J061--Electrical Inspection, Testing & Maintenance Follow on Base | Start: 11/1/25
| Agency: | VETERANS AFFAIRS, DEPARTMENT OF |
|---|---|
| State: | Federal |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | Oct 30, 2025 |
| Due Date: | Nov 10, 2025 |
| Solicitation No: | 36C25026Q0069 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Solicitation (Updated)
- Updated Published Date: Oct 30, 2025 05:12 pm EDT
- Original Published Date: Oct 27, 2025 01:14 pm EDT
- Updated Date Offers Due: Nov 10, 2025 12:00 pm EST
- Original Date Offers Due: Nov 04, 2025 12:00 pm EST
- Inactive Policy: Manual
- Updated Inactive Date: Dec 10, 2025
- Original Inactive Date: Feb 11, 2026
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: J061 - MAINT/REPAIR/REBUILD OF EQUIPMENT- ELECTRIC WIRE AND POWER DISTRIBUTION EQUIPMENT
-
NAICS Code:
- 561210 - Facilities Support Services
-
Place of Performance:
The Item 0001 apparently refers to the set of all other items listed below it. Should the price fields for Item 0001 be left blank, or should they show the total sum of the other items? It can show the total amount of the job
No test specifications were provided. Can you provide test specifications or the latest test report as an example? Test specifications will be submitted with the revision. See 3.C. Work items, definitions, and references shall comply with the latest edition of the NETA Maintenance Testing Specifications (MTS) and with the VHA Directive, Electrical Power Distribution System. Below is a list of electrical equipment that shall be maintained and tested:
Regarding Item 0003: Can MV Liquid Filled Transformers testing be limited to oil sampling, and inspection? NO Per 3.C.
If the answer to the previous question is no, should we perform tests for Polarization Index, Excitation Current, Turns Ratio, Insulation and Winding Resistance on the MV Transformers?
Regarding Item 0004: Are the (24) dry-type transformers listed low-voltage transformers? Information provided in Section C of the Statement of Work
Is it really necessary to test all (550) circuit breakers by primary injection, or can they be tested by secondary injection? Primary Injection is required for all Frame 250Amp and higher
Regarding Item 0009: Should the cables be tested using the VLF method? Megger Testing
Regarding Item 0010: Is it necessary to perform insulation tests on the panels, or can they simply be visually inspected? See 3.C.
Regarding Item 0011: Please explain in more detail what these (300) Phenolic Labels would be. Are they name tags or another type? Will the VA provide the files for printing? Please provide details and dimensions of the labels. Electrical catalog contains Phenolic Labels
Does Item 0013 require scanning only the equipment listed in the other items, or is there a separate inventory/list of equipment that needs to be scanned? See Appendix B (IR Scan Column)
Please explain what should be priced in the Item: Documentation (0014). See 3.H., 3.I., 3.F., 3.M., 3.N.
Could you please provide the previous Arc Flash analysis report? Â Information included in the Electrical Equipment Catalog Appendix B 2025.
We understand that a new and revised scope of work statement is to be issued through an amendment. Please provide a bid due date extension of at least 5 working days after this amendment is issued to allow time for critical document distribution and responsible bid preparation. An extension of 5 calendar days will be added to the current response due date.
- 2215 FULLER ROAD
- ANN ARBOR , MI 48105
- USA
- Cierra S Joshua
- Cierra.Joshua@va.gov
- Oct 30, 2025 05:12 pm EDTSolicitation (Updated)
- Oct 27, 2025 01:14 pm EDT Solicitation (Original)
Related Document
| Oct 27, 2025 | [Solicitation (Original)] J061--Electrical Inspection, Testing & Maintenance Follow on Base | Start: 11/1/25 |
| Oct 27, 2025 | [Presolicitation (Original)] J061--Electrical Inspection, Testing & Maintenance Follow on Base | Start: 11/1/25 |
| Dec 11, 2025 | [Award Notice (Original)] J061--Electrical Inspection, Testing & Maintenance Services |
See Also
Follow BORESIGHT KIT CALIBRATION and REPAIR Active Contract Opportunity Notice ID N6833526R1106 Related
DEPT OF DEFENSE
Due by 9/24/2026
Follow annual maintenance and service agreement for autoclave Active Contract Opportunity Notice ID
NATIONAL AERONAUTICS AND SPACE ADMINISTRATION
Follow J--Amendment #3 to 1333MF26Q0108 Active Contract Opportunity Notice ID 1333MF26Q0108 Related Notice
COMMERCE, DEPARTMENT OF
Due by 9/15/2026
Follow R80D Skyraider Maintenance, Training, and Spares Active Contract Opportunity Notice ID FA805126SSRADAS
DEPT OF DEFENSE
Due by 9/17/2026