J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| Posted Date: | Feb 21, 2025 |
| Due Date: | Feb 26, 2025 |
| Solicitation No: | 36C26225Q0465 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Solicitation (Updated)
- Updated Published Date: Feb 21, 2025 12:12 pm MST
- Original Published Date: Feb 12, 2025 02:18 pm MST
- Updated Date Offers Due: Feb 26, 2025 01:00 pm MST
- Original Date Offers Due: Feb 21, 2025 01:00 pm MST
- Inactive Policy: Manual
- Updated Inactive Date: Mar 28, 2025
- Original Inactive Date: Apr 22, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: J059 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS
-
NAICS Code:
- 811210 - Electronic and Precision Equipment Repair and Maintenance
-
Place of Performance:
Questions and answers to solicitation 36C26225Q0465
UPS Unit Details:
Make & Model Powerware #9355-30
Serial Number(s) #BG436KXX06
Battery Details:
Make & Model CSB Battery Co. Ltd. 108 units #HR 123W (internal) 144 units #HR 12120W(external)
Quantity required for replacement #252 units
Service Requirements Clarifications:
Does the semi-annual service include load testing or just visual inspections? Yes it is included from the list
Inspect all Printed Circuit Board (PCB) boards for cracks or damage.
Check and record input/output voltage and amperage readings.
Calibrate metering.
Perform safety shutdown function tests.
Test and record line/load voltages and amperages.
Re-torque all electrical connections.
Exercise all circuit breakers.
Inspect all Alternating Current (AC) & Direct Current (DC) electronics for damage.
Check and record each battery voltage, impedance, and general condition.
Provide VA COR with a detailed maintenance report.
Are there specific compliance or reporting requirements beyond standard preventive maintenance? per NFPA 111
Any historical maintenance logs or known issues that should be considered? yes, shall be need all
4) Battery Specifications Could you provide the model number and/or specifications of the 252 batteries that require replacement? Number of Internal Battery: 108 BATTERIES
5)MANUFACTURER: CSB BATTERY CO, LTD
MODEL #: HR 1234W
CELLS PER UNIT: 6
VOLTAGE: 12 VOLTS
CAPACITY: 34W @ 15 minute-rate to 1.67V per cell @ 25 degree centigrade
MAX DISCHARGE CURRENT: 130A
WEIGHT: APPROX 2.5 kg (5.51 lbs)
TERMINAL: F2-FAST ON TAB 250
Number of External Battery: 144 BATTERIES
MANUFACTURER: CSB BATTERY CO, LTD
MODEL #: HR 12120W
CELLS PER UNIT: 6
VOLTAGE PER UNIT: 12VOLTS
CAPACITY: 120W @ 15 MIN RATE TO 1.67V/CELL @ 25 DEGREE CENTIGRADE
MAX DISCHARGE CURRENT: 400A
6)The price/ cost schedule does not have a section to quote the replacement of the batteries, just the UPS PMs. Will the VA create an amendment to input a CLIN for the battery replacements? All is included in the quotation.
7)Battery Replacement Schedule The solicitation specifies a full battery replacement in the Base Year. Could you confirm whether another full replacement is anticipated in Option Year 4 (OY4), which aligns with standard battery lifecycle expectations? 5 years is life cycle and shall be done on base year.
8)Emergency Service and Repairs Should emergency service visits and repairs be included in the preventive maintenance pricing, or should they be quoted and billed separately on an as-needed basis? This is only for Preventive maintenance and emergency will be quoted as needed..
- 335 E. German Rd SUITE 301
- Gilbert , AZ 85297
- USA
- Jessica Brooks
- JESSICA.BROOKS3@VA.GOV
- Feb 21, 2025 12:12 pm MSTSolicitation (Updated)
- Feb 19, 2025 09:02 am MST Solicitation (Updated)
- Feb 12, 2025 02:18 pm MST Solicitation (Original)
Related Document
| Feb 7, 2025 | [Presolicitation (Original)] J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply |
| Feb 10, 2025 | [Presolicitation (Updated)] J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply |
| Feb 12, 2025 | [Solicitation (Original)] J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply |
| Feb 19, 2025 | [Solicitation (Updated)] J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply |
| Oct 28, 2025 | [Award Notice (Original)] J059--PM&R SVC for 30 Kilo-Volt Ampere Uninterrupted Power Supply -W/WD |
See Also
Follow R80D Skyraider Maintenance, Training, and Spares Active Contract Opportunity Notice ID FA805126SSRADAS
DEPT OF DEFENSE
Due by 9/17/2026
Follow J--N1 Brake Ring Active Contract Opportunity Notice ID 140R3026Q0137 Related Notice Department/Ind.
INTERIOR, DEPARTMENT OF THE
Due by 10/02/2026
Follow Atmosphere Furnaces Units - Bldg 108 Active Contract Opportunity Notice ID W911KF26QA054
DEPT OF DEFENSE
Due by 9/25/2026
Follow J065--Emergency Repair to Philips Radiology Digital Radiography Active Contract Opportunity Notice ID
VETERANS AFFAIRS, DEPARTMENT OF