FTG276 FPP Generator Control System (Brand Name Requirements)
| Agency: | DEPT OF DEFENSE |
|---|---|
| State: | Alaska |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Set Aside: | 8(a) Sole Source (FAR 19.8) |
| Posted Date: | Sep 2, 2026 |
| Due Date: | Sep 9, 2026 |
| Solicitation No: | W911KB26RA032 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Sources Sought (Updated)
- Updated Published Date: Sep 02, 2026 09:53 am AKDT
- Original Published Date: Sep 01, 2026 03:58 pm AKDT
- Updated Response Date: Sep 09, 2026 02:00 pm AKDT
- Original Response Date: Sep 08, 2026 02:00 pm AKDT
- Inactive Policy: 15 days after response date
- Updated Inactive Date: Sep 24, 2026
- Original Inactive Date: Sep 23, 2026
-
Initiative:
- None
- Original Set Aside: 8(a) Sole Source (FAR 19.8)
- Product Service Code:
-
NAICS Code:
- 332999 - All Other Miscellaneous Fabricated Metal Product Manufacturing
-
Place of Performance:
AKUSA
SOURCES SOUGHT: THIS NOTICE IS MARKET RESEARCH TO SUPPORT INCLUSION OF SOLE SOURCE (BRAND NAME) SPECIFICATIONS IN A CONSTRUCTION PROJECT – FTG276 FPP GENERATOR CONTROL SYSTEM, FORT GREELY, ALASKA - AND IS NOT A REQUEST FOR PROPOSAL.
The U.S. Army Engineer District, Alaska intends to specify the below listed items as part of a larger construction contract to be executed on Fort Greely, Alaska. A determination by the Government to not compete this requirement, for the specific items listed below, based on the responses to this notice is solely within the discretion of the Government. Reference RFO 6.103-1(d), “Only One Responsible Source and No Other Supplies or Services Will Satisfy Agency Requirements - Application for brand name descriptions.”
Items:
1. Cisco IE 3300 Network Switch. The FPP Generator Control System will utilize the Cisco IE 3300 network switches for panel-mounted applications and all generator paralleling control components are required to communicate and integrate with the PCMS and PQMS head ends.
2. Basler DECS-250 Voltage Regulators. The FPP will utilize the Basler DECS-250 Voltage Regulators to provide voltage regulation for the diesel generators.
3. Caterpillar EMCP 4.2 Generator Controllers. The FPP will utilize the Caterpillar EMCP 4.2 Generator Controllers to provide control and monitoring of the existing Caterpillar diesel generators powering facilities.
4. Woodward DSLC-2-XT and MSLC-2-XT Generator Paralleling Control System. The FPP will utilize the Woodward DSLC-2-XT and MSLC-2-XT Generator Paralleling Control System to provide auto-synchronization and isochronous load sharing control for the five diesel generators and two utility feeders that provide power.
5. Emerson CEP001 Profinet I/O Devices and associated Rx3i Profinet Scanner Cards. The FPP will utilize the Emerson CEP001 Profinet I/O Devices to replace the obsolete GE/Emerson Genius Block I/O devices in order to provide PCMS control and monitoring of medium voltage switchgear power facilities.
6. Monico Mcore Secure Data Routers. The FPP will utilize the Monico Mcore Secure Data Routers as gateways to integrate the Caterpillar generator monitoring points to the PCMS system.
7. Red Lion DA50A gateways. The FPP will utilize the Red Lion DA50A gateways to integrate power equipment monitoring points to the PCMS system
8. SEL-751A protective relays. The FPP will utilize the SEL-751A protective relays will be installed in the FPP to replace existing obsolete protective relays use for synchronism check protection. These protective relays must communicate to SEL-3530 RTAC communications gateways and SEL head-end monitoring software.
9. States 2FMS14-14QJ test blocks. The FPP will utilize the States 2FMS14-14QJ test blocks to test protective relays
THIS NOTICE IS A SOURCES SOUGHT NOTICE AND NOT A REQUEST FOR PROPOSAL. No solicitation will be available as these sole source items will be incorporated into the specifications of a FY26 solicitation for a construction project on Fort Greely, Alaska. Vendors who offer the above items which can meet all of the above functional criteria are invited to respond to this notice. Responses must include the following information:
1. Identification of the manufacturer’s name, address, and country of product manufacture.
2. Fully detailed specification sheets.
3. Narrative addressing how your product meets the salient features listed above.
Please send responses to mark.r.corn@usace.army.mil or catherine.williams@usace.army.mil
- CONTRACTING OFFICE KO 2204 3RD STREET
- ANCHORAGE , AK 99506-0898
- USA
- Mark Corn
- mark.r.corn@usace.army.mil
- Phone Number 9077532817
- Catherine Williams
- catherine.williams@usace.army.mil
- Phone Number 9077532571
- Sep 02, 2026 09:53 am AKDTSources Sought (Updated)
- Sep 02, 2026 09:52 am AKDT Sources Sought (Updated)
- Sep 01, 2026 03:58 pm AKDT Sources Sought (Original)
Related Document
| Sep 1, 2026 | [Sources Sought (Original)] Cisco IE 3300 Network Switches (Brand Name) |
| Sep 1, 2026 | [Special Notice (Original)] Balser DECS-250 Voltage Regulators (Brand Name) |
See Also
Basic Information Title INTENT TO PARTICIPATE - Sourcewell: #091125-TIM - Public Utility Equipment
State Government of Alaska
Due by 11/13/2026
+ 2026B078 - Provide First Aid and Burn Kit Inspection and Restocking Services
City of Anchorage
Due by 11/17/2026
+ 2026B078 - Provide First Aid and Burn Kit Inspection and Restocking Services
City of Anchorage
Due by 11/17/2026