| Solicitation Type | Bid |
|---|---|
| Solicitation Number | 6501 |
| Description | Chiller Pump Removal and Installation - Kent County Correctional Facility |
| Date of Issuance | 4/9/2026 |
| Inquiries Deadline Date & Time (local) | 4/21/2026, 2 PM |
| Due Date & Time (local) | 4/23/2026, 2 PM |
| Pre-Submission Conference | Yes: Non-Mandatory On-Site (attendance recommended) |
| Conference Date & Time (local) | 4/16/2026 9:00 AM |
| Buyer Name | LaBudde |
| Page | 1 | of | 3 |
|---|
PURCHASING DIVISION
Joni Laming, Manager
(616) 632-7720
purchasing@kentcountymi.gov
SOLICITATION
Solicitation Type Bid
Solicitation Number 6501
Description Chiller Pump Removal and Installation - Kent County
Correctional Facility
Date of Issuance 4/9/2026
Inquiries Deadline Date & Time (local) 4/21/2026, 2 PM
Due Date & Time (local) 4/23/2026, 2 PM
Pre-Submission Conference Yes: Non-Mandatory On-Site (attendance recommended)
Conference Date & Time (local) 4/16/2026 9:00 AM
Buyer Name LaBudde
INTRODUCTION
The Kent County Purchasing Division is soliciting bids for the removal and installation of four (4) Chiller
Pumps at the Kent County Correctional Facility located at 703 Ball N.E. Grand Rapids, MI 49503.
BID OPENING
The sealed submissions will be publicly opened and read aloud by the Kent County Purchasing Division.
Kent County Purchasing Division will conduct public openings via teleconference. Click here to join the
public opening.
SCOPE
* Drain and collect glycol from the current system (roughly 2,640 gallons)
* Re-fill system with existing glycol and add 360 gallons of new 100% dowtherm SR-1 glycol that is
purchased by Kent County from Broadmoor Products
* Disconnect, remove, and dispose of four (4) existing pumps
* Install four (4) new pumps provided by Kent County, cut sheets (Exhibit A)
* Factory start-up included with our pump purchase
* New isolation valves and piping for each drop
* Pre-fabricated piping drops with suction diffusers, flex connectors, and valves provided with the
new pumps
* New pipe insulation
* Electrical work and Can-Bus Cable wiring of all four 4 motors.
Page 1 of 3
| Conference Date | 4/16/2026 |
|---|---|
| Conference Time (local) | 09:00 AM |
| Location | 703 Ball N.E. Grand Rapids, MI 49503 (Map attached) |
| Page | 2 | of | 3 |
|---|
* Labor during normal hours
Kent County will award and contract for the goods and services in this Solicitation in an efficient and
timely manner. In no event will notification of award be more than 45 days from the date of submission.
The Kent County Standard Submission Terms posted on the Bid Opportunities page of the Kent County
Purchasing Division website are incorporated by reference and shall be deemed to have the same force
and effect as if fully set forth herein.
INQUIRIES
Any and all communication regarding this Solicitation shall be on the Kent County Purchasing Division
Inquiry Blog via the Bid Opportunities page or during pre-proposal meetings. Kent County reserves the
right to determine the response format or not respond, at its sole discretion.
PRE-SUBMISSION ON-SITE CONFERENCE
Conference Date 4/16/2026
Conference Time (local) 09:00 AM
Location 703 Ball N.E. Grand Rapids, MI 49503 (Map attached)
A pre-submission conference is scheduled for this Solicitation. Attendee should arrive a minimum of 5
minutes before the conference scheduled date and time to sign-in. Attendee will not be allowed to sign
in after the conference has commenced at mandatory meetings and is disqualified from participating
in this Solicitation.
The conference provides equal opportunity to seek clarifications and inspect the location (if applicable).
Attendee shall have fully reviewed all Solicitation documents and correspondence prior to the
conference. Attendee is responsible for taking meeting notes and shall be an employee or authorized
reseller of the Respondent with requisite knowledge, skill, and abilities to participate.
PERFORMANCE AND PAYMENT BOND
Each contract over $50,000 must be accompanied by a Performance Bond and a Payment Bond, each
payable to the Owner (County of Kent) and each in the amount of 100% of the contract price with a
corporate surety approved by the funding agency, for the faithful performance of the contract.
INVITATION FOR BID/RFQ SUBMISSION
Complete submissions must be received in the Kent County Purchasing Division on or before the due
date/time specified by the designated clock (local time). Late, faxed, or emailed responses will NOT be
considered.
Page 2 of 3
| Page | 3 | of | 3 |
|---|
Submissions may be submitted electronically on the Bid Opportunities page of the Kent County
Purchasing Division's website. Respondent must include a complete submission as 1 non-password
protected PDF document.
Respondent shall submit the Submission Form ("Bid Form" "Response Form") posted on the Bid
Opportunities page of the Kent County Purchasing Division's website. Click the Submit Online icon to
submit electronically or to print the Submission Form. Respondent must submit the Bid Bond with
Submission Form if applicable.
The time required to upload a submission may vary. Respondent assumes all risks associated with
electronic submission, including all technological difficulties, and deems the County and its service
provider harmless and without fault. Successful electronic submissions are confirmed via Respondent's
email. Respondent shall view the link in the confirmation email to determine accuracy prior to due
date/time.
Submissions that deviate from the Solicitation specifications will only be considered if the deviations are
clearly detailed and noted within the submission. In case of a dispute regarding the true intent and
meaning of the specifications, the County's interpretation will prevail. When a Solicitation states no
alternates, no deviations are permitted.
Kent County is not liable for cost incurred prior to award. A submission shall constitute an irrevocable
offer for a period of 45 days from the due date/time. In the event the notification of award is not made
within 45 days from the due date/time, the Respondent may withdraw or provide a written extension of
their submission.
Submissions may only be withdrawn by written request if the request is received before the due
date/time. Withdrawals after opening shall be subject to Kent County Fiscal Policy - Centralized
Purchasing 5(i)(2).
NO BID
Please provide feedback if you are electing not to participate in this Solicitation.
Page 3 of 3
EXHIBIT A
Submittal Ref. #: SQGMR001820_2
Design Envelope Split-Coupled Vertical In-Line Pump with Parallel Sensorless Controller
Model: Series Design Envelope Sensorless 4300 2507-015.0 with Suction Guide , Services
Project name: 48994 - Kent County Sherriff's Representative:
Office Chilled Wate
Location: Phone number:
Date submitted: 10/24/2025 12:28 PM e-mail:
Engineer: Submitted by: Kuzma, Thaddeus
Application design data
Tag number: CWP-1, 2, 3, 4 Piping configuration: P arallel + Standby
Service: C hilled water Suction pressure: 0 ft
Equipment Location: Fluid: Non-Potable Fluid - Water
Qty: 4 Fluid operating temp.: 60 degreesF
Total system flow: 900 USgpm Duty flow per pump: 300 USgpm
System head: 130 ft Viscosity: 31 SSU
Environment: Indoors Specific gravity: 1.0000
Total dissolved solids: 3000 ppm Safety factor % flow: 0 %
Efficiency at Design: 75.25 % Safety factor % head: 0 %
NPSHR: 15.51 ft Total Absorbed Power: 39.27 hp
Min. maintained 52 ft Impeller diameter: 7.67 in
pressure*:
PEIvl: 0.41 ERvl: 59
CEI: Not applicable ERCEI: Not applicable
Standby qty: 1 Pump/motor run qty: 3
Outlet velocity: 20.1 ft/s Load Profile Location: NA
Climate Zone Type: NA Building Type: NA
Time Period: 8760 (1 Year)
Redundancy %: N/A
Ambient Temperature 14 degreesF to 104 degreesF
Range:
*If minimum maintained system pressure is not known, default is 40% of design head.
Materials of construction
Construction: Stainless Steel Fitted Impeller: 316 Stainless Steel
Rating: ANSI-125 Pump shaft: 316 Stainless Steel
Connections: ANSI-125 Flanges Inlet: 2.5in, Flush line: Braided Stainless Steel
Outlet: 2.5in
Casing (volute): Cast iron, e-coated Casing o-ring: Confined Non-Asbestos Fiber
Stub Shaft: N/A
Mechanical seal data
Seal type: Outside Balanced Rotating face: Sintered Silicon Carbide
Manufacturer code: SSC-SSC G30P Stationary seat: Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel Maximum total dissolved 4000 PPM
solids (TDS)****:
Electrical data
Supplier: A r m strong Insulation class: Class F Insulation
Size: 15 hp Motor type: Permanent Magnet
Frame size: 132 Efficiency: IE5
Enclosure: TEFC Power supply: 460/3/60
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. #SQGMR001820_2 Page 1 of
5
| Series 4300 DEPM IVS Sensorless 2.5x2.5x7.5 @ 2832 rpm 250 *PT-783-0-0 ANSI/HI 14.6 3300 rpm 59 64 68 71 74 200 76 77 78 78 2832 rpm 77 150 76 )tf( 74 71 daeH 68 64 100 50 1590 rpm 15 hp System 900 rpm NPSHr 0 50 100 150 200 250 300 350 400 450 Water, spgr=1.0000 Flow (USgpm) 3.3.298-df76675d / 55906 | --Control Data- 1. Hmax @ 47.2 Hz: NPSHR: 15.51 ft Intersection Pt: 300 usgpm @ 130 ft bhp=13.09 hp, eff=75.25 %%, %bepq=119 %% 2. Control (QPC) @ 43.06 Hz: NPSHR: 11.9 ft Intersection Pt: 262.5 USgpm @ 111.72 ft bhp=9.71 hp, eff=76.3%, %bepq=113.86% 3. Control (QPC) @ 38.92 Hz: NPSHR: 8.6 ft Intersection Pt: 222 USgpm @ 94.71 ft bhp=6.88 hp, eff=77.22%, %bepq=106.7% 4. Control (QPC) @ 34.78 Hz: NPSHR: 5.65 ft Intersection Pt: 177 USgpm @ 79.15 ft bhp=4.57 hp, eff=77.38%, %bepq=95.38% 5. Control (QPC) @ 30.64 Hz: NPSHR: 3.11 ft Intersection Pt: 123 USgpm @ 65.11 ft bhp=2.74 hp, eff=73.83%, %bepq=75.05% 6. Hmin: 52 ft 26.5 Hz: NPSHR: 0.54 ft Intersection Pt: 0 USgpm @ 52 ft (Head Q Min) Setting= 40% Hmax Ambient Temperature Derating Factor: 1 |
|---|
| 3300 rp | m | 59 | 64 68 | 71 74 76 | *PT-7 ANSI/ | 83-0-0 HI 14.6 | ||
|---|---|---|---|---|---|---|---|---|
| 2832 rp | m | 77 78 78 | 77 76 | |||||
| 74 7 | 1 68 64 | |||||||
| 1590 rp 900 rpm | m | System | 15 hp |
| Flow | Head |
|---|---|
| 300 USgpm | 154.33 ft |
| 300 USgpm | 130 ft |
Operating speed @ 100% 2832 rpm Operating speed @ 50% 1949 rpm
flow: flow***:
***Based on minimum pressure setting of 40% of design head.
****Note: Please ensure proper seal is selected by inputting Total Dissolved Solids (TDS) in PPM in ADEPT if water quality is
poor at site. Also select Flush Line Filter or Cyclone Separator if there are other contaminants in the fluid
DEPM controller data
Sensorless control: Yes - Quadratic press control Communication port: RS 485
Communication protocol (*): BACnet MS/TP Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12/IP55 Analog outputs: 1 (current or voltage)
Fused disconnect switch: None Digital inputs: 2 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
Absorbed Power/BHP at 50% 7.2 hp EMI/RFI control: Integrated filter to meet EN61800-
load/flow and 55% of design 3
head:
Meets ASHRAE 90.1: Yes Harmonic suppression: Integrated DC link reactor**
(*): If Default - Field reconfigurable is selected, Default from factory will be BACnet MS/TP and can be reconfigured in the field.
** The IVS control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This
does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If
supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system
harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
Performance curve
Series 4300
DEPM IVS Sensorless
2.5x2.5x7.5 @ 2832 rpm
Water, spgr=1.0000 Flow (USgpm)
3.3.298-df76675d / 55906
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. #SQGMR001820_2 Page 2 of
5
)tf(
daeH
--Control Data-
1. Hmax @ 47.2 Hz:
NPSHR: 15.51 ft
Intersection Pt: 300 usgpm @ 130
ft
250
*PT-783-0-0 bhp=13.09 hp, eff=75.25 %%,
ANSI/HI 14.6 %bepq=119 %%
3300 rpm 59 64 68 71 2. Control (QPC) @ 43.06 Hz:
NPSHR: 11.9 ft
74
Intersection Pt: 262.5 USgpm @
200 76 111.72 ft
77 bhp=9.71 hp, eff=76.3%,
%bepq=113.86%
78
78
3. Control (QPC) @ 38.92 Hz:
2832 rpm 77 NPSHR: 8.6 ft
150 76 Intersection Pt: 222 USgpm @
94.71 ft
74 bhp=6.88 hp, eff=77.22%,
71 %bepq=106.7%
68
4. Control (QPC) @ 34.78 Hz:
64 NPSHR: 5.65 ft
100
Intersection Pt: 177 USgpm @
79.15 ft
bhp=4.57 hp, eff=77.38%,
%bepq=95.38%
5. Control (QPC) @ 30.64 Hz:
50 1590 rpm 15 hp NPSHR: 3.11 ft
Intersection Pt: 123 USgpm @
65.11 ft
System
bhp=2.74 hp, eff=73.83%,
%bepq=75.05%
900 rpm
6. Hmin: 52 ft 26.5 Hz:
NPSHr
0 50 100 150 200 250 300 350 400 450 NPSHR: 0.54 ft
Intersection Pt: 0 USgpm @ 52 ft
(Head Q Min) Setting= 40% Hmax
Ambient Temperature Derating
Factor: 1
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 300 USgpm 154.33 ft 76.77%
Design point 300 USgpm 130 ft 75.25 %
| 150 USgpm | 71.5 ft |
|---|
| Parallel Pump Curve-Series 4300 DEPM IVS Sensorless 2.5x2.5x7.5 @ 2832 rpm 180 *PT-783-0-0 30 hp 45 hp 160222888333222 rrrpppmmm 140222666444777 rrrpppmmm 120222444666222 rrrpppmmm 222222777777 rrrpppmmm )tf( 100 115 hp 2 3 daeH 222000999333 rrrpppmmm 80 1 2 3 111999000888 rrrpppmmm 1 2 3 60 1 2 3 1 2 3 40 1 2 3 System 20 0 200 400 600 800 1000 1200 Water, spgr=1.0000 Flow (USgpm) 3.3.298-df76675d / 55906 | ----Admin Data-- Tag Num: CWP-1, 2, 3, 4 Service: Chilled water Location: ----Motor Data---- Motor Size: 15 hp ----System Design Data--- Piping: Parallel + Standby Run Qty: 3 Fluid: Non-Potable Fluid Sp.Gr: 1.0000 ,Vis= 31 SSU Suction: 0 ft Total Design Flow= 900 USgpm Total Design Head= 130 ft ---Performance Data--- NPSHR : 15.51 ft Flow: 900 USgpm Head: 130 ft Eff: 75.25% ,BEP: 77.55% %BEP (Flow): 119% BHP = 39.27 hp BHP/Pump= 13.09 hp Total System Flow = 900 USgpm |
|---|
| 222888333222 rrrpppmmm | 30 | hp | *P 45 hp | T-783-0-0 | |
|---|---|---|---|---|---|
| 222666444777 rrrpppmmm 222444666222 rrrpppmmm | |||||
| 222222777777 rrrpppmmm | |||||
| 222000999333 rrrpppmmm | 11 1 | 5 hp | 2 2 | 3 3 | |
| 111999000888 rrrpppmmm | 1 | 2 | 3 | ||
| 1 1 | 2 | 2 | 3 3 | ||
| 1 | 2 System | 3 | |||
50% average flow (with default load profile) 150 USgpm 71.5 ft 76.4 %
Motor Capability @ Rated Speed 14.39 hp
Parallel Pump Curve-Series 4300
DEPM IVS Sensorless
2.5x2.5x7.5 @ 2832 rpm
Water, spgr=1.0000 Flow (USgpm)
3.3.298-df76675d / 55906
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. #SQGMR001820_2 Page 3 of
5
)tf(
daeH
----Admin Data--
Tag Num: CWP-1, 2, 3, 4
Service: Chilled water
Location:
180 ----Motor Data----
*PT-783-0-0 Motor Size: 15 hp
30 hp 45 hp
----System Design Data---
160222888333222 rrrpppmmm
Piping: Parallel + Standby
Run Qty: 3
Fluid: Non-Potable Fluid
140222666444777 rrrpppmmm Sp.Gr: 1.0000 ,Vis= 31 SSU
Suction: 0 ft
Total Design Flow= 900 USgpm
Total Design Head= 130 ft
120222444666222 rrrpppmmm
---Performance Data---
NPSHR : 15.51 ft
100 222222777777 rrrpppmmm Flow: 900 USgpm
115 hp 2 3 Head: 130 ft
Eff: 75.25% ,BEP: 77.55%
80 222000999333 rrrpppmmm 1 2 3 % BH BE P P = ( F 3 l 9 o . w 2 ) 7 : 1 h 1 p 9 %
111999000888 rrrpppmmm 1 2 3 BHP/Pump= 13.09 hp
Total System Flow = 900 USgpm
60 1 2 3
1 2 3
40 1 2 3
System
20
0 200 400 600 800 1000 1200
Operating limits (fluid temperature - pressure)
Maximum pressure: 175 psi
Maximum fluid temperature: 250 degreesF
All Pump casings are hydrostatically tested to requirements of ANSI/HI 14.6 standard.
| Size | Rating | OD | Bolt quantity* | BCD |
|---|---|---|---|---|
| 2.5 | ANSI-125 | 7.00 | 4 | 5.50 |
Options
Sensorless Bundle: Yes DEPC Parallel Sensorless: Yes*
Energy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No
*This feature is embedded into the controls of up to 4 pumps.
Cooling Heating
Q1: N/A Q2: N/A
H1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A
Optional Services
On-Site Pump Commissioning: Cost not Included Extended Warranty: No
Pump Manager: Yes,Standard (1 Include Spare Parts Qty: 0
Year Pump Manager
Professional
Dimensional data (not for construction)
Side view Top view
Weight: 398.05 lb [180.55 kg], Units of measure: inches [millimeters]
* R = minimum lifting clearance required above motor
* Coupling guard and flush line (not shown) are supplied
* Tolerance of 0.125 inch ( 3 mm) should be used
* For certified dimensions, please contact your Armstrong representative
* Pump equipped with casing drain plug and 14 inch NPT suction and
discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 2.5 ANSI-125 7.00 4 5.50 0.625
Outlet 2.5 ANSI-125 7.00 4 5.50 0.625
*Equally spaced straddling centreline
Flow Readout Accuracy
The Design Envelope model selected will provide flow reading on the pump touchscreen & digitally for the BMS. The flow
readout will be factory tested to ensure 5% accuracy.
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. #SQGMR001820_2 Page 4 of
5
Special instructions
Reference Motor Specification AES 05007.
UL STD 778 & CSA STD C22.2 no.108 certified
Impeller Balancing: Standard (Grade G6.3)
Pump Primer: Armstrong Standard Primer
Note:
Selected options
Testing: No Test Certification Required
Seal Environment Accessories: None
Pre-Wired Control Bridge: No
Sensorless Bundle: Sensorless control
Constant flow control
Constant pressure control
Flow readout
Parallel Sensorless : Yes
Design Envelope pumps offer industry-leading efficiency and performance management capabilities for significantly reduced
energy consumption. Armstrong has undertaken a multi-year project to transition our pump offering to an integrated design
that use Design Envelope Permanent Magnet technology for even greater operating cost savings. In the sizes currently
equipped with Design Envelope Permanent Magnet motors, the pumps are also more compact and lighter than our standard
Design Envelope pumps.
Please note that depending on the pump sizes, your shipment may include a combination of:
* Design Envelope Permanent Magnet pumps
* Design Envelope Permanent Magnet pumps with IVS controls
* Design Envelope Pumps with Premium efficiency induction motors and IVS controls
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. #SQGMR001820_2 Page 5 of
5
| Qty | Model | Pipe Conn.size | Pump Conn.size | Design flowrate | Pressure Drop* |
|---|
| Cast Iron | Cover gasket: |
|---|---|
| Cast Iron | Strainer: |
Submittal Ref. #: SQGMR001820_2
Suction guide
Model: SG-425
Project name: Representative: Thaddeus Kuzma
Location: Phone number: 6162880822
Date submitted: 10/24/2025 12:28 PM e-mail: kuzmat@hedrickassoc.com
Engineer: Submitted by: Kuzma, Thaddeus
Application design data
Tag Qty Model Pipe Pump Design Pressure Associated pump
Conn.size Conn.size flowrate Drop*
CWP-1, 4 SG-425 4 in 2.5 in 300 1.84 ft Design Envelope Sensorless
2, 3, 4 USgpm 4300 2507-015.0
*at design flow
Materials of construction
SG-425
Body: Cast Iron Cover gasket: Synthetic fiber
Guide vanes: Cast Iron Strainer: Stainless Steel,0.188"(5mm)Perf..
Cover plate: Cast Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours of pump operation
Operating limits (temperature - pressure)
SG-425-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 300 F
Units are hydrostatically tested to 150% of
maximum working pressure
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. # SQGMR001820_2 Page 1 of 2
Dimensional data (not for construction)
SG-425 Weight: 58.94 lb [26.73 kg]
Side view Top view
Not to scale
Units of measure: inches [millimeters]
Tolerance of +/- 0.125 inch (+/- 3 mm) should be used
For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 10/24/2025 12:28:51 PM, Ref. # SQGMR001820_2 Page 2 of 2
With Free Trial, you can:
You will have a full access to bids, website, and receive daily bid report via email and web.
Project Bid/Proposal Bid Opening Date & Time bid Tab 2026-28 Farm Land Lease
City of Greenville
Bid Due: 12/30/2026
Description: Tech Center Renovation - Door Access Readers Department: Dickinson-Iron ISD Buyer: Jessica
State of Michigan
Bid Due: 7/27/2026
Description: 751/26332.MDL; DeTour State Harbor - Fuel Tanks Department: Technology, Management and Budget
State of Michigan
Bid Due: 7/30/2026