT
FEEDER FEEDING AMP VOLTS VOLTAGE WIRE/PHASE
AMPACITY WIRE WIRE NEUTRAL MATERIAL RUNS SIZE (IN) AMPS AT
SIZE DROP (%)
PANEL
HBBF 250 480 248 2% #350 KCMIL #350 KCMIL #2 COPPER 1 4 10243
POLE A2 (BASEBALL CKT) 30 480 40 1% #8 #8 #8 COPPER 1 1
POLE A3 30 480 40 2% #8 #8 #8 COPPER 1 1
POLE B2 (BASEBALL CKT) 30 480 40 0% #8 #8 #8 COPPER 1 1
POLE B3 30 480 30 2% #6 #6 #6 COPPER 1 1
POLE C1 30 480 40 1% #8 #8 #8 COPPER 1 1
POLE C2 30 480 30 2% #6 #6 #6 COPPER 1 1
LBBF 175 208 175 0% #2/0 #2/0 #4 COPPER 1 2.5 1946
LBBF XFMR PRI 70 480 85 0% #4 ----- #8 COPPER 1 1.5 8085 "
GENERAL NOTES:
1) CONDUIT SIZE IS BASED ON 2020 N.E.C. FOR EMT, IMC, RMC, FLEXIBLE METAL, AND SCHED 40 PVC. IF ANY OTHER TYPE OF CONDUIT/TUBING IS USED, THE
CONTRACTOR SHALL RESIZE CONDUIT AND SIZE AS REQUIRED TO COMPLY WITH THE N.E.C..
2) USE CABLE REDUCERS AT TERMINATIONS AND/OR AT/IN JUNCTION BOX NEAR TERMINATIONS AS REQUIRED TO COORDINATE OVERSIZED PHASE OR
NEUTRAL CONDUCTORS WITH TERMINATION LUG SIZE OR PROVIDE TERMINATION/LUGS SIZED FOR FEEDERS.
3) CONTRACTOR IS TO MEGGER TEST ALL FEEDERS PER SPECIFICATIONS.
4) WHERE DISCONNECT SWITCH (DISC SW) IS INCLUDED IN THE NAME UNDER "FEEDER FEEDING", PROVIDE DISC SW TO MEET ALL ELECTRICAL
CHARACTERISTICS PER THIS SCHEDULE, INCLUDING SCCR RATING. PROVIDE FUSE IN FUSIBLE SWITCHES OR PROVIDE UPSTREAM CIRCUIT BREAKER,
WHERE NON-FUSED SWITCHES ARE USED, AS REQUIRED BY DISCONNECT SWITCH MANUFACTURER FOR SHORT CIRCUIT AMPS SHOWN.
ARCH/ENGR OF RECORD
DESIGNED BY DRAWN BY
ISSUE DATE AE PROJECT NUMBER
DRAWING NO.
SNOISIVER
YROTSIH
TNEMUCOD
NOITPIRCSED
ETAD
.ON
130 Candace Drive
Maitland, FL 32751
ENG. BUS. No. EB-0005096 PHONE (407) 740-5020
CERT. OF AUTH. No. 5096 FAX (407) 740-0365
Engineer
Adrian Baus
AWB MM/AWB
02/20/2026 2025-135
SHEET TITLE
HGIH
DNALNIAM
GNITHGIL
DLEIF
LLABESAB
5728462
.ON
tcejorP
SCV
,DVLB
YAWDEEPS
LANOITANRETNI
W
5521
41123
LF
,HCAEB
ANOTYAD
POWER RISER DIAGRAM
AND SCHEDULES
E601