Dry Chemical HAZMAT Locker System Replacement at U.S. Coast Guard Sector San Diego
| Agency: | HOMELAND SECURITY, DEPARTMENT OF |
|---|---|
| State: | California |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Set Aside: | No Set aside used |
| Posted Date: | Sep 2, 2025 |
| Due Date: | Sep 16, 2025 |
| Solicitation No: | 37250PR250000236 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Combined Synopsis/Solicitation (Original)
- Original Published Date: Sep 02, 2025 03:51 pm EDT
- Original Date Offers Due: Sep 16, 2025 09:00 am EDT
- Inactive Policy: 15 days after date offers due
- Original Inactive Date: Oct 01, 2025
-
Initiative:
- None
- Original Set Aside: No Set aside used
- Product Service Code: 7125 - CABINETS, LOCKERS, BINS, AND SHELVING
-
NAICS Code:
- 332311 - Prefabricated Metal Building and Component Manufacturing
-
Place of Performance:
San Diego , CA 92110USA
Replace and Install 06 Hazmat Locker Systems at US Coast Guard Sector San Diego:
2710 North Harbor Drive
San Diego CA 92101
For site visit please contact: CWO Kyle Kagami, Facilities Engineer Cell: (832) 293-5117
Replacement of the (6) dry chemical hazmat locker systems. Current systems are no longer supported and have multiple deficiencies.
Remove the system release, cylinder, supply line, nozzle, pull station and pressure switch at each hazmat room.
Install Pyrochem MONARCH dry chemical system components at each hazmat room:
1. MCH3 mechanical release and CO2 actuation cartridge w/MB-2 mounting bracket.
2. PCL-17ABC cylinder w/MB-15 mounting bracket.
3. Explosion proof pressure switch.
4. 3/4" galvanized supply line pipe and a NV-ABC nozzle.
5. RPS-M remote pull station.
6. Update existing mechanical detection.
All necessary Bracketing and Supports per the Monarch Manual.
Qualifications:
Devices such as contactors, shunt trips, solenoids, fans, relays, controls, power, line voltage or building fire alarm tie-in if applicable is by others. Wiring from Monarch micro switches to said devices by others.
Add: for one (1) suppression plan and NICET III stamp comprised of all six (6) systems. Individual suppression plans for
each system to incur additional charges. Permit/plan review fees if assessed to be reimbursed at cost.
Add: per system for explosion proof pressure switches, in lieu of micro switches, for electrical interlocks.
Installation to be performed during normal business hours 7am-3:30pm.
Electrical connection safe-off and reconnection by others.
There are existing penetrations in the cabinets housing the suppression systems. Sealing of the penetration's by others.
Services to be completed
[Industrial/Dry Chemical Suppression] Location - Building
DEFICIENCIES (SYSTEMS ARE NO LONGER SUPPORTED, DUE TO THE TYPE AND QUANTITY OF DEFICINCIES,
REPLACEMENT MATERIAL IS NOT AVAILABLE TO CERTIFY SYSTEMS. PROPOSED RESOLUTION IS REPLACEMENT OF
SYSTEMS WITH A PRODUCT LINE CURRENTLY SUPPORTED)
BLDG 66509:
-PULL STATION SEIZED
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66510:
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66511:
-BELL DID NOT OPERATE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66512:
-PRESSURE SWITCH WOULD NOT RESET (WATER DAMAGE)
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66513:
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
BLDG 66514:
-CYLINDER LOW ON PRESSURE
-HOSE REQUIRES HYDROSTATIC TESTING
-6 YEAR MAINTENANCE REQUIRED
-12 YEAR HYDROTEST REQUIRED
- 1001 SEASIDE AVE
- SAN PEDRO , CA 90731
- USA
- Kyle Kagami
- Kyle.S.Kagami@uscg.mil
- Phone Number (832) 293-5117
- Ryan H. King
- ryan.h.king2@uscg.mil
- Phone Number 6199435942
- Sep 02, 2025 03:51 pm EDTCombined Synopsis/Solicitation (Original)
Related Document
| Sep 9, 2025 | [Combined Synopsis/Solicitation (Updated)] Dry Chemical HAZMAT Locker System Replacement at U.S. Coast Guard Sector San Diego |
See Also
Project Name Acosta Operations Center (BP 05 - Millwork, Solid Surface Countertops, &
UCLA Capital Programs
Due by 10/06/2026
Follow MFT 26-119 - Furniture - 349 AMW Wing Staff Agencies (Ammend 1)
DEPT OF DEFENSE
Due by 9/15/2026
Basic Information Title IFB No. 132405 Metal Doors and Vision Glass Panels Replacement,
State Government of California
Due by 10/02/2026
Bid Number: 2026-008 Bid Title: Artesia Botanical Garden Category: Public Works Status: Open
City of Artesia
Due by 10/12/2026