ROCK COUNTY
COURTHOUSE
ROCK COUNTY FACILITIES MGMT
COURTHOUSE PROBATE VAULT ALTERATION
ARCHITECT
Venture Architects
212 North 25th Street
Milwaukee, Wisconsin 53233
Phone: (414) 271-3359
Fax: (414) 271-0939
WISCONSIN MAP
ELECTRICAL
Harwood Engineering
255 North 21st Street
Milwaukee, Wisconsin 53233
Phone: (414) 475-5554
Fax: (414) 773-9299
MECHANICAL
Harwood Engineering
255 North 21st Street
Milwaukee, Wisconsin 53233
Phone: (414) 475-5554
Fax: (414) 773-9299
SITE MAP
PLUMBING / FIRE
PROTECTION
Harwood Engineering
255 North 21st Street
Milwaukee, Wisconsin 53233
Phone: (414) 475-5554
Fax: (414) 773-9299
Reference:
N
PLAN NORTH
KEY PLAN
ARCHITECTURAL
2 - G100 COVER SHEET / INDEX / LIFE SAFETY PLANS
2 - A100 DEMOLITION PLANS AND FLOOR PLANS
2 - A200 REFLECTED CEILING PLANS
2 - A300 INTERIOR ELEVATIONS
2 - A400 DETAILS
2 - A401 SCHEDULES
ELECTRICAL
2 - EL
2 - E100
2 - E200
2 - E201
ELECTRICAL SYMBOLS, ABBREVIATIONS AND NOTES
LIGHTING AND ELECTRICAL PLAN
LIGHTING AND POWER SCHEDULE AND DETAILS
3RD FLOOR DATA AND TELECOM
MECHANICAL
2 - ML
2 - M000
2 - M100
2 - M500
2 - M600
MECHANICAL SYMBOLS, ABBREVIATIONS AND NOTES
MECHANICAL SPECIFCATIONS
THIRD FLOOR MECHANICAL PLAN
MECHANICAL DETAILS
MECHANICAL SCHEDULES
FIRE PROTECTION
2 - F100 THIRD FLOOR FIRE PROTECTION PLAN
SECURITY ELECTRONICS
2 - SE001 CABLE AND SYMBOL
2 - SE100 FLOOR LAYOUTS
B
A3
1 THIRD FLOOR LIFE SAFETY PLAN / CODE
1/8" = 1'-0"
CODE REVIEW INFORMATION
CODE REVIEW INFORMATION
CONSTRUCTION DOCUMENTS WERE PREPARED UTILIZING THE 2015 INTERNATIONAL EXISTING
BUILDING CODE (IEBC) FOR BUILDING DESIGN.
CHAPTER 3 – USE & OCCUPANCY CLASSIFICATION
GROUP A3 – ASSEMBLY
GROUP B – BUSINESS Condition 4 - Free Movement Restricted. Remote Control Release Provided.
THIRD FLOOR
ASSEMBLY
NON-JURIED COURTROOM - 670.57 SF/40
BUSINESS
OFFICE - 151.04 SF / 100
17 OCCUPANTS CALCULATED - 19 ACTUAL
2 OCCUPANTS
TOTAL OCCUPANT LOAD=
19 OCCUPANTS
CHAPTER 5 – BUILDING HEIGHTS AND AREAS - UNCHANGING
TABLE 504.4 AND 506.2
GROUP B - BUSINESS
TYPE IIB
SPRINKLERED
SECTION 504 ALTERATION - LEVEL 2
LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR
ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSTION OF ANY
SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
CHAPTER 6 – TYPES OF CONSTRUCTION
CONSTRUCTION TYPE IS IIB.
CHAPTER 9 – FIRE PROTECTION SYSTEMS
BUILDING IS PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM
CHAPTER 10 – MEANS OF EGRESS
1004 - OCCUPANT LOAD:
THIRD FLOOR:
Office / Business:
Courtrooms:
Total:
151 / 100 = 2
671 / 40 = 17
19
1005.3.2 Egress Width - Other Components
19 occupants x 0.2 = 3.8" egress width required, 108" provided
Revisions:
No. Date:
Description:
Graphic
Scale
Project
Number
210105.00
Set
Type
BID SET
Date
Issued
1/05/2023
2 - G100 Sheet
Number
D1
EXISTING VAULT
D2
D5
D3
1' - 11"
1 THIRD FLOOR DEMOLITION PLAN
1/4" = 1'-0"
4 7/8"
3 5/8" METAL STUDS @ 16" O.C. - PROVIDE
CONTINUOUS DEEP LEG DEFLECTION TRACK
AT UNDERSIDE OF ROOF DECK (MIN. 1-1/2"
DEFLECTION DISTANCE), PROVIDE BRIDGING
SUPPORT W/ IN 12" OF TOP OF STUD, AND
FILL GAP WITH SEALANT AT BOTH SIDES OF
WALL.
SOUND BATT INSULATION FROM
CONCRETE FLOOR TO STRUCTURE
ABOVE
(1)LAYER 5/8" GYPSUM WALL BOARD
EACH SIDE - FINISH PER
SPECIFICATIONS.
A6.1 WIDTH MAY VARY DEPENDING ON FIELD
VERIFICATION
3 A6 : INTERIOR WALL
1 1/2" = 1'-0"
20
5' - 6"
4"
CR
20'-10"
AV AND I.T.
RACKING
20
DAR SYSTEM
OFFICE
284.1
A6
SHRED BIN
(NIC)
27" X 32"
FILE
CABINETS
(NIC)
9 SIM
2 - A400
9 SIM
2 - A400
3' - 7"
4
21 - A300
2' - 0"
4'-7"
1
3'-3"
6'-7"
3
21 - A300
2
21 - A300
12 - A300 NON-JURY
COURTROOM
284
8
9 2 - A300 7
6
9 SIM
2 - A400
2'-5"
A6.2
23
21 - A300
5
EQ
3' - 0"
EQ
CR
5 Sim
2 - A300
284A
26
2 THIRD FLOOR PLAN
1/4" = 1'-0"
4 1/4"
3 5/8" METAL STUDS @ 16" O.C. - PROVIDE
CONTINUOUS DEEP LEG DEFLECTION TRACK
AT UNDERSIDE OF ROOF DECK (MIN. 1-1/2"
DEFLECTION DISTANCE), PROVIDE BRIDGING
SUPPORT W/ IN 12" OF TOP OF STUD, AND
FILL GAP WITH SEALANT AT BOTH SIDES OF
WALL.
(1)LAYER 5/8" GYPSUM WALL BOARD
ONE SIDE - FINISH PER
SPECIFICATIONS.
4 A6.2 : INTERIOR WALL
1 1/2" = 1'-0"
FLOOR PLAN KEYNOTES THIRD FLOOR
KEY
20
23
26
D1
D2
D3
D5
KEYNOTE DESCRIPTION
INFILL SIDE OF FRAME FOR NEW SPECIFIED DOOR AND FRAME.
ALIGN NEW GYPSUM WALLBOARD INFILL FRAMING WITH
ADJACENT EXISTING WALLS FOR FLUSH FINISHES CONDITION.
FOR FINISHES ON COURTROOM SIDE, SEE ROOM FINISH
SCHEDULE. ON CORRIDOR SIDE, MATCH ADJACENT WALL
FINISHES.
IF FIRE SUPPRESSION IS BELOW NEW CEILING, BOX AROUND IT.
REMOVE EXISTING DOOR, FRAME, AND CONCRETE FRAME
SURROUND.
REMOVE EXISTING CEILING.
REMOVE EXISTING PORTION OF WALL FOR SCHEDULED DOOR.
CUT AND SALVAGE PORTION OF STONE WAINSCOT.
GENERAL PLAN NOTES
1. DIMENSIONS ARE TO FINISHED FACE OF WALL.
2. ALL WALLS TO UNDERSIDE OF STRUCTURE UNLESS OTHERWISE
INDICATED.
3. DOOR JAMBS TO BE 4" FROM ADJACENT WALLS UNLESS
OTHERWISE INDICATED.
4. FOR ANY WORK IN EXISTING BUILDING, PATCH ALL DISTURBED
WALLS, FLOORS AND CEILINGS TO MATCH SURROUNDING
MATERIALS AND FINISHES.
5. FURNITURE SHOWN IN PLAN NOT IN CONTRACT.
6. FIELD VERIFY DIMENSIONS OF EXISTING WALLS.
GENERAL DEMOLITION NOTES
EXISTING WALLS TO REMAIN
ITEMS FOR DEMOLITION
CONSTRUCTION LIMITS
1. GENERAL CONTRACTOR SHALL PROTECT AREAS ADJACENT TO PROJECT
CONSTRUCTION. ANY AND ALL DAMAGE IS THE RESPONSIBILITY OF THE
GENERAL CONTRACTOR AND SHALL BE REPAIRED OR REPLACED TO MATCH
EXISTING.
2. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE INTERIM STORAGE
OF ALL EQUIPMENT AND FIXTURES SUCH AS: TOILET ROOM ACCESSORIES,
CORNER GUARDS, BUMPER GUARDS, FIRE EXTINGUISHERS, AND FIRE
EXTINGUISHER CABINETS. SAVE FOR POSSIBLE REUSE/RELOCATION.
3. ADDITIONAL DEMOLITION, REMOVAL OR REFINISHING INFORMATION MAY
ALSO BE FOUND ON THE NEW CONSTRUCTION PLANS.
4. ALL EXISTING CONDITIONS SHALL BE REMOVED AS REQUIRED TO
ACCOMODATE PROPOSED CONSTRUCTION WHETHER OR NOT NOTED ON
DEMOLITION DRAWINGS.
5. FIELD VERIFY THAT PARTITIONS SCHEDULED FOR REMOVAL ARE NOT
STRUCTURAL AND CONTAIN NO LOAD BEARING ELEMENTS. IF ANY
CONFLICTS OCCUR, CONTACT THE ARCHITECT IMMEDIATELY.
6. SEE MECHANICAL, ELECTRICAL, PLUMBING & NEW CONSTRUCTION PLANS
FOR ADDITIONAL DEMOLITION, REMOVAL OR REFINISHING INFORMATION,
CUT OUT LOCATIONS, INFILL AND PATCHING OF FLOORS AND WALLS.
7. EXISTING FIXTURES AND EQUIPMENT THAT ARE REMOVED SHALL REMAIN
THE PROPERTY OF THE OWNER. IF SAID FIXTURES AND EQUIPMENT IS NOT
DESIRED BY OWNER, IT SHOULD BE DISPOSED.
8. DEMOLITION AROUND COLUMNS AND OF FIRE RATED ENCLOSURES NEED TO
BE VERIFIED BY THE ARCHITECT.
9. ALL DIMENSIONS GIVEN ON DEMOLITION DRAWING ARE TO BE FIELD
VERIFIED AND COORDINATED AGAINST NEW CONSTRUCTION PLANS.
10. REMOVE EXISTING FLOORING, ADHESIVE & BASE THROUGHOUT
CONSTRUCTION LIMITS. PROVIDE A CLEAN SURFACE READY TO RECEIVE
NEW FLOOR FINISH MATERIALS.
11. REMOVE EXISTING CEILINGS, SOFFITS AND CEILING MOUNTED EQUIPMENT
WHERE NEW CEILING FINISHES ARE SPECIFIED.
Reference:
N
PLAN NORTH
KEY PLAN
Revisions:
No. Date:
Description:
Graphic
Scale
Project
Number
210105.00
Set
Type
BID SET
Date
Issued
1/05/2023
2 - A100 Sheet
Number
OFFICE
284.1
ACT-2
9' - 0"
GWB-1
9' - 0"
12' - 0"
EQ
EQ
NON-JURY
COURTROOM
284
ACT-2
10' - 6"
5
1 - A400
GWB-1
9' - 0"
1 THIRD FLOOR - CEILING PLAN
1/4" = 1'-0"
REFLECTED CEILING GENERAL NOTES
1. SEE ROOM FINISH SCHEDULE, SHEET A401, FOR ADDITIONAL
INFORMATION ON CEILING MATERIAL TYPES.
2. SEE ELECTRICAL DRAWINGS FOR LIGHT FIXTURE TYPES,
LOCATIONS AND OTHER DEVICES.
3. SEE MECHANICAL DRAWINGS FOR SUPPLY AND RETURN
GRILLE TYPES AND LOCATIONS.
4. FOR ADDITIONAL WALL REINFORCING SEE STRUCTURAL
DRAWINGS AND SECURITY PLAN KEY.
5. SEE WALL TYPES, SHEET A100, FOR ACTUAL WALL
THICKNESS AND TYPES.
6. SEE CODE REVIEW SHEET G100 FOR ADDITIONAL WALL
CONSTRUCTION REQUIREMENTS.
7. ALL WALLS FROM CONCRETE FLOOR TO UNDERSIDE OF
FLOOR OR ROOF STRUCTURE ABOVE UNLESS OTHERWISED
INDICATED.
8. SEE FIRE PROTECTION DRAWINGS FOR FIRE PROTECTION
SPRINKLER HEAD LOCATIONS, TYPES AND SYSTEMS.
REFLECTED CEILING LEGEND
ACT-2
24" X 48" ACOUSTICAL LAY-IN
CEILING TILE
GWB-1
GYPSUM BOARD CEILING
LIGHT FIXTURE
STRIP FIXTURE
DOWNLIGHT FIXTURE
SURFACE MOUNTED LIGHT
FIXTURE
SPRINKLER HEAD - PENDANT
CONCEALED SPRINKLER HEAD
SPRINKLER HEAD - UPRIGHT
SUPPLY GRILLE
RETURN/EXHAUST
Reference:
N
PLAN NORTH
KEY PLAN
Revisions:
No. Date:
Description:
Graphic
Scale
Project
Number
210105.00
Set
Type
BID SET
Date
Issued
1/05/2023
2 - A200 Sheet
Number
6
2 - A400
SSM-1
10
2
-
A400
9 WEST ELEVATION - THIRD FLOOR
3/8" = 1'-0"
PT-1
WDT-1
WVP-1
A6
SSM-1
T econit Copyrgi 207ht
SIM
9
2
-
A400
3rd Floor
130' - 0"
INTERIOR KEYNOTES THIRD FLOOR
KEY
DESCRIPTION
22 3'-0" DIA. HIGH DENSITY URETHANE STATE SEAL MOUNTED ON WALL.
24 SOLID CORE WOOD GATE, STAINED TO MATCH RAIL. HARDWARE BY
MILLWORK SUPPLIER.
WDT-1
PT-1
WDT-1
WVP-1
RB-1
EQ
WDT-1
22
WVP-1
9'-2"
WDT-1
PT-1
TV (NIC)
6
2 - A400
WDT-1
WVP-1
RB-1
EQ
3rd Floor
130' - 0"
8 NORTH ELEVATION - THIRD FLOOR
3/8" = 1'-0"
Reference:
N
PLAN NORTH
KEY PLAN
PT-1
TV (NIC)
WDT-1
RB-1
PT-1
WVP-1
6
2 - A400
PT-1
WDT-1
WVP-1
SSM-1
10
2
-
A400
3rd Floor
130' - 0"
6
2 - A400
PT-1
WDT-1
WVP-1
RB-1
3rd Floor
130' - 0"
7 EAST ELEVATION - THIRD FLOOR
3/8" = 1'-0"
SSM-1
WVP-1
WB-1
EQ
24
WVP-1
3'-0"
10
2 - A400
SSM-1
WVP-1
WB-1
EQ
5 GALLERY WALL THIRD FLOOR
3/8" = 1'-0"
6 SOUTH ELEVATION - THIRD FLOOR
3/8" = 1'-0"
Revisions:
No. Date:
Description:
3rd Floor
130' - 0"
9 SIM
2 - A400
SSM-1
WVP-1
WB-1
3'-7"
3rd Floor
130' - 0"
9 SIM
2 - A400
SSM-1
WVP-1
WB-1
6'-7"
3rd Floor
130' - 0"
4 CLERK'S SIDE WALL THIRD FLOOR
3/8" = 1'-0"
3 CLERK'S FRONT WALL THIRD FLOOR
3/8" = 1'-0"
9 SIM
2 - A400
SSM-1
9 SIM
2 - A400
SSM-1
WVP-1
WB-1
3'-3"
3rd Floor
130' - 0"
2 WITNESS FRONT WALL THIRD FLOOR
3/8" = 1'-0"
WVP-1
WB-1
4'-7"
3rd Floor
130' - 0"
Graphic
Scale
Project
Number
210105.00
Set
Type
BID SET
1 COMMISSIONER FRONT WALL THIRD FLOOR
Date
Issued
1/05/2023
3/8" = 1'-0"
2 - A300 Sheet
Number
8"
3/4" 1/2"
BACKER AS
REQUIRED
SSM-1 CAP
5/8" PLYWOOD SHEATHING
WALL TYPE PER PLANS.
LEVEL 3 BULLET RESISTANT
SHEATHING
WOOD VENEER PANEL
8 ENLARGED CAP DETAIL (THIRD FLOOR)
3" = 1'-0"
SSM-1
CAP RAIL
8
2
-
WOOD PANELS EACH SIDE,
A400
WVP-1
SQUARE SUPPORT POST-SEE
FOR LOCATIONS
5/8" PLYWOOD SHEATHING EACH
SIDE
FLOOR SLEEVE WITH
COVER. TOP TO BE FLUSH
WITH ADJACENT FINISHED
FLOOR.
WOOD BASE
CONCRETE FLOOR OR
TOPPING
7
2
-
A400 100' - 0"
10 SECTION THRU GALLERY RAIL (THIRD FLOOR)
1 1/2" = 1'-0"
SSM-1
CAP RAIL
WOOD PANELS EACH SIDE,
WVP-1
SQUARE SUPPORT POST-SEE
FOR LOCATIONS
3/4" PLYWOOD SHEATHING EACH
SIDE
LEVEL 3 BULLET RESISTANT
SHEATHING.
FLOOR SLEEVE WITH
COVER. TOP TO BE FLUSH
WITH ADJACENT FINISHED
FLOOR.
8
2
-
A400
2' - 8"
1/2" SOLID
SURFACE
COUNTERTOP
COUNTER TOP
SUPPORT BRACKET
30" O.C.
WOOD BASE
CONCRETE FLOOR OR
7
TOPPING
2
100'-0"
-
A400
9 SECTION THRU Cx BENCH (THIRD FLOOR)
1 1/2" = 1'-0"
WALL TYPE PER PLANS.
LEVEL 3 BULLET RESISTANT
SHEATHING
PLASTIC LAMINATE PANEL
1/2"
BELOW C.TOP
WOOD BASE
7 ENLARGED BASE DETAIL (THIRD FLOOR)
3" = 1'-0"
WALL TYPE PER PLAN
3/4"
HARDWOOD TRIM - SEE ELEVATIONS
FOR HEIGHT
VENEER
6 WOOD TRIM DETAIL (THIRD FLOOR)
1 1/2" = 1'-0"
UNDERSIDE OF FLOOR OR
ROOF STRUCTURE
BRACE BACK TO STRUCTURE
3 5/8" METAL STUD FRAMING - FASTEN
METAL STUD TRACK TO UNDERSIDE OF
STRUCTURE ABOVE
5/8" GYPSUM BOARD ON 3 5/8" MTL.
STUDS 16" O.C
VARIES A.F.F
SEE RCP, A200
SUSPENDED ACT CEILING - SEE
REFLECTED CEILING PLAN,
VARIES- SEE RCP, A200
METAL CORNER BEAD
- TYPICAL
SUSPENDED ACT CEILING - SEE
REFLECTED CEILING PLAN,
5 CEILING BULKHEAD (THIRD FLOOR)
1 1/2" = 1'-0"
Reference:
N
PLAN NORTH
KEY PLAN
PER WALL TYPE
WALL PROTECTION WHERE NOTED ON
INTERIOR ELEVATIONS OR ROOM
FINISH SCHEDULE OR BOTH.
REFER TO PLAN FOR WALL TYPES.
METAL STUD BOX LINTEL FOR
OPENINGS ≥ 42".
METAL RUNNER TRACK ONLY
FOR OPENINGS < 42".
SEALANT TYP. BOTH SIDES
FRAME AS SCHEDULED.
DOOR AS SCHEDULED.
PER WALL TYPE
WALL PROTECTION WHERE
NOTED ON INTERIOR ELEVATION
OR ROOM FINISH SCHEDULE OR
BOTH.
REFER TO PLAN FOR WALL TYPES.
DBL. STUDS @ JAMBS. TYP.
SEALANT TYP. BOTH SIDES
FRAME AS SCHEDULED.
(3) ANCHORS PER JAMB. TYP.
DOOR AS SCHEDULED.
EQ
5 3/4"
EQ
WALL PER WALL TYPES.
BOND BEAM PER STRUCTURAL.
CONTINUOUS PERIMETER SEALANT
BOTH SIDES.
HOLLOW METAL FRAME. GROUT
SOLID.
DOOR AS SCHEDULED.
EQ
5 3/4"
EQ
WALL TYPE PER PLANS.
STRAP ANCHORS AS REQUIRED.
CONTINUOUS PERIMETER SEALANT
BOTH SIDES.
HOLLOW METAL FRAME. GROUT
SOLID.
DOOR AS SCHEDULED.
4 HM DOOR HEAD (THIRD FLOOR)
1 1/2" = 1'-0"
3 HM DOOR JAMB AT GWB (THIRD FLOOR)
1 1/2" = 1'-0"
2 HM HEAD 4" @ CMU (THIRD FLOOR)
1 1/2" = 1'-0"
1 HMU DOOR JAMB AT CMU (THIRD FLOOR)
1 1/2" = 1'-0"
Revisions:
No. Date:
Description:
Graphic
Scale
Project
Number
210105.00
Set
Type
BID SET
Date
Issued
1/05/2023
2 - A400 Sheet
Number