J059--Newington Replacement Breakers
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Virginia |
| Type of Government: | Federal |
| FSC Category: |
|
| Set Aside: | Veteran-Owned Small Business Set-Aside (specific to Department of Veterans Affairs) |
| Posted Date: | Aug 18, 2025 |
| Due Date: | Aug 25, 2025 |
| Solicitation No: | 36C24125Q0602 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Combined Synopsis/Solicitation (Updated)
- Updated Published Date: Aug 18, 2025 11:33 am EDT
- Original Published Date: Jul 02, 2025 11:19 am EDT
- Updated Date Offers Due: Aug 25, 2025 05:00 pm EDT
- Original Date Offers Due: Jul 15, 2025 05:00 pm EDT
- Inactive Policy: Manual
- Updated Inactive Date: Sep 24, 2025
- Original Inactive Date: Sep 13, 2025
-
Initiative:
- None
- Original Set Aside: Veteran-Owned Small Business Set-Aside (specific to Department of Veterans Affairs)
- Product Service Code: J059 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRICAL AND ELECTRONIC EQUIPMENT COMPONENTS
-
NAICS Code:
- 811210 - Electronic and Precision Equipment Repair and Maintenance
-
Place of Performance:
VA Medical Center Newington Newington , 06111
Can you please advise part # of breaker needed / pictures of existing breaker?
There are 2 breakers noted in the solicitation. The first of which cannot be racked out for information due to the support bracket being damaged. This is the breaker that needs to be replaced. Here is the information I have available to me:
MFR: EATON
Catalog # MDN4083XEA0552N
Frame Type: K600-AR-600NM
Frame Size: 800
Voltage Rating: 480
Trip Unit: DIGITRIP 520
Trip Rating: 250
Can you please send us the catalog number for this breaker and information on the trip unit? If you have any pictures, that would help.
The second breaker failed a trip test and will need the trip unit replaced. Here is the information I have available from the second breaker.
MFR: EATON
Catalog # MDN4083XEA0552N
Frame Type: K600-AR-600NM
Frame Size: 800
Voltage Rating: 480
Trip Unit: DIGITRIP 520
Trip Rating: NA (This will need to be dialed in as best you can)
Please note as stated in the SOW, this breaker will need a temporary unit for use until the trip unit is rebuilt, and the breaker can be racked back in. This unit supports the hospital s CT scanners and downtime is not acceptable.
Please also note that each breaker will require a testing report via secondary injection testing to verify functionality.
- ONE VA CENTER
- TOGUS , ME 04330
- USA
- Shawn Lawrence
- Shawn.Lawrence@va.gov
- Phone Number 203-932-5711
- Aug 18, 2025 11:33 am EDTCombined Synopsis/Solicitation (Updated)
- Jul 02, 2025 11:19 am EDT Combined Synopsis/Solicitation (Original)
Related Document
| Jul 2, 2025 | [Combined Synopsis/Solicitation (Original)] 5925--Newington Replacement Breakers |
See Also
Virginia Lottery iLottery System, Services, and Su... Status: Open RFP 123127-2 Virginia State
State Government of Virginia
Due by 9/23/2026
Follow J059--Automatic Transfer Switch and Isolation Panel Service | Leavenworth VAMC | Active
VETERANS AFFAIRS, DEPARTMENT OF
Due by 10/02/2026
Follow Getinge Preventive Maintenance Active Contract Opportunity Notice ID HT9410 Related Notice Department/Ind.
DEPT OF DEFENSE
Due by 9/16/2026
Biomedical Preventative Maintenance and Repair Ser... Status: Open IFB 127602-1 Piedmont Geriatric Hospital
State Government of Virginia
Due by 9/21/2026