H146-- NEW Critical SPS Water Testing Milwaukee VAMC and Green Bay CBOC

Agency: VETERANS AFFAIRS, DEPARTMENT OF
State: Federal
Type of Government: Federal
FSC Category:
  • H - Quality Control, Testing, and Inspection Services
NAICS Category:
  • 541380 - Testing Laboratories
Posted Date: Feb 4, 2026
Due Date: Feb 9, 2026
Solicitation No: 36C25226Q0092
Original Source: Please Login to View Page
Contact information: Please Login to View Page
Bid Documents: Please Login to View Page

Description

Follow
H146-- NEW Critical SPS Water Testing Milwaukee VAMC and Green Bay CBOC
Active
Contract Opportunity
Notice ID
36C25226Q0092
Related Notice
Department/Ind. Agency
VETERANS AFFAIRS, DEPARTMENT OF
Sub-tier
VETERANS AFFAIRS, DEPARTMENT OF
Office
252-NETWORK CONTRACT OFFICE 12 (36C252)
Looking for contract opportunity help?

APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.

APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.

The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).

General Information View Changes
  • Contract Opportunity Type: Solicitation (Updated)
  • Updated Published Date: Feb 04, 2026 09:22 am CST
  • Original Published Date: Jan 20, 2026 12:34 pm CST
  • Updated Date Offers Due: Feb 09, 2026 10:00 am CST
  • Original Date Offers Due: Dec 05, 2025 10:00 am CST
  • Inactive Policy: Manual
  • Updated Inactive Date: Mar 11, 2026
  • Original Inactive Date: Feb 03, 2026
  • Initiative:
    • None
Classification
  • Original Set Aside:
  • Product Service Code: H146 - QUALITY CONTROL- WATER PURIFICATION AND SEWAGE TREATMENT EQUIPMENT
  • NAICS Code:
    • 541380 - Testing Laboratories and Services
  • Place of Performance:
Description View Changes
Who will provide the bottles for specimen testing?
The vendor will supply all bottles, tubes, cold packs, packaging and any other material supplies needed to perform and ship the specimens to maintain sample viability.

Regarding the Perry Johnson Laboratory Accreditation (PJLA)Testing Accreditation and International Organization for Standardization (ISO) and International Electrotechnical Commission (IEC) 17025:2017 certifications, We have the A2LA Laboratory Certification, Elite Laboratory and the ASSE International Certification. Our questions is:Â Do we have to have the PJLA or is the Certifications that we have for testing sufficient?
We will let the verbiage in the original documents stand. PJLA certification is required.

Would the VA like us to incorporate an SOP for the SPS?.
This would not be a need as part of the contract.
4. To make sure hold times are not exceeded in the event of shipping samples, will sampling in the afternoon be acceptable?
Sampling in the afternoon is acceptable provided it does not delay delivery to the lab or interfere with maintaining appropriate chain of custody.
5. Can you please confirm the parameters needed to be tested monthly for the first point of generation critical water chemistry panel with micro.
ST108 outlines all of the testing parameters. If the vendor is not aware of these testing parameters, the vendor likely lacks the knowledge or experience to adequately perform critical water testing. Please see attached document for the ST108 standard.

6. are field tests acceptable for pH, Alkalinity, conductivity, and hardness or will these need to be done by a Lab?
Final results need to be conducted through lab analysis.
7. Does the Lab have to have PJLA certification or is another ANSI recognized auditing body such as ANAB acceptable for ISO certification?
PJLA certification is required.
8. The solicitation states results must be password protected, does this apply only to the database where results are stored, or do emails need to be encrypted?
Emails do not need to be encrypted. The web-based reporting structure should be password protected.
9. Clarification on how many of the tests are being run prior to the UV? Â
UV treatment is continual in our critical water loops, with the exception of the cart washer loop at the Green Bay facility, where there is no UV treatment.
Attachments/Links
Contact Information
Contracting Office Address
  • GREAT LAKES ACQUISITION CENTER 115 S 84TH ST
  • MILWAUKEE , WI 53214
  • USA
Primary Point of Contact
Secondary Point of Contact


History
Get Government Bids Like This by Email Receive daily bid alerts that match your keywords, business categories, and target regions.

See Also

Follow High-Impact Shock and Shipboard Vibration Environmental Qualification Testing Active Contract Opportunity Notice

DEPT OF DEFENSE

Due by 9/18/2026

Follow HEATING, VENTILATION AND AIR CONDITIONING (HVAC) S Active Contract Opportunity Notice ID

INTERIOR, DEPARTMENT OF THE

Due by 9/17/2026

Follow KFO VAULT TOILET PUMPING Active Contract Opportunity Notice ID 140L6226Q0031 Related Notice

INTERIOR, DEPARTMENT OF THE

Due by 9/17/2026

Follow CUGA- UPGRADE WR CAMPGROUND ELECTRICAL Active Contract Opportunity Notice ID 140P5326R0024 Related

INTERIOR, DEPARTMENT OF THE

Due by 9/21/2026

* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.