GENERATOR REPLACEMENT
SHREVEPORT JAIL
CITY OF SHREVEPORT
SHREVEPORT, LOUISIANA
SHEET INDEX
ED1.1
ED1.2
EP1.1
EP7.1
EP8.1
ELECTRICAL
ELECTRICAL DEMOLITION FLOOR PLAN - WEST
ELECTRICAL DEMOLITION FLOOR PLAN - EAST
ELECTRICAL FLOOR PLAN - WEST
ELECTRICAL DETAILS, NOTES, & SYMBOLS
ELECTRICAL DETAILS, RISER DIAGRAM, & PANEL SCHEDULES
EMA Engineering & Consulting, Inc.
Tyler | Austin | Houston | El Paso
DFW | San Antonio | Shreveport
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818
www.EMAengineer.com
REVIEW ONLY
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer: James M. Tate III
License State: TX License No.: 102864237
10-24-2025 4/1/2024 10:52:47 AM
Date:
ISSUE DATE
OCT. 24, 2025
ISSUE STATUS
DATE
SHREVEPORT
LOCATION MAP
NORTH
KEY PLAN
EMA JOB #: 5-001-1898-006
DRAWN BY:
MSA
CHECKED:
CMC
COVER PAGE
SHEET NUMBER
COVER SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
J ED13
H2
MECH. / ELEC.
L2
ED4 ED3
CONTROL
BOOKING DESK
OFFICE 1
ED5
OFFICE 2
ED5
RELEASE
OFFICE 3
ED5
OFFICE JAIL COMNDR
ED6
ED5
J ED9
EXISTING PANEL EHDP
EXISTING ATS ED2
EXISTING PANEL MHDP
MECH./ ELEC.
ED1
EXISTING EMERGENCY GENERATOR
1
ELECTRICAL DEMOLITION FLOOR PLAN - WEST
1/8"=1'-0"
CU-3
ED7
EL1
ET1 ED12
EH1 ED10
ED8
AHU-3
L1
T1
MECH./ ELEC.
H1
ELECTRICAL GENERAL NOTES
1. SEE SHEET EP7.1 FOR GENERAL NOTES APPLICABLE TO THE ENTIRE DRAWING SET.
ELECTRICAL DEMOLITION PLAN NOTES
EMA Engineering & Consulting, Inc.
Tyler | Austin | Houston | El Paso
DFW | San Antonio | Shreveport
Texas Firm Registration No. F-893
ED1
EXISTING GENERATOR TO BE REMOVED AND REPLACE. REMOVE EXISTING CONDUIT AND WIRING BACK TLoOuisiana Firm Registration No. EF-5818
SOURCE.
www.EMAengineer.com
ED2 EXISTING ATS TO BE REMOVED. REMOVE EXISTING CONDUIT AND WIRING BACK TO SOURCE.
ED3 EXISTING LIGHTING TO REMAIN IN PLACE AND OPERATIONAL.
REVIEW ONLY
ED4 EXISTING RECEPTACLES IN THIS ROOM TO BE REMOVED. EXISTING CONDUIT AND WIRING TO REMAIN ANDANPOPTRFOOVRALR, EPGEURLMAITTTOIRNYG,
BE REUSED TO PROVIDE POWER TO NEW RECEPTACLES.
OR CONSTRUCTION
ED5
EXISTING RECEPTACLES IN THIS ROOM TO BE REMOVED. REMOVE EXISTING CONDUIT AND WIRING BACK
TO SOURCE.
Engineer: James M. Tate III
10-24-2025 ED6
EXISTING LIGHT FIXTURES TO REMAIN IN ROOMS 242, 243, 244, AND 245. REMOVE EXISTING CONDUIT ANDLicense State: TX License No.: 108264327
WIRING BACK TO NEAREST JUNCTION POINT SERVING THESE ROOMS. EXISTING CIRCUIT TO REMAIN FOR
4/1/2024 10:52:47 AM
OTHER AREAS.
Date:
ED7
REMOVE EXISTING CIRCUIT SERVING CONDENSER UNIT FROM EXISTING PANEL 'H1'. REMOVE CONDUIT
AND WIRING BACK TO SOURCE. TURN BREAKER OFF AND MARK AS 'SPARE'.
ISSUE DATE
OCT. 24, 2025 ED8
REMOVE EXISTING CIRCUIT SERVING AIR HANDLER UNIT FROM EXISTING PANEL 'H1'. REMOVE CONDUIT
AND WIRING BACK TO SOURCE. TURN BREAKER OFF AND MARK AS 'SPARE'.
ISSUE STATUS
DATE
ED9
REMOVE EXISTING CIRCUIT SERVING FACP FROM EXISTING PANEL 'L2'. REMOVE CONDUIT AND WIRING
BACK TO SOURCE. TURN BREAKER OFF AND MARK AS 'SPARE'.
DISCONNECT AND REMOVE EXISTING UPSTREAM CONDUIT AND FEEDER BACK TO SOURCE FOR PANEL
ED10 'EH1'. TURN EXISTING UPSTREAM BREAKER OFF AND MARK AS 'SPARE'.
ED12
DISCONNECT AND REMOVE EXISTING UPSTREAM CONDUIT AND FEEDER BACK TO SOURCE FOR
TRANSFORMER 'ET1' THAT IS FEEDING PANEL 'EL1'. TURN EXISTING UPSTREAM BREAKER OFF AND
MARK
AS 'SPARE'.
ED13 EXISTING FULL BODY SCANNER TO REMAIN IN PLACE AND OPERATIONAL.
NO ELECTRICAL SCOPE IN THIS AREA
KEY PLAN
EMA JOB #: 5-001-1898-006
DRAWN BY:
MSA
CHECKED:
CMC
ELECTRICAL DEMOLITION
FLOOR PLAN - WEST
SHEET NUMBER
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
ED1.1
2148
2148
2148
KL1
2148
2148
2148
KT1
KH1 MECH. / ELEC.
EL2
ET2 ED15
EH2 ED11
ELECTRICAL GENERAL NOTES
1. SEE SHEET EP7.1 FOR GENERAL NOTES APPLICABLE TO THE ENTIRE DRAWING SET.
ELECTRICAL DEMOLITION PLAN NOTES
ED3 EXISTING LIGHTING TO REMAIN IN PLACE AND OPERATIONAL.
EMA Engineering & Consulting, Inc.
Tyler | Austin | Houston | El Paso
DFW | San Antonio | Shreveport
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818
www.EMAengineer.com
ED11
DISCONNECT AND REMOVE EXISTING UPSTREAM CONDUIT AND FEEDER
'EH2'. TURN EXISTING UPSTREAM BREAKER OFF AND MARK AS 'SPARE'.
BACK
TO SOURCE FOR
PANEL
ED14 EXISTING RECEPTACLES IN THIS ROOM TO REMAIN IN PLACE AND OPERATIONAL.
REVIEW ONLY
ED15
DISCONNECT AND REMOVE EXISTING UPSTREAM CONDUIT AND FEEDER BACK TO SOURCE FOR
TRANSFORMER 'ET2' THAT IS FEEDING PANEL 'EL2'. TURN EXISTING UPSTREAM BREAKER OFF AND MARK
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
AS 'SPARE'.
Engineer: James M. Tate III
License State: TX License No.: 102846327
10-24-2025 4/1/2024 10:52:47 AM
Date:
ISSUE DATE
OCT. 24, 2025
ISSUE STATUS
DATE
CONTROL 2
ED14
ED3
NO ELECTRICAL SCOPE IN THIS AREA
1
MEP FLOOR PLAN TEMPLATE
1/8"=1'-0"
KEY PLAN
EMA JOB #: 5-001-1898-006
DRAWN BY:
MSA
CHECKED:
CMC
ELECTRICAL DEMOLITION
FLOOR PLAN - EAST
SHEET NUMBER
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
ED1.2
H2
MECH. / ELEC.
L2
E13
J
E1
CONTROL
E1
BOOKING DESK
OFFICE 1
EL3-3
EL3-1
OFFICE 2
RELEASE
OFFICE 3
EL3-7
EL3-5
OFFICE JAIL COMNDR
EL3-2
EL3-4
EL3-9
E10 EL3-10
EL3-11
EL3-8
EL3-17
J E2
E6 E11 E12
EXISTING PANEL EHDP
NEW ATS-S E8
EXISTING PANEL MHDP E9
MECH./ ELEC.
E8
E14
NEW ATS-1 EL3-16
E7
NEW GENERATOR
EXISTING EMERGENCY GENERATOR
1
ELECTRICAL FLOOR PLAN - WEST
1/8"=1'-0"
EL3
TXEL3
CU-3
E3
E4
EL1
ET1
MECH./ ELEC.
EH1 E5
AHU-3
L1
T1
H1
ELECTRICAL GENERAL NOTES
1. SEE SHEET EP7.1 FOR GENERAL NOTES APPLICABLE TO THE ENTIRE DRAWING SET.
ELECTRICAL PLAN NOTES
EMA Engineering & Consulting, Inc.
Tyler | Austin | Houston | El Paso
DFW | San Antonio | Shreveport
Texas Firm Registration No. F-893
E1 PROVIDE POWER TO NEW RECEPTACLES IN THIS ROOM FROM EXISTING CIRCUIT IN PANEL 'EL' THAT Louisiana Firm Registration No. EF-5818
PREVIOUSLY SERVED REMOVED RECEPTACLES. EXTEND ELECTRICAL CONDUIT AND WIRE AS REQUIRED.pwww.EMAengineer.com
E2
PROVIDE BATTERY PACK FOR FIRE ALARM CONTROL PANEL AS REQUIRED FOR LIFE SAFETY. EXTEND
ELECTRICAL CONDUIT AND WIRE AS REQUIRED.
REVIEW ONLY PROVIDE POWER TO EXISTING CONDENSER FROM EXISTING PANEL 'EHDP'. PROVIDE 80A 3P BREAKER. USE
E3 #3 WIRE. REUSE EXISTING DISCONNECT AND FUSES. EXTEND ELECTRICAL CONDUIT AND WIRE AS
NOT FOR REGULATORY
REQUIRED.
APPROVAL, PERMITTING,
OR CONSTRUCTION
E4
PROVIDE POWER TO EXISTING AIR HANDLER UNIT FROM EXISTING PANEL 'EHDP'. PROVIDE 80A 3P
BREAKER. USE #3 WIRE. REUSE EXISTING DISCONNECT AND FUSES. EXTEND ELECTRICAL CONDUIT AND
Engineer: James M. Tate III
WIRE AS REQUIRED.
License State: TX License No.: 102846237
E5 PROVIDE NEW 60A 3P BREAKER IN EXISTING PANEL 'EH1' TO FEED PANEL 'EH2'. SEE RISER DIAGRAM FOR
MORE INFORMATION.
Date:
10-24-2025 4/1/2024 10:52:47 AM
E6
PROVIDE NEW 50A 3P BREAKER, AND 30A 3P BREAKER IN EXISTING PANEL 'EHDP' TO FEED EXISTING
TRANSFORMER 'ET1' AND TRANSFORMER 'ET2' RESPECTIVELY. SEE RISER DIAGRAM FOR MORE
INFORMATION.
E7 NEW GENERATOR TO BE INSTALLED IN THIS LOCATION. SEE SHEET EP7.1 FOR MORE INFORMATION.
E8 NEW ATS TO BE INSTALLED IN THIS LOCATION. SEE RISER DIAGRAM FOR MORE INFORMATION.
ISSUE DATE
OCT. 24, 2025
ISSUE STATUS
DATE
E9
PROVIDE NEW 100A 3P BREAKER FOR LIFE SAFETY PANEL'S ATS-S IN EXISTING PANEL 'MHDP'. ATS-S
FEEDS PANEL 'EH1'. UTILIZE AVAILABLE BREAKER SPACES.
E10
PROVIDE NEW LIGHTING CIRCUIT TO SERVE EXISTING LIGHT FIXTURES
A245 FROM PANEL 'EH1'. PROVIDE 20A 1P BREAKER WITH #12 WIRE.
IN
ROOMS
A216,
A243,
A244,
AND
E11
PROVIDE NEW 30A 3P BREAKER IN EXISTING PANEL 'EHDP' TO FEED NEW TRANSFORMER
AVAILABLE BREAKER SPACES. SEE RISER DIAGRAM FOR MORE INFORMATION.
'TXEL3'.
UTILIZE
E12 REUSE EXISTING 225A 3P BREAKER IN EXISTING PANEL 'MHDP' TO FEED NEW ATS-1. SEE RISER DIAGRAM
FOR MORE INFORMATION.
E13 EXISTING FULL BODY SCANNER TO REMAIN IN PLACE AND OPERATIONAL.
E14 WEATHERPROOF GFCI MAINTENANCE OUTLET INSTALLED 18" A.F.F.
NO ELECTRICAL SCOPE IN THIS AREA
KEY PLAN
EMA JOB #: 5-001-1898-006
DRAWN BY:
MSA
CHECKED:
CMC
ELECTRICAL FLOOR PLAN
- WEST
SHEET NUMBER
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.
EP1.1
GENERATOR INFO
SIZE (kW) - 200kW
VOLTAGE (V) - 480v
PHASE (ph) - 3
PRI. BREAKER (A) - 225A
SEC. BKR (A) - 100A
ATS INFO SUPPORT EQUIP CTKS
ATS-1 SIZE (Amps) - 300A 120V GFCI Maint Outlet - EL3-16
ATS-S SIZE (Amps) - 100A 120V Battery Charger - EL3-14
w/ Maintenance Bypass - N
120v Block Heater - EL3-12
Service Entrance Rated - N
PROVIDE 1"
CONDUITS FROM
SERVING PANEL TO
SUPPORT
EQUIPMENT LISTED
IN THIS DETAIL.
Provide Signage at the service entrance equipment indicating
"Emergency Power Source via Generator" per NEC 700.7
Slab around generator
to extend 3' beyond
generator dimensions
for access.
Slab - consult
structural engineer for
requirements.
Prime Mover
DIMENSIONS:
LENGTH -234in
WIDTH - 54in
HEIGHT - 111in
Genset
Main
Breaker(s)
48 Hr Diesel Belly Tank
SEE DRAWINGS FOR
GENERATOR ATS
LOCATION
COORDINATE EXACT
LOCATION OF REMOTE
ANNUNCIATOR PANEL
WITH OWNER
ATS
NEMA 3R
ALL FEEDERS
PER RISER
DIAGRAM
1" C. TO
GENSET
GENERATOR PAD TO BE 3' LARGER THAN
GENERATOR DIMENSIONS ALL THE WAY AROUND
FOR ACCESS AND MAINTENANCE.
TO PARENT PANEL OR TX
TO DOWNSTREAM
PANEL OR LOAD
1
GENERATOR INFORMATION
N.T.S.
BC2
277/480V, 3PH, 4W
Fed from MDP
A/C # B105
208V, 3PH
Circuit BAC-15
PANELBOARD LABEL (TYPICAL)
HVAC DISCONNECT SWITCH LABEL (TYPICAL)
NOTES:
1. ATTACH SECURELY WITH NON-CORRODING STAINLESS STEEL SCREWS, NON-CORRODING POP RIVETS
ARE ACCEPTABLE, ADHESIVE ATTACHMENT IS NOT ACCEPTABLE.
2. LABEL ALL PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, HVAC DISCONNECT SWITCHES, AND
MOTOR CONTROL CENTERS AS REQUIRED, REFERENCE SPECIFICATION SECTION 260553.
2
ELECTRICAL EQUIPMENT IDENTIFICATION
N.T.S.
WALL
ROOF
3" MIN.
12" MAX.
JOIST
ROOF
CEILING
ROUTE CONDUIT IN WALL UP AS
HIGH AS POSSIBLE. DO NOT RUN
CONDUIT EXPOSED ON WALL.
ROUTE CONDUIT IN EXPOSED AREAS
PERPENDICULAR OR PARALLEL TO WALLS.
ROUTE CONDUIT AS HIGH AS POSSIBLE
AND ROUTE CONDUIT RUNS ADJACENT TO
EACH OTHER. CONDUIT SHALL BE
ORDERLY AND NEAT.
3
EXPOSED CONDUIT ROUTING
N.T.S.
NEVER SUPPORT CONDUITS FROM BOTTOM CHORD OF JOIST.
USE WHERE ATTIC SPACE IS
GREATER THAN 3'-0"
ATTACH TO TOP CHORD OF
STRUCTURE AS REQUIRED
WITH BEAM CLAMPS
CHANNEL PIPE
STRAPS OR CLIPS
1/4" CONTINUOUS
THREADED ROD
CONDUIT(S) AS REQUIRED
GALVANIZED CHANNEL - 1 5/8" X 1 5/8"
X 12 GAUGE SPACED AS DIRECTED
FINISHED CEILING AS
SCHEDULED
4
CONDUIT SUPPORT
N.T.S.
2"
3M FIRE BARRIER FS-195+
WRAP/STRIP. (FOR FIRE
RATED WALL PENETRATIONS
OR EXTERIOR WALLS)
CONDUIT
3M FIRE BARRIER RC-1 RESTRICTING
COLLAR OR PPD. (FOR FIRE RATED
WALL PENETRATIONS OR EXTERIOR
WALLS)
WALL - SEE ARCHITECTURAL FOR
CONSTRUCTION TYPE
2"
GALVANIZED
STEEL SLEEVE
CONDUIT
FILL PER SPECIFICATION
AND NEC
5
WALL PENETRATION
N.T.S.
3"
2"
3"
MIN MIN MIN
GRADE PER NEC 300.5(D)(3)
WARNING TAPE
EARTH FILL
CONCRETE ENCASEMENT FOR
PRIMARY AND SECONDARY FEEDERS.
SAND BACKFILL/IMBEDMENT FOR ALL
OTHER FEEDERS
CONDUIT (QUANTITY VARIES)
12" MAX PER NEC 300.5(A) or
24" MIN. UTILITY REQUIREMENTS,
WHICHEVER IS GREATER.
3" MIN
SUPPORT CONDUIT
PER NEC 352.30B
4" MIN
PLASTIC SPACE SUPPORTS
SEE SPECIFICATION SECTION 26 20 00 PART 3 & 26 05 33 FOR MORE INFORMATION.
6
UNDERGROUND CONDUITS
N.T.S.
ELECTRICAL GENERAL NOTES
1. BRANCH CIRCUIT - PROVIDE A SEPARATE NEUTRAL CONDUCTOR FOR EACH CIRCUIT. MULTIPLE
CIRCUITS SHALL NOT SHARE A COMMON NEUTRAL. NEUTRAL CONDUCTORS SHALL BE SIZED AS LARGE
AS THE PHASE CONDUCTORS. NEUTRAL CONDUCTORS SHALL NOT BE OF A REDUCED SIZE.
2. CONDUIT - WHERE POSSIBLE, ALL CONDUIT AND/OR CABLING SHALL BE INSTALLED BETWEEN THE
BOTTOM AND TOP CHORD OF JOIST. WHERE NO CEILINGS ARE SCHEDULED, ALL CONDUIT SHALL BE UP
AGAINST BOTTOM OF THE TOP CHORD. DO NOT SUPPORT OR REST CONDUITS ON BOTTOM CHORD OF
THE JOISTS.
3. CONDUIT - ROUTE CONDUIT IN EXPOSED AREAS PERPENDICULAR OR PARALLEL TO WALLS. ROUTE
CONDUIT AS HIGH AS POSSIBLE AND ROUTE CONDUIT RUNS ADJACENT TO EACH OTHER. CONDUITS
SHALL BE ORDERLY AND NEAT.
4. EQUIPMENT - DURING THE SUBMITTAL PHASE, THIS CONTRACTOR SHALL SUBMIT LAYOUT OF ALL
PANELS, SWITCHGEAR, TRANSFORMERS, CONTACTORS, ETC. IN EACH EQUIPMENT ROOM WHERE THIS
EQUIPMENT IS LOCATED. ALL LAYOUTS MUST BE DRAWN TO SCALE AND DIMENSIONED.
ELECTRICAL DEMOLITION GENERAL NOTES
1. UNLESS NOTED ON DRAWINGS, ALL LIGHTING, SWITCHES, OUTLETS AND OTHER ELECTRICAL DEVICES
ARE TO REMAIN.
2. REFER TO SPECIFICATION SECTION 26 05 05, ELECTRICAL DEMOLITION REMODELING, FOR GENERAL
DEMOLITION REQUIREMENTS.
3. ALL MATERIAL REMOVED AND NOT RETAINED BY THE OWNER SHALL BE DISPOSED OF OFF SITE IN A
LAWFUL MANNER.
EMA Engineering & Consulting, Inc.
Tyler | Austin | Houston | El Paso
DFW | San Antonio | Shreveport
Texas Firm Registration No. F-893
Louisiana Firm Registration No. EF-5818
www.EMAengineer.com
REVIEW ONLY
NOT FOR REGULATORY
APPROVAL, PERMITTING,
OR CONSTRUCTION
Engineer:
License State: TX License No.: 108637
10-24-2025 4/1/2024 10:52:47 AM
Date:
ISSUE DATE
OCT. 24, 2025
ISSUE STATUS
DATE
SYMBOL
DESCRIPTION
BRANCH CIRCUIT - CONDUIT IN WALL or ABOVE CEILING, INDICATES DEVICES AND EQUIPMENT ON A CIRCUIT.
NOT INTENDED TO SHOW ROUTING
BRANCH CIRCUIT OR FEEDER CONDUIT UNDER FLOOR or UNDERGROUND
CL-1,3,5
SWITCH WIRE - SWITCH CIRCUIT
ARROW INDICATES HOMERUN, TEXT INDICATES PANEL AND CIRCUIT
PANEL BOARD or SWITCHGEAR (SEE PANEL SCHEDULES AND RISER DIAGRAM)
;
SPECIAL PANEL, EQUIPMENT RACK, CABINET, ETC. - SURFACE MOUNT ; FLUSH MOUNT
TX
POWER TRANSFORMER - SEE PANEL SCHEDULE, RISER AND SPECIFICATIONS
DISCONNECT / SAFETY SWITCH - SEE SCHEDULES FOR MORE INFORMATION
;
GROUND ; WEATHERHEAD
;
J; J
GFCI DUPLEX RECEPTACLE @6" ABOVE BACKSPLASH IF SHOWN AT MILLWORK or @18" AFF ; WEATHERPROOF GFCI
JUNCTION BOX - @ 18" AFF OR AS NOTED ; FLUSH WALLS / FLUSH CEILING or FLOOR or ELSE
;;
SR
RECEPTACLE @18" AFF OR AS NOTED - DUPLEX ; QUAD ; SIMPLEX
SURFACE-MOUNT RACEWAY - SEE SPECIFICATIONS FOR MORE INFORMATION
FIRE ALARM SIGNAL
LIGHT SWITCH BANK (REFER TO
STACKING DIAGRAM)
THERMOSTAT
INTERCOM
DEVICE
FIRE ALARM
PULL STATION
80"
4" 4" 4"
ELECTRICAL AND
COMMUNICATION
4"
44"
OUTLETS.
18"
SWITCH & OUTLET LOCATION DIAGRAM
1 TO 4
5 TO 6
7 TO 8
NOTE:
1. IF HIGH WATTAGE DIMMERS ARE USED ADJACENT
TO LIGHTING BANK, STACKING IS TO BE USED AS
INDICATED.
2. PROVIDE SINGLE GANGING PLATE W/ 1, 2, 3, OR 4
SWITCH LEG CAPACITY WHEREVER POSSIBLE.
PLAN
DIMEN.
COVER PLATE STACKING DIAGRAM
PLAN
DIMEN.
PLAN
DIMEN.
4" 4"
MAX. MAX.
4" MAX.
4" MAX.
FLOOR OUTLET DIAGRAM
OUTLET DIAGRAM
N.T.S.
4" 4"
MAX. MAX.
KEY PLAN
EMA JOB #: 5-001-1898-006
DRAWN BY:
MSA
CHECKED:
CMC
ELECTRICAL DETAILS,
NOTES, AND SYMBOLS
SHEET NUMBER
SUBMISSION OF BID WILL BE CONSIDERED ACKNOWLEDGMENT THAT THE
CONTRACTOR HAS VISITED THE SITE AND HAS VERIFIED ALL EXISTING JOB
CONDITIONS AND INCLUDED ANY NECESSARY MODIFICATION TO EXISTING
AND NEW WORK REQUIRED FOR INSTALLATION OF A COMPLETE AND
WORKING SYSTEM.