J061--FY25: Lake Nona Medium Voltage Repair
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Jun 13, 2025 |
| Due Date: | Jun 16, 2025 |
| Solicitation No: | 36C24825Q0885 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
Follow
Active
Contract Opportunity
Notice ID
36C24825Q0885
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
248-NETWORK CONTRACT OFFICE 8 (36C248)
General Information
Classification
Description
Contact Information
History
- Contract Opportunity Type: Special Notice (Original)
- Original Published Date: Jun 13, 2025 03:18 pm EDT
- Original Response Date: Jun 16, 2025 11:00 am EDT
- Inactive Policy: Manual
- Original Inactive Date: Aug 15, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
-
NAICS Code:
- 238210 - Electrical Contractors and Other Wiring Installation Contractors
-
Place of Performance:
The Department of Veteran Affairs, Network Contracting Office 08 invites interested Contractors to attend a site visit for the purpose of assessing the issues identified in the government-generated Trouble Call report. This site visit will assist prospective offers in evaluating the work environment and technical requirements in preparation for submitting a quote under the upcoming Request for Quote (RFQ).
Instructions:
Interested parties must pre-register attendees (no more than two) by providing names to Robert.edwards2@va.gov and rohan.mckenzie@va.gov no later than June 16, 2025, 11:00 AM. Please arrive on time and bring proper identification to gain access to the facility.
Site Visit Details:
Date: June 17, 2025
Time: 10:00 AM (local time)
Location: Orlando VA Medical Center at Lake Nona, 13800 Veterans Way, Orlando, FL 32827
Meeting Point: Inside the lobby near the piano
Purpose: Visual inspection and discussion of the issue described in Trouble Call Report
Follow-up: Contractor questions will be address on-site and incorporated into the forthcoming RFQ as appropriate.
Background:
Emergency (generator) power circuit(s) to the Lake Nona clinic are faulted and/or unreliable.
The medium voltage circuit DAG-3 is the emergency (generator) circuit powering the Clinic substation SS-CG2; and is the alternate power source for Clinic substation SS-CG1. It was Hi-Pot tested and the report indicated a catastrophic failure on B-phase, requiring both substations to be placed on the alternate circuit (DAG-15) with no redundancy. A visual inspection of manholes EA1-1 and EA1-2 in the duct bank series noted splices in them that show signs corrosion and degradation. Troubleshooting, testing was performed on the circuit and damage to the B-phase conductor insulation is suspected to be localized the within the ductwork itself requiring emergent replacement.
The medium voltage circuit DAG-15 is the emergency (generator) circuit powering the Clinic substation SS-CG1 and is the alternate power source for Clinic substation SS-CG2. It was Hi-Pot tested and the report indicated signs of leakage, likely from several splices/phases in the duct bank series manholes. A visual assessment was performed in conjunction with the Hi-Pot test and noted signs of swelling on several splices. Circuit DAG15 is the sole operable emergency (generator) circuit to the Clinic substations SS-CG1/2 (in its current switched state) and in urgent need of replacement and/or repair.
The Normal power circuit to the Lake Nona Domiciliary is unreliable. The medium voltage circuit DAN-2 is the sole normal power circuit powering the Domiciliary substation SS-DG1. It was quickly identified to have sustained a catastrophic splice failure on only C-phase on 12Nov24 in manhole NA2-5. Only C- phase splice was repaired, and the circuit was put back in service in >24hrs. During the visual assessment splices were noted in manholes NA2-5, NA2-6, NA2-7, and NA2-8 with various signs of corrosion and swelling indicative of impending failure. Circuit DAN-2 requires urgent replacement.
DBN-7 Hospital (Normal Power) circuit - A visual assessment confirmed smoke and electrical burning signs from manhole NB2-3 near the golf cart yard of the warehouse. Suspected leaking splice damage. IMG_1005 1.3gp.
Attachments:
ATTACHMENT A - Trouble Call Report of the Hi-Pot Cable test DAG-3
ATTACHMENT B - Trouble Call Report of the Hi-Pot Cable test DAG-15
Note: This notice is for informational and planning purposes only. It does not constitute a solicitation or guarantee of future contract award.
Instructions:
Interested parties must pre-register attendees (no more than two) by providing names to Robert.edwards2@va.gov and rohan.mckenzie@va.gov no later than June 16, 2025, 11:00 AM. Please arrive on time and bring proper identification to gain access to the facility.
Site Visit Details:
Date: June 17, 2025
Time: 10:00 AM (local time)
Location: Orlando VA Medical Center at Lake Nona, 13800 Veterans Way, Orlando, FL 32827
Meeting Point: Inside the lobby near the piano
Purpose: Visual inspection and discussion of the issue described in Trouble Call Report
Follow-up: Contractor questions will be address on-site and incorporated into the forthcoming RFQ as appropriate.
Background:
Emergency (generator) power circuit(s) to the Lake Nona clinic are faulted and/or unreliable.
The medium voltage circuit DAG-3 is the emergency (generator) circuit powering the Clinic substation SS-CG2; and is the alternate power source for Clinic substation SS-CG1. It was Hi-Pot tested and the report indicated a catastrophic failure on B-phase, requiring both substations to be placed on the alternate circuit (DAG-15) with no redundancy. A visual inspection of manholes EA1-1 and EA1-2 in the duct bank series noted splices in them that show signs corrosion and degradation. Troubleshooting, testing was performed on the circuit and damage to the B-phase conductor insulation is suspected to be localized the within the ductwork itself requiring emergent replacement.
The medium voltage circuit DAG-15 is the emergency (generator) circuit powering the Clinic substation SS-CG1 and is the alternate power source for Clinic substation SS-CG2. It was Hi-Pot tested and the report indicated signs of leakage, likely from several splices/phases in the duct bank series manholes. A visual assessment was performed in conjunction with the Hi-Pot test and noted signs of swelling on several splices. Circuit DAG15 is the sole operable emergency (generator) circuit to the Clinic substations SS-CG1/2 (in its current switched state) and in urgent need of replacement and/or repair.
The Normal power circuit to the Lake Nona Domiciliary is unreliable. The medium voltage circuit DAN-2 is the sole normal power circuit powering the Domiciliary substation SS-DG1. It was quickly identified to have sustained a catastrophic splice failure on only C-phase on 12Nov24 in manhole NA2-5. Only C- phase splice was repaired, and the circuit was put back in service in >24hrs. During the visual assessment splices were noted in manholes NA2-5, NA2-6, NA2-7, and NA2-8 with various signs of corrosion and swelling indicative of impending failure. Circuit DAN-2 requires urgent replacement.
DBN-7 Hospital (Normal Power) circuit - A visual assessment confirmed smoke and electrical burning signs from manhole NB2-3 near the golf cart yard of the warehouse. Suspected leaking splice damage. IMG_1005 1.3gp.
Attachments:
ATTACHMENT A - Trouble Call Report of the Hi-Pot Cable test DAG-3
ATTACHMENT B - Trouble Call Report of the Hi-Pot Cable test DAG-15
Note: This notice is for informational and planning purposes only. It does not constitute a solicitation or guarantee of future contract award.
Attachments/Links
Contracting Office Address
- 8875 HIDDEN RIVER PARKWAY
- TAMPA , FL 33637
- USA
Primary Point of Contact
- Rohan McKenzie
- Rohan.Mckenzie@va.gov
- Phone Number 407-631-8720
Secondary Point of Contact
- Jun 13, 2025 03:18 pm EDTSpecial Notice (Original)
Get Government Bids Like This by Email
Receive daily bid alerts that match your keywords, business categories, and target regions.
See Also
Follow BORESIGHT KIT CALIBRATION and REPAIR Active Contract Opportunity Notice ID N6833526R1106 Related
DEPT OF DEFENSE
Due by 9/24/2026
Follow annual maintenance and service agreement for autoclave Active Contract Opportunity Notice ID
NATIONAL AERONAUTICS AND SPACE ADMINISTRATION
Follow J--Amendment #3 to 1333MF26Q0108 Active Contract Opportunity Notice ID 1333MF26Q0108 Related Notice
COMMERCE, DEPARTMENT OF
Due by 9/15/2026
Follow R80D Skyraider Maintenance, Training, and Spares Active Contract Opportunity Notice ID FA805126SSRADAS
DEPT OF DEFENSE
Due by 9/17/2026
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.