The purpose of this modification is to replace the specifications in the previous synopsis with the performance requirements listed below:
Evaporative Cooling Tower System Performance Requirements
The contractor shall provide two (2) independent induced draft cooling towers capable of cooling "at least" 375 Gallons per Minute (GPM) from 95 degrees F to 85 degrees F with a 78 degrees F entering wet bulb temperature "Minimum" with the following minimum performance specifications.
1. Shall provide 180 tons of cooling2. Shall provide heat load for a grand total of 2,166,400 BTU/hour3. Shall maintain a constant equipment inlet water temperature of no greater than 65 degrees F 4. Evaporative cooling tower system shall have back up or secondary circulation capabilities 5. Main refrigeration system shall have back up or secondary pump system. 6. All electronics shall have back up or secondary systems for emergency operation7. Shall meet California Energy efficiency standards 8. Shall meet California EPA noise and refrigeration standards9. Controller workstation system requirements:a. shall be capable to run full diagnostics of all systemsb. shall provide complete read out of entire operational running parameters on clear, easy to read display screenc. controller workstation operator must have full function control of entire system operation from the controller workstationd. shall provide monitoring of refrigerant pressures and temperatures, water temperatures, voltage, amp draw, kW demand, alarm history, and captured data at time of alarm condition, demand profile with kW usage10. Shall have full manufacture warranty.
Solicitation 1
Sensitive/Secure Package:
no
Posted Date:
September 5, 2008
Description: See Solicitation
Contracting Office Address:
N68936 NAVAL AIR WARFARE CENTER WEAPONS DIVISION DEPT.1 Naval Air Warfare Center Weapons Division Dept.1 429 E. Bowen Rd - Stop 4015 China Lake, CA
|
General Information
Notice Type:
Solicitation
Original Posted Date:
August 13, 2008
Posted Date:
September 5, 2008
Response Date:
September 12, 2008
Original Response Date:
September 12, 2008
Archiving Policy:
Automatic, on specified date
Original Archive Date:
August 18, 2009
Archive Date:
September 4, 2009
Classification Code:
41 -- Refrigeration, air-conditioning & air circulating equipment
NAICS Code:
541 -- Professional, Scientific, and Technical Services/541330 -- Engineering Services
|