41--Temperature Conditioning Trailer
Program Summary
Title: 41--Temperature Conditioning Trailer
GovCB Opps ID : ADP12191915240000958
Document Type: Presolicitation (Modified)
FSC Code: 41 - Refrigeration, Air Conditioning and Air Circulating Equip.
Set Aside: N/A
Solicitation No.: N0017808Q1280
Source: https://www.fbo.gov/?s=opportunity&mode=form&id=30480bfbf227dccebb499ce47886ef40&tab=cor...
Posted Date:
Aug 19, 2008
Last Update: Aug 28, 2008
Due Date: Aug 21, 2008

Description
41--Temperature Conditioning Trailer
Solicitation Number: N0017808Q1280
Agency: Department of the Navy
Office: Naval Sea Systems Command
Location: NSWC Dahlgren Division
  • Print
  • Link
    Copy or Bookmark this Page

    Copy the url below for a direct link to this page.

    Bookmark this page by right-clicking here and choosing "Bookmark This Link..."

Opportunity History
Solicitation Number:
N0017808Q1280
Notice Type:
Presolicitation
Synopsis:
Added: Aug 12, 2008 3:13 pm Modified: Aug 19, 2008 3:33 pmTrack Changes
The purpose of Modification 0001 is to provide answers to the questions received in response to N00178-08-Q-1280, as follows:

1. The chamber temperature requirements state 50 deg F to positive 160 deg F. Is this accurate or should it be negative 50 deg F to positive 160 deg F?

The range should be negative 50 degrees F to positive 160 degrees F.

2. What is considered the live load in the requirements for the floor capacity? We understand it to be a fixed non moving mass. Please clarify if the load is giving off heat for btu design considerations.

Yes, live load is a fixed, non-moving mass. The load should not generate any heat.



3. Is the conditioning system condenser to be water or air cooled?

The condenser should be air-cooled.



4. Is there an output format for the data that is downloaded from the USB port on the logging device?

Any format should be acceptable as long as we know what to expect.

5. Are the power requirements at 60 or 50 hertz?

The power should operate at 60 Hz.

6. I understand that delivery date for the unit is Sep 30, 2008. Is this the correct date?

Yes, delivery is required NLT 30 September 2008.

7. The chamber temperature range is positive 50 degrees F to positive 160 degrees F. Is this correct?

No, the range should be negative 50 deg F to positive 160 deg F.

8. There is no heating or cooling performance stated?

There are no specific heating and cooling requirements beyond what is necessary to meet the temperature specifications.

9. Can the heating elements and cooling evaporator be located in a conditioning pleum with air circulation, in the chamber, separated from the work space by a shroud?

As long as the heating elements and condenser are isolated from the test items, a shroud may be acceptable.

10. The heating elements are not required to be temperature limited?

As long as the temperature performance is within the given specifications (range and accuracy), the temperature of the heating elements should not need to be limited.

NOTE: The closing date of this synopsis has NOT changed. Quotations are due 21 August 2008 no later than 2:00pm local NSWCDD time (EDST) to Naval Surface Warfare Center, Dahlgren Division, 17632 Dahlgren Road, Suite 157, Dahlgren, VA 22448-5110 at Building 183, First Floor, Room 102A. Quotations may also be faxed to (540) 653-7088 or email to DLGR_NSWC_XDS11@navy.mil.
Contracting Office Address:
N00178 NAVAL SURFACE WARFARE CENTER, DAHLGREN DIVISION 17632 DAHLGREN ROAD, DAHLGREN VA 22448-5110
Point of Contact(s):
XDS115 540-284-0708
General Information
Notice Type:
Presolicitation
Original Posted Date:
August 12, 2008
Posted Date:
August 19, 2008
Response Date:
August 21, 2008
Original Response Date:
August 21, 2008
Archiving Policy:
Automatic, on specified date
Original Archive Date:
December 31, 2008
Archive Date:
December 31, 2008
Original Set Aside:
N/A
Set Aside:
N/A
Classification Code:
41 -- Refrigeration, air-conditioning & air circulating equipment
NAICS Code:
333 -- Machinery Manufacturing/333415 -- Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing




Home - Browse By Keyword - Browse By Region - About Us - Privacy Policy - Terms of Use - Sitemap - Help
Copyright 2004 GovCB.com All rights reserved