Classical High School-Campus Electrical Upgrades Drawings
| Agency: | City of Providence |
|---|---|
| State: | Rhode Island |
| Type of Government: | State & Local |
| NAICS Category: |
|
| Posted Date: | Aug 28, 2026 |
| Due Date: | Oct 5, 2026 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
Attachment Preview
CITY OF PROVIDENCE
PROVIDENCE PUBLIC SCHOOL DEPARTMENT
CAMPUS ELECTRICAL UPGRADES AT
CLASSICAL HIGH SCHOOL
770 WESTMINSTER ST,
PROVIDENCE, RI 02903
PROJECT LOCATION MAPS
PROJECT LOCATION
CLASSICAL HIGH SCHOOL
770 WESTMINSTER ST,
PROVIDENCE, RI 02903
CLASSICAL HIGH SCHOOL
SITE
AREA MAP
LOCATION MAP
TRUE
NORTH
PLAN NORTH
SITE MAP
SHEET INDEX
SHEET NUMBER
SHEET TITLE
GENERAL
G-000
COVER SHEET
ELECTRICAL
E-000
ELECTRICAL COVER SHEET
E-101
ELECTRICAL SITE PLAN
E-102
ENLARGED ELECTRICAL FLOOR PLANS
E-501
ELECTRICAL DETAILS
E-502
ELECTRICAL DETAILS
E-601
ELECTRICAL SINGLE LINE DIAGRAM - BLDG 1
E-602
ELECTRICAL SINGLE LINE DIAGRAM - BLDG 2
Website: www.StudioJAED.com
Email: info@StudioJAED.com
ARCHITECT
STUDIOJAED
■ 2500 WRANGLE HILL ROAD, STE 110
BEAR, DELAWARE 19701
P: (302) 832-1652
■ 306 E. CAMDEN-WYOMING AVENUE
CAMDEN, DELAWARE 19934
P: (302) 832-1652
■ 42 WEYBOSSETT STREET, STE 403
PROVIDENCE, RHODE ISLAND 02903
P: (401) 648-0884
THIS DRAWING IS THE PROPERTY OF STUDIOJAED
AND IS PREPARED FOR THE EXCLUSIVE USE OF
ITS CLIENTS AT THE LOCATION INDICATED. NO
OTHER USE IS AUTHORIZED OR INTENDED.
ARCHITECT / ENGINEER SEAL
TRUE
NORTH
REVISIONS
MARK
DESCRIPTION
DATE
CODE INFORMATION
1. APPLICABLE CODES AND STANDARDS
SBC-1 RHODE ISLAND STATE BUILDING CODE (IBC 2021)
SBC-3 RHODE ISLAND STATE PLUMBING CODE (IPC 2021)
SBC-4 RHODE ISLAND STATE MECHANICAL CODE (IMC 2021)
SBC-5 RHODE ISLAND STATE ELECTRICAL CODE (NFPA 70, 2023)
SBC-8 RHODE ISLAND STATE ENERGY CONSERVATION CODE (IECC 2024)
INTERNATIONAL BUILDING CODE (IBC), 2021
INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2021
INTERNATIONAL ENERGY CONSERVATION CODE (IECC), 2024
NFPA 101+1 LIFE SAFETY CODE, 2021
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2021
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2019
ICC ANSI A117.1, 2017
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN (ADAAG)
OWNER:
2. PROJECT DATA
PROVIDENCE PUBLIC SCHOOL DEPARTMENT
SHEET TITLE
COVER SHEET
ISSUE
CONSTRUCTION
DOCUMENTS
AUGUST 13, 2026
DRAWN
JD
CHK'D
PP
PROJECT NO.
26020
LOCATION: CLASSICAL HIGH SCHOOL
TRUE
SHEET NO.
NORTH
ADDRESS: 770 WESTMINSTER ST, PROVIDENCE, RI 02903
G-000
OCCUPANCY CLASSIFICATION: EDUCATION GROUP E
© 2025 JAED CORPORATION
ELECTRICAL GENERAL NOTES
1. PROVIDE ALL LABOR, MATERIALS, TOOLS, EQUIPMENT, COORDINATION, ADDITIONAL DESIGN AND ALL INCIDENTALS NECESSARY
TO PROVIDE A COMPLETE AND OPERABLE SYSTEM AS DETAILED ON PLANS TO THE SATISFACTION OF THE ENGINEER AND THE
OWNER. COORDINATE ALL WORK WITH THE ENGINEER BEFORE THE START OF WORK.
2. PRIOR TO SUBMITTING BID, THE CONTRACTOR SHALL VISIT THE SITE AND BE THOROUGHLY FAMILIAR WITH THE EXISTING
CONDITIONS AND PROPOSED CONSTRUCTION. CONTRACTOR SHALL INCLUDE IN THEIR BID ALL MATERIAL, LABOR, AND ALL
INCIDENTALS FOR A COMPLETE INSTALLATION WHETHER SPECIFICALLY INDICATED OR NOT. ALL ERRORS, DISCREPANCIES AND
MISSED ITEMS SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER DURING THE BIDDING PROCESS BY THE CONTRACTOR.
THESE ITEMS SHALL BE INCLUDED IN THE BID PRICE. NO EXTRA COST WILL BE ALLOWED FOR ANY DISCREPANCY WHICH COULD
HAVE BEEN NOTICED AT THE SITE VISIT BY THE CONTRACTOR.
3. PERFORM WORK AS REQUIRED BY APPLICABLE CODES, REGULATIONS, AND LAWS OF LOCAL, STATE, AND FEDERAL
GOVERNMENTS AND OTHER AUTHORITIES WITH LAWFUL JURISDICTION. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST
EDITION OF THE NATIONAL ELECTRIC CODE.
4. MATERIAL AND EQUIPMENT SHALL BE NEW (UNLESS NOTED), UL, NEMA, ANSI, IEEE, ADA & CMB APPROVED FOR INTENDED
PURPOSE. MATERIAL AND INSTALLATION SHALL MEET REQUIREMENTS OF NATIONAL AND LOCAL ELECTRICAL CODE.
5. GIVE NOTICES, FILE PLANS, OBTAIN PERMITS, AND LICENSES, PAY FEES AND BACK CHARGES, AND OBTAIN NECESSARY
APPROVALS FROM AUTHORITIES THAT HAVE JURISDICTION.
6. MAINTAIN RECORD DRAWINGS ON SITE. RECORD SET MUST BE COMPLETE AND CURRENT AND AVAILABLE FOR INSPECTION
WHEN REQUISITIONS FOR PAYMENT ARE SUBMITTED.
7. GUARANTEE WORK IN WRITING PER SPECIFICATIONS, REPAIR OR REPLACE DEFECTIVE MATERIALS OR INSTALLATION AT NO
COST TO OWNER DURING THE GUARANTEE PERIOD. CORRECT DAMAGE CAUSED IN MAKING NECESSARY REPAIRS AND
REPLACEMENTS UNDER GUARANTEE AT NO COST TO OWNER. SUBMIT GUARANTEE TO OWNER BEFORE FINAL PAYMENT.
8. COORDINATE ALL ELECTRICAL ITEMS WITH EXISTING FIELD CONDITIONS. LOCATIONS SHOWN ARE APPROXIMATE AND MAY
REQUIRE MINOR ADJUSTMENT IN THE FIELD TO SATISFY THE DESIGN INTENT.
9. DAMAGE TO EXISTING FACILITIES AND EQUIPMENT SHALL BE REPAIRED OR REPLACED IMMEDIATELY BY THE CONTRACTOR AT
NO ADDITIONAL EXPENSE TO THE OWNER.
10. THE LOCATIONS ON THESE PLANS ARE APPROXIMATE AND REQUIRE COORDINATION WITH ALL OTHER TRADES AND
VERIFICATION OF EXISTING CONDITIONS. ROUTING OF CONDUIT IS DIAGRAMMATIC IN NATURE AND NOT INTENDED TO SHOW ALL
REQUIRED OFFSETS AND DETAILS. THE CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING ASSOCIATED
EQUIPMENT AND CONDITIONS. COORDINATE THE LOCATION OF ALL EQUIPMENT WITH THE ENGINEER AND THE OWNER.
CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL OTHER TRADE’S DRAWINGS AND SPECIFICATIONS AND COORDINATING WITH
ALL OTHER TRADES DURING BIDDING AND CONSTRUCTION. THE CONTRACTOR IS TO INCLUDE CIRCUIT LENGTHS OF WIRE AND
CONDUIT REQUIRED TO INSTALL CONNECTED DEVICES AND EQUIPMENT SUCH AS PANELBOARDS, SWITCHBOARDS,
TRANSFORMERS, ETC. WITHIN 15 FEET OF THE LOCATION SHOWN.
11. CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING CONTINUITY OF ALL POWER, CONTROL, FIRE ALARM, SECURITY
SYSTEMS, AND COMMUNICATIONS FUNCTIONS TO ALL AREAS AFFECTED BY DEMOLITION AND/OR NEW CONSTRUCTION.
12. REPAIR AND PATCH ANY DISTURBED AREAS TO MATCH ADJACENT CONSTRUCTION.
13. DISCONNECT AND MAKE SAFE ANY EQUIPMENT TO BE REMOVED BY OTHERS. COORDINATE REMOVAL OF EQUIPMENT WITH
OTHER TRADES PRIOR TO DEMOLITION.
14. IN ANY AREA REQUIRING THE PERFORMANCE OF ANY TRADE’S WORK, THIS CONTRACTOR SHALL CAREFULLY REMOVE AND
STORE ANY OR ALL ELECTRICAL ITEMS IN PATH OF WORK, REINSTALLING, AND RECONNECTING SAME AS REQUIRED, IN
ACCORDANCE WITH THE PLANS AND/OR AS DIRECTED AFTER COMPLETION OF OTHER TRADE’S WORK IN THAT AREA.
15. PRIOR TO THE START OF DEMOLITION, CONTRACTOR SHALL FIELD VERIFY ALL BRANCH CIRCUITS AND MAINTAIN THOSE
CIRCUITS THAT EXTEND OUTSIDE THE SCOPE OF WORK.
16. AFTER RENOVATING EXISTING ELECTRICAL WORK, THE CONTRACTOR SHALL ENSURE THAT ALL REMAINING AND NEW
EQUIPMENT WILL OPERATE PROPERLY, INCLUDING BUT NOT LIMITED TO BACKFEEDING OF EXISTING POWER AND LIGHTING
CIRCUITS. REFER TO SINGLE LINE DIAGRAM.
17. ALL ELECTRICAL WORK INDICATED TO REMAIN SHALL BE SUITABLY PROTECTED TO PREVENT ANY DAMAGE.
18. WHERE ELECTRICAL SYSTEMS PASS THROUGH RENOVATED AREAS TO SERVE OTHER PORTIONS OF THE PREMISES, SYSTEMS
SHALL BE SUITABLY PROTECTED TO PREVENT DAMAGE OR RELOCATED AND THE SYSTEMS RESTORED TO NORMAL OPERATION.
ANY OUTAGES IN SYSTEMS SHALL BE COORDINATED WITH OWNER. RESTORE POWER TO EXISTING TO REMAIN EQUIPMENT IF
INTERRUPTED BY DEMOLISHED CIRCUITS IN THE AREA.
19. CONTRACTOR SHALL SUBMIT FOR REVIEW, SHOP DRAWINGS FOR ALL EQUIPMENT AND MATERIALS USED ON THE PROJECT.
SUBMITTALS SHALL BE REVIEWED BY THE ENGINEER BEFORE PURCHASE OF MATERIALS.
20. ALL WIRING SHALL BE COPPER, 600V, 75°/90° RATED WITH FLAME-RETARDENT, HEAT AND MOISTURE RESISTANT INSULATION.
ALL NEW PANELBOARDS AND SWITCHBOARDS SHALL BE PROVIDED WITH COPPER BUSBARS, COPPER NEUTRAL BARS, AND
COPPER GROUND BARS. ALL NEW TRANSFORMERS SHALL HAVE COPPER WINDINGS.
21. PERMANENTLY LABEL ALL NEW ELECTRICAL EQUIPMENT, INCLUDING BUT NOT LIMITED TO, DEVICE DESIGNATION AND SUPPLY
CIRCUIT DESIGNATION. UPDATE OR REPLACE PANEL DIRECTORIES TO INCLUDE NEW CIRCUIT INFORMATION RESULTING FROM
THIS PROJECT.
22. PROVIDE TEMPORARY POWER AND LIGHTING FOR ALL TRADES AS REQUIRED TO COMPLETE THE PROJECT. ALL TEMPORARY
AND INTERIM EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES AND STANDARDS INCLUDING, BUT
NOT LIMITED TO NFPA 110 AND NFPA 70.
23. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION THAT IS NOT SHOWN ON THE DRAWINGS.
24. OPENINGS IN EXISTING CONCRETE AND MASONRY WALLS AND FLOORS REQUIRED FOR CONDUIT INSTALLATION SHALL BE CORE
DRILLED. MAXIMUM CORE DRILL SIZE SHALL BE 5” IN DIAMETER. CORE DRILL LOCATIONS SHALL BE SPACED A MINIMUM OF 6”
FROM EACH OTHER MEASURED FROM THE OUTSIDE EDGE OF THE CORE DRILL. ALL CORE DRILL OPENINGS SHALL BE PROPERLY
SEALED ACCORDING TO THEIR LOCATION AND APPLICATION.
25. ALL OUTAGES SHALL BE KEPT TO A MINIMUM. ALL WORK THAT REQUIRES A SUSTAINED EQUIPMENT OUTAGE SHALL BE
PERFORMED CONTINUOUSLY AROUND THE CLOCK UNTIL WORK IS COMPLETED UNLESS NOTED OTHERWISE. COORDINATE
OUTAGES WITH OWNER REPRESENTATIVE.
26. PROVIDE FOR EACH BRANCH CIRCUIT AND FEEDER CIRCUIT A DEDICATED EQUIPMENT GROUND WIRE. FOR SINGLE PHASE
BRANCH CIRCUITS OF 120 V/1PH OR 277V/1 PH, PROVIDE DEDICATED HOT, DEDICATED NEUTRAL AND DEDICATED EQUIPMENT
GROUND WIRES. SHARING OF NEUTRAL OR EQUIPMENT GROUND WIRES IS NOT PERMITTED. WIRING TO ALL HVAC EQUIPMENT
OR OTHER TRADE EQUIPMENT SHALL BE IN CONDUIT. ALL EQUIPMENT AND FEEDER WIRING IN MECHANICAL ROOM/ELECTRICAL
ROOM SHALL BE IN RIGID CONDUIT. USE OF MC CABLE IS LIMITED TO BRANCH CIRCUIT WIRING ABOVE RECESSED CEILING OR
CONCEALED IN WALL. WIRING TO OUTLETS ON TABLE SHALL BE PROVIDE IN EITHER EMT CONDUIT OR FLEXIBLE METAL CONDUIT.
DO NOT USE PLASTIC TIE WRAPS TO SUPPORT CONDUITS AND MC CABLES. MC CABLES SHALL BE SUPPORTED AT MAXIMUM OF
6'-0" WITH SECURELY FASTENED MC CABLE SUPPORT CLAMPS, J-HOOKS, OR METAL CABLE BRACKETS.
27. PROVIDE IDENTIFICATION LABELS FOR ALL BRANCH CIRCUITS AND FEEDERS CIRCUITS AT JUNCTION BOXES, PANELBOARDS,
TROUGHS, AND SPLICE BOXES.
28. PROVIDE UNSPLICED FEEDERS FROM PANELBOARD OR SWITCHBOARD TO ALL EQUIPMENT, INCLUDING ALL 20 AMPERE, SINGLE
POLE BRANCH CIRCUIT WIRING.
29. ALL WIRING DEVICES ARE TO BE RECESSED WHERE POSSIBLE. WHERE RECESSING IS NOT POSSIBLE, WIRING DEVICES ARE TO
BE SURFACE MOUNTED WITH CIRCUIT WIRING ROUTED IN SURFACE MOUNTED CONDUIT PER SPECIFICATIONS.
30. ALL CONDUIT PENETRATIONS THROUGH WALLS OR CEILINGS SHALL BE PATCHED AND SEALED WITH FIRE RATED FOAM SEALANT.
31. PROVIDE INSULATING BUSHINGS ON CONDUIT THREADS OR CONNECTORS WHERE RACEWAYS WITH CONDUITS OR MC CABLES
ENTER A BOX OR ENCLOSURE. THIS BUSHING SHALL BE INSTALLED ON ALL CABLES AND CONDUITS.
ELECTRICAL SYMBOL LEGEND
Power Devices
WP/GFCI
GENERAL PURPOSE DUPLEX RECEPTACLE - 20AMP, 125VOLTS, NEMA5-20R, TAMPER RESISTANT. ELECTRICAL BOX TO
BE 2-1/8" DEEP.
GENERAL PURPOSE GFCI DUPLEX RECEPTACLE - 20AMP, 125VOLTS, NEMA5-20R, TAMPER RESISTANT. ELECTRICAL
BOX TO BE 2-1/8" DEEP. OUTLETS INSTALLED OUTDOORS OR ON ROOF SHALL HAVE DIECAST ALUMINUM BOX 2-1/8"
DEEP (MIN.), AND WHILE IN USE WEATHERPROOF COVER; THOMAS&BETTS CKMUV OR APPROVED EQUAL.
JB
JUNCTION BOX
FUSED DISCONNECT SWITCH-HEAVY DUTY, 3POLE WITH FUSE CLIPS SUITABLE FOR CLASS "R" FUSES. NEMA1 UNLESS
NOTED. WP-WEATHER PROOF-NEMA3R ENCLOSURE. (NOMENCLATURE: 30A/20A = SWITCH SIZE/FUSE SIZE). SQ D CLASS
3110 OR EQUAL. DO NOT INSTALL ON TOP OF EQUIPMENT LABELS OR NAMEPLATES.
GRAPHIC CONVENTIONS
Wiring Devices
HOMERUN PANEL
DESIGNATION
PLA-11
BRANCH CIRCUIT
DESIGNATION
OUTLETS TO BE MOUNTED AT
STANDARD HEIGHT UNLESS
OTHERWISE NOTED
Disconnects
30A, WP
20A, RK1
DISCONNECT SIZE,
WP: WEATHER PROOF
FUSE SIZE,
TYPE RK1
ELECTRICAL ABBREVIATIONS
(D) - DENOTES EQUIPMENT OR WIRING TO BE DEMOLISHED
(E) - DENOTES EXISTING EQUIPMENT OR WIRING TO REMAIN
(N) - DENOTES NEW EQUIPMENT OR WIRING
A - AMPS
AC - ABOVE CEILING
AF - AMPERE FRAME
AFF - ABOVE FINISHED FLOOR
AT - AMPERE TRIP
ATS - AUTOMATIC TRANSFER SWITCH
BLDG - BUILDING
C - CONDUIT
CB - CIRCUIT BREAKER
DISC - DISCONNECT
ENCL - ENCLOSURE
FA - FIRE ALARM
FC - FOOTCANDLE(S)
G - GROUND
GFCI - GROUND FAULT CIRCUIT INTERRUPTER
KA - KILO AMPERE
KV - KILO VOLT
KVA - KILO VOLT AMPERE
LI - LONG TIME + INSTANTANEOUS
LSI - LONG TIME + SHORT TIME + INSTANTANEOUS
LSTG - LONG TIME + SHORT TIME + INSTANTANEOUS + GROUND
MCB - MAIN CIRCUIT BREAKER
MCCB - MOLDED CASE CIRCUIT BREAKER
MDP - MAIN DISTRIBUTION PANEL
MFR - MANUFACTURER
NTS - NOT TO SCALE
OC - ON CENTER
PH - PHASE
PNL - PANEL
RM - ROOM
SP - SPEAKER
SPD - SURGE PROTECTIVE DEVICE
SW - SWITCH
SWBD - SWITCHBOARD
UG - UNDERGROUND
UPS - UNINTERRUPTIBLE POWER SOURCE
V - VOLTS
W - WATTS OR WIRE
WP - WEATHERPROOF
XFMR - TRANSFORMER
Z - IMPEDANCE
Website: www.StudioJAED.com
Email: info@StudioJAED.com
ARCHITECT
STUDIOJAED
■ 2500 WRANGLE HILL ROAD, STE 110
BEAR, DELAWARE 19701
P: (302) 832-1652
■ 306 E. CAMDEN-WYOMING AVENUE
CAMDEN, DELAWARE 19934
P: (302) 832-1652
■ 42 WEYBOSSETT STREET, STE 403
PROVIDENCE, RHODE ISLAND 02903
P: (401) 648-0884
THIS DRAWING IS THE PROPERTY OF STUDIOJAED
AND IS PREPARED FOR THE EXCLUSIVE USE OF
ITS CLIENTS AT THE LOCATION INDICATED. NO
OTHER USE IS AUTHORIZED OR INTENDED.
ARCHITECT / ENGINEER SEAL
REVISIONS
MARK
-
DESCRIPTION
-
DATE
-
SHEET TITLE
ELECTRICAL
COVER SHEET
ISSUE
CONSTRUCTION
DOCUMENTS
AUGUST 13, 2026
DRAWN
JD
CHK'D
PP
PROJECT NO.
26020
SHEET NO.
E-000
© 2025 JAED CORPORATION
5
E-102
CLASSICAL
- BUILDING 1
LOCATION OF NEW XFMR-1
FOR BUILDING 1 - WO14814108
(N) 4"DIA
(D) 4"DIA
(N) 4"DIA
(D) 4"DIA
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
(N) (8) 4" PVC SCH40
E
E
E
E
- UG IN CONCRETE
E
E
E
E
DUCT BANK
E
E
(N) 4"DIA
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
(D) 4"DIA
E
E
E
(N) (2) 4" PVC SCH40
- UG IN CONCRETE
DUCT BANK
2
E-101
EC SHALL DISCONNECT AND REMOVE OUTDOOR PAD MOUNTED TRANSFORMER AND DEMOLISH
CONCRETE PAD. EC SHALL PROVIDE NEW SPLICE BOX ON A NEW CONCRETE PAD. SPLICE BOX
SHALL BE 30"H x 64"W x 24"D, NEMA-3R, LOCKABLE COVER, WITH POLARIS OR APPROVED EQUAL
LUGS TO SPLICE CONDUCTORS. SEE SHEET E-502 FOR CONCRETE PAD DETAILS.
CENTRAL
CLASSICAL
- BUILDING 2
E
E
(N) 10"DIA
(D) 10"DIA
LOCATION OF NEW SWITCHGEAR
(D) 10"DIA
(N) 10"DIA
MANHOLE PROVIDED BY EC IN
ACCORDANCE WITH UTILITY
REQUIREMENTS
3
E-101
BLDG - "H"
BOILER ROOM
(N) (2) 4" PVC SCH40
- UG IN CONCRETE
DUCT BANK
LOCATION OF NEW XFMR-2
FOR BUILDING 2 - WO14814110
2
E-102
1 OVERALL ELECTRICAL SITE PLAN
TRUE
E-101 SCALE: 1/32" = 1'-0"
NORTH
(N) 4"DIA
(D) 4"DIA
(N) PAD MOUNTED XFMR AND
CONCRETE PAD - SEE TRANSFORMER
DETAILS ON SHEET E-501. COORDINATE
ORIENTATION AND LOCATION WITH
UTILITY. COORDINATE WITH EXISTING
UNDERGROUND UTILITIES. WO14814108
(N) 4"DIA
(D) 4"DIA
(N) 4"DIA
E
E
E
E
E
E
E
(N) (8) 4" PVC SCH40
- UG IN CONCRETE
DUCT BANK
Website: www.StudioJAED.com
Email: info@StudioJAED.com
ARCHITECT
STUDIOJAED
■ 2500 WRANGLE HILL ROAD, STE 110
BEAR, DELAWARE 19701
P: (302) 832-1652
■ 306 E. CAMDEN-WYOMING AVENUE
CAMDEN, DELAWARE 19934
P: (302) 832-1652
■ 42 WEYBOSSETT STREET, STE 403
PROVIDENCE, RHODE ISLAND 02903
P: (401) 648-0884
(N) METER - BY UTILITY
(D) 4"DIA
(N) (2) 4" PVC SCH40 UG
IN CONCRETE DUCTBANK
WITH HV CABLE
(N) BOLLARDS - SEE BOLLARD
DETAIL ON SHEET E-501.
2 ENLARGED ELECTRICAL SITE PLAN - 1
E-101 SCALE: 1/4" = 1'-0"
THIS DRAWING IS THE PROPERTY OF STUDIOJAED
AND IS PREPARED FOR THE EXCLUSIVE USE OF
ITS CLIENTS AT THE LOCATION INDICATED. NO
TRUE
OTHER USE IS AUTHORIZED OR INTENDED.
NORTH
ARCHITECT / ENGINEER SEAL
CONTRACTOR TO REMOVE AND
REPLACE EXISTING FENCING AS
REQUIRED TO FACILITATE
CONSTRUCTION.
E
E
(N) 10"DIA
(D) 10"DIA
(N) (2) 4" PVC SCH40
- UG IN CONCRETE
DUCT BANK
CONTRACTOR TO PROVIDE
(2) NEW 3'-0" WIDE GATES IN
NEW FENCING.
LOCATION OF NEW SWITCHGEAR MANHOLE
PROVIDED BY EC IN ACCORDANCE WITH
UTILITY REQUIREMENTS. SEE SWITCHGEAR
MANHOLE BOLLARD DETAIL AND SWITCHGEAR
MANHOLE PLAN & SECTION ON SHEET E-502.
(D) 10"DIA
(N) 10"DIA
3 ENLARGED ELECTRICAL SITE PLAN - 2
E-101 SCALE: 1/4" = 1'-0"
REVISIONS
MARK
-
DESCRIPTION
-
DATE
-
SHEET TITLE
ELECTRICAL SITE PLAN
ISSUE
CONSTRUCTION
DOCUMENTS
AUGUST 13, 2026
DRAWN
JD
CHK'D
PP
PROJECT NO.
26020
SHEET NO.
TRUE
NORTH
E-101
© 2025 JAED CORPORATION
2
E-102
CONTRACTOR TO
RELOCATE EXISTING
CONEX BOX TO NEW
LOCATION.
E
E
E
E
E
E
E
E
KILN
1FT03A
STO
---
STORAGE
1FT05
CLASSROOM
1FT06
ELEV
---
STO
---
E
VEST
---
E
HALL
---
E
E
STAIR
---
E
E
JAN
---
TOILET
---
MECHANICAL ROOM
---
TOILET
---
ROOM
---
E
E
E
E
E
E
E
E
E
E
CORRIDOR
---
TENNIS
---
VISITORS LOCKER ROOM
---
ATHLETIC DIRECTOR
---
BOYS LOCKER ROOM
---
ROOM
---
ROOM
---
TOILET
---
VEST
---
VEST
---
STO
---
TRAINER/COACH RM
---
STO
TOILET
---
---
HALL
---
VEST
---
STO
---
VARSITY LOCKER ROOM
---
ROOM
136
115 SF
STORAGE
---
STO
---
ROOM
137
114 SF
3,4
E-102
STAIRWELL
118
213 SF
STAIRWELL
116
284 SF
PASSAGE
103
86 SF
MENS TLT
105
122 SF
MENS DRESSING RM
104
237 SF
PASSAGE
108
45 SF
MAIN ELECTRICAL
123
215 SF
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
STO
---
VENDING
ROOM
---
TEMP. GIRLS
LOCKER RM.
---
GIRLS TLT
106
111 SF
WOMENS TLT
107
358 SF
MUSIC TEACHER
122
203 SF
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
GIRLS TLT
110
306 SF
PASSAGE
109
51 SF
ROOM
119
1667 SF
CAFETERIA
131
9140 SF
BOYS TLT
SCKV-IT_T4AU9RNR7EW2ION-TEAULSLSCHINA
111
240 SF
PASSAGE
112
48 SF
ROOM
126
155 SF
FAMILY CENTER
120
203 SF
ROOM
135
361 SF
ROOM
132
1171 SF
ROOM
133
631 SF
ROOM
134
207 SF
LOBBY
117
732 SF
ROOM
102
230 SF
ROOM
138
43 SF
ROOM
101
288 SF
STAIRWELL
115
156 SF
1 BUILDING 2 - ELECTRICAL FLOOR PLAN
E-102 SCALE: 1/16" = 1'-0"
CORRIDOR
124
986 SF
CHOIR ROOM
121
1398 SF
MUSIC ROOM
113
1711 SF
STAIRWELL
125
94 SF
MUSIC PRACT
127
90 SF
MUSIC PRACT
130
92 SF
MUSIC PRACT
129
92 SF
MUSIC PRACT
128
92 SF
CORRIDOR
114
2100 SF
TRUE
NORTH
(E) SWBD
Website: www.StudioJAED.com
Email: info@StudioJAED.com
ARCHITECT
STUDIOJAED
■ 2500 WRANGLE HILL ROAD, STE 110
BEAR, DELAWARE 19701
P: (302) 832-1652
■ 306 E. CAMDEN-WYOMING AVENUE
CAMDEN, DELAWARE 19934
P: (302) 832-1652
■ 42 WEYBOSSETT STREET, STE 403
PROVIDENCE, RHODE ISLAND 02903
P: (401) 648-0884
THIS DRAWING IS THE PROPERTY OF STUDIOJAED
AND IS PREPARED FOR THE EXCLUSIVE USE OF
ITS CLIENTS AT THE LOCATION INDICATED. NO
OTHER USE IS AUTHORIZED OR INTENDED.
ARCHITECT / ENGINEER SEAL
(N) PAD MOUNTED XFMR AND
CONCRETE PAD - SEE TRANSFORMER
DETAILS ON SHEET E-501. COORDINATE
ORIENTATION AND LOCATION WITH
UTILITY. COORDINATE WITH EXISTING
UNDERGROUND UTILITIES. WO14814110
(N) BOLLARDS - SEE BOLLARD
DETAIL ON SHEET E-501.
(2) 4" PVC SCH40
UG IN DUCTBANK
WITH HV CABLE
E
E
E
(N) METER - BY UTILITY
E
E
E
E
E
(7) 4" PVC SCH40 UG IN
NON-CONCRETE DUCT
BANK - 30" BELOW
GRADE
4'-0"
E
E
2'-0"
(N) MCB
(N) DISTB.
E
E
(N) FLOOR
MTD
ACTIVE
FILTER
EXISTING FIRE
SPRINKLER PIPE
E
E
E
E
E
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
STORAGE
EXISTING FIRE
SPRINKLER PIPE
4" HIGH CONCRETE PAD 6"
LARGER THAN FOOTPRINT OF
EQUIPMENT ON ALL SIDES.
2 BUILDING 2 - PARTIAL ELECTRICAL SITE PLAN
TRUE
E-102 SCALE: 1/4" = 1'-0"
NORTH
2.4 KW SWITCH (D)
DRYTYPE XFMR - 500 KWA,
2.4 KV/208/120V, 3P4W (D)
PASSAGE
MAIN SWITCH - 1600A,
208/120V, WESTINGHOUSE
& ATS - 400A (D)
DISTRIBUTION SECTION
- 1600A, 208/120V (D)
PASSAGE
MAIN
ELECTRICAL
CORRIDOR
PASSAGE
PASSAGE
PROVIDE NAMEPLATE INDICATING
LOCATION OF TRANSFORMER'S
PRIMARY SIDE DISCONNECTING
MEANS.
E
E
(N) XFMR
(N) MCB
(N) DISTB.
E
E
MAIN
ELECTRICAL
CORRIDOR
112.5 KWA DRYTYPE
480 - 208/120V (D)
(E) 200A, FSW ATHLETIC
FIELD LTG PNL TO REMAIN
3 BUILDING 2 - ELEC RM DEMOLITION PLAN
E-102 SCALE: 1/4" = 1'-0"
E
E
E
E
E
E
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
TO (N) SWBD-1
E
E
(E) 200A, FSW ATHLETIC
FIELD LTG PNL TO REMAIN
(N) 4# 4/0 +1#4G - 2 1/2"C
4 BUILDING 2 - ELEC RM CONSTRUCTION PLAN
E-102 SCALE: 1/4" = 1'-0"
(E) CONDUIT
EC SHALL DISCONNECT AND REMOVE OUTDOOR
PAD MOUNTED TRANSFORMER AND DEMOLISH
CONCRETE PAD. EC SHALL PROVIDE NEW SPLICE
BOX ON A NEW CONCRETE PAD. SPLICE BOX
SHALL BE 30" x 64" x 24", NEMA-3R, LOCKABLE
COVER, WITH POLARIS OR APPROVED EQUAL
LUGS TO SPLICE CONDUCTORS.
E
E
E
E
E
5 BUILDING 1 - BASEMENT ELECTRICAL PLAN
E-102 SCALE: 3/16" = 1'-0"
REVISIONS
MARK
-
DESCRIPTION
-
DATE
-
WO14814110
AREA OF WORK
WO14814110
AREA OF WORK
(N) PAD MOUNTED XFMR AND
CONCRETE PAD - SEE TRANSFORMER
DETAILS ON SHEET E-501. COORDINATE
ORIENTATION AND LOCATION WITH
UTILITY. COORDINATE WITH EXISTING
UNDERGROUND UTILITIES. WO14814110
(N) BOLLARDS - SEE BOLLARD
DETAIL ON SHEET E-501.
(2) 4" PVC SCH40
UG IN DUCTBANK
WITH HV CABLE
(7) 4" PVC
SCH40 UG
IN
NON-CONCRETE
DUCT
BANK - 30" (N) METER - BY UTILITY
BELOW
GRADE
2'-0"
4'-0"
(N) MCB
EXISTING FIRE
SPRINKLER PIPE
(N) DISTB.
(N)
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
FLOOR
MTD
ACTIVE 4" HIGH CONCRETE PAD 6"
FILTER LARGER THAN FOOTPRINT OF
EQUIPMENT ON ALL SIDES.
EXISTING FIRE
SPRINKLER PIPE
E
KILN
1FT03A
STO
---
STORAGE
1FT05
CLASSROOM
1FT06
ELEV
---
STO
---
VEST
---
HALL
---
E
STAIR
---
JAN
---
TOILET
---
MECHANICAL ROOM
---
TOILET
---
ROOM
---
TENNIS
---
E
CORRIDOR
E
---
VISITORS LOCKER ROOM
---
ATHLETIC DIRECTOR
---
BOYS LOCKER ROOM
---
ROOM
---
ROOM
---
TOILET
---
VEST
---
VEST
---
STO
---
TRAINER/COACH RM
---
STO
---
TOILET
---
HALL
---
VEST
---
STO
---
VARSITY LOCKER ROOM
---
ROOM
136
115 SF
STORAGE
---
STO
---
ROOM
137
114 SF
ROOM
135
361 SF
ROOM
132
1171 SF
ROOM
133
631 SF
ROOM
134
207 SF
STAIRWELL
118
213 SF
E
E
STO
---
VENDING
ROOM
---
E
TEMP. GIRLS
LOCKER RM.
---
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
CAFETERIA
131
9140 SF
STAIRWELL
116
284 SF
MENS TLT
105
122 SF
MENS DRESSING RM
104
237 SF
E
PROVIDE NAMEPLATE INDICATING
LOCATION OF TRANSFORMER'S
PRIMARY SIDE DISCONNECTING
MEANS.
2.4 KW SWITCH (D)
(N) XFMR
DRYTYPE XFMR - 500 KWA,
2.4 KV/208/120V, 3P4W (D)
PASSAGE
MAIN SWITCH - 1600A,
103 208/120V, WESTINGHOUSE
& ATS - 400A (D)
86 SF
(N) MCB
DISTRIBUTION SECTION
- 1600A, 208/120V (D)
(N) DISTB.
PASSAGE
108
45 SF
MAIN ELECTRICAL
123
215 SF
(2) 4"C ABOVE
CEILINGS WHERE
APPLICABLE
TO (N)
SWBD-1
112.5 KWA DRYTYPE
480 - 208/120V (D)
(E) 200A, FSW ATHLETIC
FIELD LTG PNL TO REMAIN
(N) 4# 4/0 +1#4G - 2 1/2"C
GIRLS TLT
106
111 SF
WOMENS TLT
107
358 SF
MUSIC TEACHER
122
203 SF
GIRLS TLT
110
306 SF
PASSAGE
109
51 SF
ROOM
119
1667 SF
BOYS TLT
111
240 SF
PASSAGE
112
48 SF
ROOM
126
155 SF
FAMILY CENTER
120
203 SF
LOBBY
117
732 SF
ROOM
102
230 SF
ROOM
138
43 SF
ROOM
101
288 SF
STAIRWELL
115
156 SF
CORRIDOR
124
986 SF
CHOIR ROOM
121
1398 SF
MUSIC ROOM
113
1711 SF
STAIRWELL
125
94 SF
MUSIC PRACT
127
90 SF
MUSIC PRACT
130
92 SF
MUSIC PRACT
129
92 SF
MUSIC PRACT
128
92 SF
CORRIDOR
114
2100 SF
KEY PLAN - BLDG 2
E
E
E
E
WO14814108
AREA OF WORK
(E) SWBD
(E) CONDUIT
KEY PLAN - BLDG 1
SHEET TITLE
ENLARGED ELECTRICAL
FLOOR PLANS
ISSUE
CONSTRUCTION
DOCUMENTS
AUGUST 13, 2026
DRAWN
JD
CHK'D
PP
PROJECT NO.
26020
SHEET NO.
E-102
© 2025 JAED CORPORATION
NOTES :
1. CONDUIT AND GROUNDING MUST BE COORDINATED WITH PAD INSTALLATION.
2. PROVIDE COPPER CLAD STEEL GROUND ROD AND CAD WELD TO REBAR AND
CONNECT TO XFMR FRAME.
3. CONTRACTOR TO COORDINATE LOCATION OF TRANSFORMER, PLACEMENT OF
TRANSFORMER, POSITION OF TRANSFORMER AND ACCESSIBILITY TO
TRANSFORMER WITH LOCATION OF GENERATOR, FENCE, OR ANY OBJECT WITHIN
THE REQUIRED CLEARANCE DISTANCE BETWEEN THE TRANSFORMER AND SAID
OBJECT. COORDINATE WITH UTILITY PROVIDER.
4. CONTRACTOR TO COORDINATE LOCATION AND POSITION OF TRANSFORMER PAD
WITH PRIMARY AND SECONDARY WIRING.
5. COORDINATE REQUIRED "PAD WIDTH" AND "PAD LENGTH" WITH UTILITY PROVIDER.
"PAD WIDTH"
(7)#5 REBAR -
EVENLY SPACED
GRADE
PRIMARY
SECONDARY
(9)#5 REBAR -
EVENLY SPACED
CONTRACTOR TO FEILD LOCATE 4"
PVC SLEAVES FOR CABLE
PENETRATIONS WITHIN THIS AREA
TRANSFORMER DOORS AT THIS END OF PAD.
CONTRACTOR TO COORDINATE LOCATION OF
DOORS WITH REQUIRED CLEARANCE DISTANCE.
COORDINATE WITH UTILITY PROVIDER.
3"
XFMR SLAB
GRADE
COMPACT SUBGRADE TO
95% MAXIMUM DENSITY
PER ASTM D-1557-70
GEOTEXTILE FILTER
FABRIC
CR-467 COMPACTED TO
95% MAXIMUM DENSITY
PER ASTM D-1557-70
1 TRANSFORMER PAD DETAIL
E-501 SCALE: NO SCALE
2 TRANSFORMER PAD CONTAINMENT AREA DETAIL
E-501 SCALE: NO SCALE
3 TRANSFORMER PAD GROUNDING AND BONDING DETAIL
E-501 SCALE: NO SCALE
4 BOLLARD DETAIL
E-501 SCALE: NO SCALE
EXISTING ASPHALT SIDEWALK
NEW ASPHALT PAVING
TOP COURSE - 1 1/2" HOT MIX
ASPHALT SURFACE COURSE (TYPE C)
TACK COAT
BASE COURSE - 2 1/2" HOT MIX
ASPHALT BASE COURSE (TYPE B)
4" GRADED AGGREGATE SUBBASE (GABC)
WOVEN GEOTEXTILE FABRIC
OVER COMPACT EXISTING SOIL
5 TYPICAL NEW ASPHALT PAVING SECTION
E-501 SCALE: 3" = 1'-0"
EXIST. GRADE
WIDTH VARIES
4" THICK P.C.C. SIDEWALK
4000 PSI @ 28 DAYS
W/ 6 x 6 - W1.4 x W1.4 WWF
CONSTRUCT 1/2" DEEP
TOOLED JOINTS @ 5' O.C.
& 1/2" WIDE EXPANSION
JOINTS @ 20' O.C.
X
X
X
X
X
X
X
X
X
COMPACTED
4" RIDOT CR-1 TYPE A
COMPACTED SUBGRADE
(PROOF ROLL)
6 TYPICAL NEW CONCRETE SIDEWALK SECTION
E-501 SCALE: 1/4" = 1'-0"
EXIST. GRADE
12" EXP. MATERIAL
NEW CURB
EXIST. ASPHALT PAVING
PATCH AT NEW CURB
MATCH EXIST.
MATCH EXIST.
SLOPE
X
X
X
X
7 TYPICAL NEW CONCRETE CURB SECTION
E-501 SCALE: 1/4" = 1'-0"
EXIST. GRADE
4" THICK P.C.C. SIDEWALK
3500 PSI @ 28 DAYS
W/ 6 x 6 - W1.4 x W1.4 WWF
CONSTRUCT 1/2" DEEP
TOOLED JOINTS @ 5' O.C.
& 1/2" WIDE EXPANSION
JOINTS @ 20' O.C.
4" RIDOT CR-1 TYPE A
COMPACTED
COMPACTED SUBGRADE
(PROOF ROLL OR TAMP)
NOTE:
THIS DETAIL IS TYPICAL FOR UNDERGROUND CONDUIT INSTALLATIONS
BELOW DRIVEWAYS, PARKING LOTS, ETC.
NON-BIODEGRADABLE WARNING TAPE - 4" WIDE, ENTIRE LENGTH
CONCRETE/ASPHALT: MATCH SURROUNDING
ELEVATION AND MATERIAL.
NOTE: SPACERS ARE
REQUIRED EVERY 4 FEET.
1'-0"
GRADE
NOTE: INSTALL #4 REINFORCEMENT
BARS THROUGH THE OUTSIDE EDGES OF
THE DUCT SPACER TO PROVIDE
TEMPORARY ANCHORING TO PREVENT
THE CONDUIT FROM FLOATING OR
CHANGING ALIGNMENT WHILE POURING
ENVELOPE.
SELECT BACKFILL
2500# CONCRETE
GRAVEL BASE
2'-6"
5 1/4"
3"
3"
3"
5 1/4"
C
C
C
C
C
C
C
C
3"
3"
1'-6"
3"
6" MIN
7 1/2"
7 1/2"
7 1/2"
3'-2"
7 1/2"
7 1/2"
TYPE
C
DESCRIPTION
4" PVC SCH. 40 CONDUIT
8 CONCRETE DUCT BANK DETAIL - 1
E-501 SCALE: NO SCALE
NOTE:
THIS DETAIL IS TYPICAL FOR UNDERGROUND CONDUIT INSTALLATIONS
BELOW DRIVEWAYS, PARKING LOTS, ETC.
NON-BIODEGRADABLE WARNING TAPE - 4" WIDE, ENTIRE LENGTH
CONCRETE/ASPHALT: MATCH SURROUNDING
ELEVATION AND MATERIAL.
NOTE: SPACERS ARE
REQUIRED EVERY 4 FEET.
GRADE
1'-0"
NOTE: INSTALL #4 REINFORCEMENT
BARS THROUGH THE OUTSIDE EDGES OF
THE DUCT SPACER TO PROVIDE
TEMPORARY ANCHORING TO PREVENT
THE CONDUIT FROM FLOATING OR
CHANGING ALIGNMENT WHILE POURING
ENVELOPE.
SELECT BACKFILL
2500# CONCRETE
GRAVEL BASE
2'-6"
3"
3"
3"
C
C
3"
1'-0"
3"
6" MIN
1'-6"
TYPE
C
DESCRIPTION
4" PVC SCH. 40 CONDUIT
9 CONCRETE DUCT BANK DETAIL - 2
E-501 SCALE: NO SCALE
NOTE:
THIS DETAIL IS TYPICAL FOR UNDERGROUND CONDUIT INSTALLATIONS IN
GRASSY AREAS OR BELOW SIDEWALKS.
NON-BIODEGRADABLE WARNING TAPE
- 4" WIDE, ENTIRE LENGTH
CONCRETE/ASPHALT (WHERE
PRESENT): MATCH
SURROUNDING ELEVATION
AND MATERIAL.
GRADE
1'-0"
SIZES AND
QUANTITIES OF
2'-6"
CONDUITS VARY -
SEE SITE PLANS.
SELECT BACKFILL
GRAVEL BASE
6" MIN
1'-0" MIN.
10 NON-CONCRETE DUCT BANK DETAIL
E-501 SCALE: NO SCALE
OUTDOORS
METAL SLEEVE 1" BIGGER IN
DIAMETER THAN CONDUIT SIZE
CONDUIT CLAMPS @ 3 FT ON
WALL
INDOORS
FLOOR ABOVE
SUSPENDED
CEILING
EXISTING CONCRETE WALL OR FLOOR
METAL SLEEVE 1" BIGGER IN DIAMETER
THAN CONDUIT SIZE
RIGID METAL CONDUIT ALONG
WALL UP TO CEILING HEIGHT
CONDUIT
PVC TO RIGID METAL CONDUIT
TRANSITION FITTING
4" HIGH CONCRETE PAD
APPROPRIATELY SEALED FOR
LOCATION AND APPLICATION.
WHERE PENETRATING A 1-HOUR
RATED WALL, PROVIDE 1-HOUR
RATED UL LISTED SEALANT.
PVC CONDUIT
UNDER SLAB
GRADE
6"
PVC CONDUIT UG
11 TYPICAL PENETRATION IN WALL OR FLOOR
E-501 SCALE: NO SCALE
12 TYPICAL CONDUIT INSTALLATION DETAIL
E-501 SCALE: NO SCALE
Website: www.StudioJAED.com
Email: info@StudioJAED.com
ARCHITECT
STUDIOJAED
■ 2500 WRANGLE HILL ROAD, STE 110
BEAR, DELAWARE 19701
P: (302) 832-1652
■ 306 E. CAMDEN-WYOMING AVENUE
CAMDEN, DELAWARE 19934
P: (302) 832-1652
■ 42 WEYBOSSETT STREET, STE 403
PROVIDENCE, RHODE ISLAND 02903
P: (401) 648-0884
THIS DRAWING IS THE PROPERTY OF STUDIOJAED
AND IS PREPARED FOR THE EXCLUSIVE USE OF
ITS CLIENTS AT THE LOCATION INDICATED. NO
OTHER USE IS AUTHORIZED OR INTENDED.
ARCHITECT / ENGINEER SEAL
REVISIONS
MARK
-
DESCRIPTION
-
DATE
-
SHEET TITLE
ELECTRICAL DETAILS
ISSUE
CONSTRUCTION
DOCUMENTS
AUGUST 13, 2026
DRAWN
JD
CHK'D
PP
PROJECT NO.
26020
SHEET NO.
E-501
© 2025 JAED CORPORATION
This page summarizes the opportunity, including an overview and a preview of the attached documents.
Get Government Bids Like This by Email
Receive daily bid alerts that match your keywords, business categories, and target regions.
See Also
Info Opening Time Solicitation Number Status Bid Title Posting Group Posting Entity Contact
State Government of Rhode Island
Due by 12/04/2026
Info Opening Time Solicitation Number Status Bid Title Posting Group Posting Entity Contact
State Government of Rhode Island
Due by 11/12/2026
27-001 New City Hall Parking Lot Stormwater Design Addendum 1
City of Pawtucket
Due by 11/12/2026
Info Opening Time Solicitation Number Status Bid Title Posting Group Posting Entity Contact
State Government of Rhode Island
Due by 11/12/2026
* Disclaimer: This website provides information about bids, requests for proposals (RFPs), or requests for qualifications (RFQs) for convenience only and does not serve as an official public notice. Individuals who wish to respond to or inquire about bids, RFPs, or RFQs should contact the relevant government department directly.