Bid Solicitation: BD-24-1202-COCC1-COCC1-99773
|
Header Information
|
Bid Number:
|
BD-24-1202-COCC1-COCC1-99773
|
Description:
|
IFB 2024-4A PROVIDE & INSTALL SMOKE DETECTORS (Re-Bid)
|
Bid Opening Date:
|
04/12/2024 11:00:00 AM
|
Purchaser:
|
Rita Brousseau
|
Organization:
|
Lowell Housing Authority
|
Department:
|
COCC1 - Finance & Procurement
|
Location:
|
COCC1 - Finance & Procurement
|
Fiscal Year:
|
24
|
Type Code:
|
NS - Non-Statewide Solicitation
|
Allow Electronic Quote:
|
No
|
Alternate Id:
|
|
Required Date:
|
|
Available Date
:
|
03/13/2024 11:16:12 AM
|
Info Contact:
|
Rita V. Brousseau, Chief Procurement Officer, rbrousseau@lhma.org
|
Bid Type:
|
OPEN
|
Informal Bid Flag:
|
No
|
Purchase Method:
|
Open Market
|
Pre Bid Conference:
|
NONE
|
Bulletin Desc:
|
All bids receive on February 29, 2024 have been rejected and a now call for bids is available at www.lhma.org/bids.
|
|
Ship-to Address:
|
Rita V. Brousseau
350 Moody Street
Lowell, MA 01854
US
Email: rbrousseau@lhma.org
Phone: (978)364-5341
FAX: (978)937-5758
|
Bill-to Address:
|
B OKeefe
PO Box 60
Lowell, MA 01853-0060
US
Email: bokeefe@lhma.org
Phone: (978)364-5310
FAX: (978)937-3725
|
Print Format:
|
Bid Print
|
File Attachments:
|
HUD-5369-b-Instructions-to-offerors-NONCONSTRUCTION.pdf
Table 5.1.pdf
LHA Code of Ethics.pdf
PO Reservation of Rights 2017
|
Form Attachments:
|
|
Required Quote Attachments
|
|
|
Item # 1:
(
72-13
-
00
)
|
Scope of Work: Contractor shall be responsible for providing and installing new photoelectric battery-operated smoke detectors in every bedroom at properties throughout the agency in accordance with Building Code and Federal HUD Regulations. There are approximately 797 wood ceilings and 1,664 concrete ceilings, see table below for bedroom breakdown.
Smoke alarm will be installed on ceilings and must be 18 inches from the wall and 18 inches from the doorway.
Smoke alarm will be installed at least 10 feet from a cooking appliance.
Smoke alarm should not: - Be installed near windows, doors, or ducts where drafts might interfere with their operation.
Installation inside each bedroom; - Within 21 feet of any door to a bedroom measured along a path of travel; and - Where a smoke detector installed outside a bedroom is separated from an adjacent living area by a door.
Smoke detectors offered by the bidder shall have 10-Year sealed lithium battery, voice notifications, test button, and end of unit life alerts. The authority reserves the right to determine whether the smoke detectors offered are acceptable.
|
|
U N S P S C Code:
|
72-13-00
General building construction
|
Qty
|
Unit Cost
|
UOM
|
Total Discount Amt.
|
Tax Rate
|
Tax Amount
|
Total Cost
|
1.0
|
|
EA - Each
|
|
|
|
|
Manufacturer:
|
|
Brand:
|
|
Model:
|
|
Make:
|
|
Packaging:
|
|
|
|
|
|
|
|
|
|
|