Bernville Emergency Generator
| Agency: | DEPT OF DEFENSE |
|---|---|
| State: | Pennsylvania |
| Type of Government: | Federal |
| FSC Category: |
|
| NAICS Category: |
|
| Posted Date: | May 8, 2025 |
| Due Date: | May 20, 2025 |
| Solicitation No: | W912BU25R0032 |
| Original Source: | Please Login to View Page |
| Contact information: | Please Login to View Page |
| Bid Documents: | Please Login to View Page |
Description
APEX Accelerators are an official government contracting resource for small businesses. Find your local APEX Accelerator (opens in new window) for free government expertise related to contract opportunities.
APEX Accelerators are funded in part through a cooperative agreement with the Department of Defense.
The APEX Accelerators program was formerly known as the Procurement Technical Assistance Program (opens in new window) (PTAP).
- Contract Opportunity Type: Sources Sought (Original)
- Original Published Date: May 08, 2025 09:45 am EDT
- Original Response Date: May 20, 2025 04:00 pm EDT
- Inactive Policy: 15 days after response date
- Original Inactive Date: Jun 04, 2025
-
Initiative:
- None
- Original Set Aside:
- Product Service Code: 6115 - GENERATORS AND GENERATOR SETS, ELECTRICAL
-
NAICS Code:
- 236220 - Commercial and Institutional Building Construction
-
Place of Performance:
Leesport , PA 19533USA
** This is not a solicitation. The solicitation is expected to be published in June 2025. This notice is for market research to determine interested and capable vendors for a Emergency Generator for the Dam at Blue Marsh Lake. USACE welcomes interested vendors to respond with capabilities and size standards**
Here is the summarized Statement of Work. The full statement of work will be posted with the solicitation. This is a design/build construction project.
STATEMENT OF WORK
BLUE MARSH LAKE AND DAM, LEESPORT, PA
INSTALL EMERGENCY GENERATOR FOR
BERNVILLE PROTECTIVE WORKS PUMP STATION
Background:
The town of Bernville, Pennsylvania is protected by a levee and pump station that were built in conjunction with the Blue Marsh project. The Bernville Protective Works currently does not have an emergency backup generator in case of utility power failure. If a power failure were to occur during a significant event, the town of Bernville would be subject to consequential flooding. With an emergency backup generator, this flooding could be prevented. Per a site visit report and recommendations from a multi-agency Emergency Tabletop Exercise conducted in 2018, an emergency generator needs to be designed, purchased and installed at the Bernville Pump Station.
Scope:
The contractor shall execute a Design/Build contract to install an emergency generator at the Bernville, PA Protective Works Pump Station. The contractor shall design, install, and commission an emergency backup diesel generator system for the Bernville Pump Station. Design shall include a generator sized to power the entire facility under worst case conditions which includes six (6) 250 HP storm water pumps starting sequentially along with other facility general and ancillary loads. The generator system shall support 72 hours of continuous operation at 100% load without refueling. Preliminary analysis with the Cummins Power Suite generator sizing software estimates the generator size to be 1500kW.
The generator shall be located across the existing parking lot, southeast from the building, closest to the levee in the grass area. A concrete equipment pad will be installed, and the generator will be surrounded by bollards. An electrical underground ductbank will be installed approximately 125 feet long with approximately 50 feet under the existing asphalt from the generator to the pump station. Ductbank shall be concrete encased, schedule 40 PVC, as the entire run will experience traffic/vehicle loads. The Motor Control Center {MCC) shall be replaced since it has reached end of life. The new MCC will also have an Automatic Throw Over {ATO) control system. This is basically an Automatic Transfer Switch System built into the MCC and controlled digitally. There will also be an option in the contract to replace the existing Westinghouse service transformer. Pavement and site work is included in the base work.
- 1650 ARCH STREET 7TH FLOOR
- PHILADELPHIA , PA 19103-0000
- USA
- Brian Cox
- brian.w.cox@usace.army.mil
- Phone Number 2156566897
- Cherita Williams
- cherita.l.williams@usace.army.mil
- Phone Number 2156566775
- May 08, 2025 09:45 am EDTSources Sought (Original)
See Also
RFI - EP - Failure of the Variable Frequency Drive (VFD) Serving Uhler
Pennsylvania State System of Higher Education
Due by 10/02/2026
Number Type Date Added Start Date Q&A Deadline Due Date Status Purchasing Group
Pennsylvania Turnpike Commission
Due by 10/14/2026
General Information Department for this solicitation: Procurement Date Prepared: 09/09/26 Types: RFA Advertisement
State Government of Pennsylvania
Due by 10/14/2026
Series Frequency Converters Item 26-00200-AJQL SEPTA will accept bids with the eProcurement system
Southeastern Pennsylvania Transportation Authority
Due by 10/08/2026